Filter drier or liquid line is cold or frosted
Frost on the filter drier or liquid line: a clogged filter drier, a throttling valve and pressure drop in the line.
Choose “Save as PDF” in the print dialog.
The liquid line should be at about ambient temperature or slightly above. If it turns cold, sweaty or frosted at one point ahead of the expansion valve, the pressure drops there and the refrigerant starts to boil: a restriction. Measure the temperature before and after the component; a difference of more than about 2 K across a filter drier indicates clogging [1][2].
Confirm the fault first
Measure the liquid line temperature before and after each component: filter drier, solenoid valve, shut-off valve and sight glass. Where the temperature drops is where the restriction is.
📏 Measurement guide: calculate superheat and subcooling 🔢 Alarm and fault codes
Troubleshoot step by step
Flowchart
Causes, most likely first
The order is approximate and based on common faults in the field. Always measure before replacing anything.
- 1Flowchart A
The filter drier is clogged by dirt, moisture or acid.
Remedy: Replace the filter drier. Find out where the dirt comes from; if there is acid or repeated replacements, check the oil.
🛠 How do I do it? Step by step
Only qualified personnel may work on refrigeration and electrical systems. Follow the manufacturer's manual and local rules; the steps are guidance, not a replacement for training.
Replace a filter drier
Replace the filter drier after moisture, a compressor burnout, a restriction across the drier or whenever the circuit has been opened. Work on the refrigerant circuit requires F-gas certification; brazing is hot work.
- Isolate or recover the refrigerant. Pump down or close valves to isolate the drier section where the system allows, otherwise recover the refrigerant with a recovery unit into a marked recovery cylinder. Break the vacuum with dry nitrogen to just above atmospheric pressure before opening. With A2L/A3 refrigerants purge with nitrogen and check with a gas detector.
✓ Check: The section reads slightly above 0 bar(g) on nitrogen and the pressure does not rise (no refrigerant left).
- Choose the right drier. Use a drier of the same size or larger, with connections and capacity for the refrigerant. After a burnout or acid in the oil use a burnout (acid-removing) type and plan to replace it again after the clean-up; after moisture choose one with ample water capacity.
✓ Check: The new drier matches the refrigerant, size and situation, and its arrow follows the flow direction.
- Cut out the old drier. Cut the pipes with a pipe cutter (never a hacksaw, which leaves filings) and deburr with the pipe end held downward. Keep the new drier capped until just before fitting.
✓ Check: Pipe ends are round, clean and burr-free.
- Braze with nitrogen flowing. Get a fire permit, have an extinguisher at hand and remove flammable material. Purge a low flow of dry nitrogen through a regulator while brazing, and cool the drier body with a wet cloth so the desiccant is not overheated. Never use oxygen or compressed air. Flare driers are fitted with torque spanners instead.
✓ Check: Clean joints with full penetration, and no black oxide scale inside the pipe ends.
- Pressure test with nitrogen. Pressurise with dry nitrogen through a regulator to the test pressure for the system, never above PS, and leak test the new joints.
✓ Check: The pressure holds and no leak is found at the joints.
- Evacuate, charge and record. Evacuate with a micron gauge to the manufacturer's level (commonly below 500 micron/0.67 mbar), close off the pump and check that the vacuum holds. Charge the specified amount by weight and record the work and refrigerant amounts in the logbook.
✓ Check: The vacuum holds, the charge is weighed in and the logbook entry is complete.
Test the oil for acid
Acid and moisture in the oil follow a motor burnout, overheating or a wet system, and they destroy a new compressor quickly. An acid test tells you whether the oil and drier must be changed and when the clean-up is finished.
- Choose the right kit. Use an acid test kit made for the oil in the compressor (POE, PAG, mineral or PAO; see the compressor nameplate). Check the expiry date. Wear goggles and gloves: burnt oil is acidic and the reagent is a chemical; follow its safety data sheet.
✓ Check: The kit matches the oil type and is within its expiry date.
- Take the oil sample. Take the sample from the compressor's oil drain or sampling valve, opening it slowly with low pressure in the crankcase and the sample bottle held firmly. On a hermetic compressor without a valve, the refrigerant must be recovered first and the oil drained from a removed compressor; that work requires F-gas certification (EPA 608 in the USA). Let the first few drops run to waste.
✓ Check: The clean bottle holds the amount the kit asks for, without refrigerant foaming over.
- Look at and smell the oil. Before testing, judge the oil by eye: clean oil is clear and light. Dark or black oil, a sharp burnt smell, sludge or metal particles point to a burnout or mechanical wear.
✓ Check: Colour, smell and any particles are noted.
- Run the test. Mix the oil and the reagent exactly as the kit instructions say (amounts, shaking time, waiting time).
✓ Check: The mixture has stood for the time stated in the kit instructions.
- Read the result against the kit chart. Compare the colour with the chart supplied with the kit. The colours differ between makes, so use only that kit's chart, never colours remembered from another brand.
✓ Check: The result is read as 'acceptable' or 'acid' according to the kit's own chart.
- Decide and record. If the oil is acidic: change the oil, fit a burnout filter drier (suction and liquid line) and repeat the test after some operating time until it passes. Record the result, the action and the date in the logbook.
✓ Check: The logbook shows the test result, the action taken and when the next test is due.
- Isolate or recover the refrigerant. Pump down or close valves to isolate the drier section where the system allows, otherwise recover the refrigerant with a recovery unit into a marked recovery cylinder. Break the vacuum with dry nitrogen to just above atmospheric pressure before opening. With A2L/A3 refrigerants purge with nitrogen and check with a gas detector.
- 2Flowchart B
A valve in the liquid line throttles.
Remedy: Open the shut-off valve fully. Check that the solenoid valve opens fully (coil and voltage) and that the strainer ahead of it is clean.
🛠 How do I do it? Step by step
Only qualified personnel may work on refrigeration and electrical systems. Follow the manufacturer's manual and local rules; the steps are guidance, not a replacement for training.
Check valve positions and trapped liquid
A service or shut-off valve left closed or half open gives symptoms like a restriction or a low charge, and liquid shut in between closed valves can burst the pipe when it warms up. Wear goggles and gloves and never exceed the system PS.
- Go through the circuit with the diagram. Follow the flow diagram and list every service valve, ball valve and king valve from the compressor through condenser, receiver, liquid line, evaporators and suction line.
✓ Check: You have a list of all valves and their required position in normal operation.
- Check the service valves. With a valve key, check that suction, discharge and liquid service valves are fully open (back-seated). Turn slightly off the back seat only while a gauge is connected. Refit the caps afterwards.
✓ Check: Spindles are fully open and caps are tight.
- Look for partly closed valves. With the system running, measure pipe temperature before and after each valve on the liquid line with a clamp thermometer. A clear temperature drop, frost or sweating after a valve means it is partly closed or restricted.
✓ Check: There is no noticeable temperature drop across any valve in the liquid line.
- Check the solenoid valves. Check that solenoid valves open on a call: the coil is energised (magnet tester or voltage on the coil) and there is flow (temperature change after the valve).
✓ Check: Each solenoid valve opens when it is called and closes when it is not.
- Never trap liquid. Before closing two valves on a liquid-filled section, pump the liquid out or make sure the section has a pressure relief path (relief valve or open path to the receiver). Never leave a liquid line closed at both ends.
✓ Check: Every section that can be closed in is empty or has a relief path.
- CO2: check standstill protection. On R744 systems, confirm that the standstill unit, the relief valves and any pressure-holding function are in service before valves are closed, because the pressure of trapped CO2 rises quickly as it warms (see the CO2 standstill guide).
✓ Check: The standstill pressure stays well below PS and the relief valves are open to their outlet.
Check a solenoid valve (liquid line or hot gas)
A solenoid valve that does not open starves the evaporator (low pressure, warm room); one that does not close lets refrigerant through when it should not (pump-down fails, flooding, or hot gas leaking into the evaporator). Check the coil first, then the valve itself.
- Find out whether the valve should be open. Read in the controller or the wiring diagram when the valve is energised (for example with cooling demand, during pump-down or during hot gas defrost). Compare with what the system does right now.
✓ Check: You know whether the valve should be open or closed at this moment.
- Check that the coil gets voltage. Measure the voltage across the coil terminals when the valve should be open. Hold a steel screwdriver blade near (not touching) the top of the coil: a live coil pulls it slightly. Check that the coil voltage on its label matches the supply.
✓ Check: The coil has the rated voltage (label) when the valve should be open; if not, the fault is upstream: thermostat, controller output, contactor, fuse or wiring.
- Check the coil itself. Isolate and lock off, prove dead, and disconnect the coil. Measure its resistance and compare with the manufacturer's value; look for a burnt smell, discolouration or a cracked coil. Make sure the coil is the right type for the valve body and sits fully down on the armature tube with its nut tight.
✓ Check: Coil resistance matches the data (an open circuit or a very low value means a faulty coil), and the coil is the right one and correctly fitted.
- Check that the valve opens. With the coil energised and the system running, measure the temperature on both sides of the valve with clamp thermometers. An open valve has (almost) the same liquid temperature on both sides; a clear temperature drop or frost after the valve means it is not opening fully or is restricted. Check the flow direction arrow on the valve body.
✓ Check: Little or no temperature difference across the valve when it should be open, and it is fitted in the direction of the arrow.
- Check that the valve closes. De-energise the coil (or let the controller close it) and watch what happens: on a pump-down system the suction pressure must fall and the compressor must stop on the low pressure switch and stay off; a hot gas valve must leave the line after it cool during the freeze or cooling cycle.
✓ Check: The system pumps down and stays down, or the line after a hot gas valve stays cool; a valve that leaks through must be repaired or replaced.
- Repair or replace. A faulty coil can be changed without opening the circuit. If the valve body leaks or sticks, opening the circuit is work for certified personnel: recover the refrigerant, replace the valve (or its internal parts) with nitrogen flowing while brazing, pressure test with dry nitrogen, evacuate and charge by weight. Protect the valve from heat while brazing as the manufacturer describes.
✓ Check: The valve opens and closes as it should, there is no leak at the new joints, and the work is recorded in the logbook where the refrigerant rules require it.
- Go through the circuit with the diagram. Follow the flow diagram and list every service valve, ball valve and king valve from the compressor through condenser, receiver, liquid line, evaporators and suction line.
- 3Flowchart C
A restriction in the pipe itself (pinched pipe, sharp bend) or pressure drop in a long or high liquid riser.
Remedy: Follow the line and feel where the cold begins. Troubleshoot the bubbles in the sight glass and check subcooling.
🛠 How do I do it? Step by step
Only qualified personnel may work on refrigeration and electrical systems. Follow the manufacturer's manual and local rules; the steps are guidance, not a replacement for training.
Find a restriction in the liquid line
A partly blocked filter drier, strainer or valve makes the liquid flash and starves the evaporator. Pressure drop shows up as a temperature drop at the restriction.
- Confirm the symptoms. In stable operation, measure superheat and subcooling. A restriction typically gives high superheat and low suction pressure while subcooling before the restriction is normal or high.
✓ Check: The measurements fit a restriction rather than a simple shortage of refrigerant.
- Look and feel along the line. Follow the liquid line from the condenser or receiver. Look for sweating or frost and feel for a cold spot right after a component. Wear gloves against cold burns.
✓ Check: You have found any spot that is clearly colder than the line before it.
- Measure across each component. Clamp thermometers before and after the filter drier, solenoid valve, strainer, sight glass and shut-off valves, one component at a time.
✓ Check: The temperature is the same on both sides of a free component; a noticeable drop of more than a degree or two marks the restriction.
- Measure the pressure drop. Where there are service ports before and after the filter drier or valve, measure the pressure on both sides and compare with the maker's permitted pressure drop.
✓ Check: The pressure drop is within the maker's data, or the component is confirmed as restricted.
- Check the sight glass and valves. Bubbles after a component but clear liquid before it point to that component. Check that hand and shut-off valves are fully open and that the solenoid valve opens fully when energised.
✓ Check: All valves are fully open and you know where flashing starts.
- Repair. Replacement opens the circuit and needs F-gas certified personnel: pump down or recover, never trap liquid between closed valves (especially CO2), braze with nitrogen flowing, pressure test, evacuate and recharge by weight.
✓ Check: After repair there is no temperature drop across the component and superheat is back to normal.
Measure subcooling
Subcooling shows how much the liquid is cooled below its condensing temperature. Together with superheat it helps judge the charge and the condenser.
- Run until stable. Let the system run at steady load for at least 15 minutes, not during or just after a defrost. Check that the condenser is clean and its fans run.
✓ Check: Pressures and temperatures are steady.
- Measure the liquid pressure. Connect a gauge to the port at the condenser outlet or on the liquid line (see the guide on connecting gauges). Wear goggles and gloves.
✓ Check: You have a steady liquid pressure.
- Measure the liquid temperature. Clamp a thermometer on clean pipe at the same place as the pressure reading and insulate the probe.
✓ Check: You have a steady pipe temperature from the same place.
- Convert and calculate. Convert the pressure to saturation temperature for the refrigerant (bubble point for zeotropic blends). Subcooling = saturation temperature − measured liquid temperature.
✓ Check: You have a subcooling value in K.
- Compare with the target. Compare with the manufacturer's target for the system. In systems with a receiver, subcooling at the receiver outlet is normally small and says little about the charge. On transcritical CO2 there is no subcooling on the high side; use the gas cooler outlet temperature and pressure instead.
✓ Check: You know whether the value is low, normal or high for this system type.
- Interpret with care. Low subcooling with high superheat can mean too little refrigerant or a restriction; high subcooling with high condensing pressure can mean overcharge or non-condensables. Never add refrigerant to try: leak test first, repair, recover and weigh in the correct charge (F-gas certified personnel).
✓ Check: The conclusion is supported by superheat and pressures, not by subcooling alone.
Read the sight glass and moisture indicator
The sight glass shows whether the liquid line is full of liquid, and the moisture indicator whether the refrigerant is dry. Both must be read in stable operation and together with other measurements.
- Check marking and position. Check that the sight glass is marked for the refrigerant in the system and its pressure, and that it sits in the liquid line after the filter drier.
✓ Check: Marking and position are correct; otherwise the colour reading cannot be trusted.
- Run until stable. Let the system run at steady load for at least 15 minutes, not just after start, a defrost or a capacity step. Wipe the glass and light it with a torch.
✓ Check: Pressures and temperatures are steady and you can see clearly into the glass.
- Read the moisture indicator. Compare the indicator colour with the colour scale printed on the sight glass ring. Colours differ between makers (often green for dry and yellow for wet). The indicator reacts slowly: after a drier change it can take many hours to show the true value.
✓ Check: The colour matches the 'dry' field on the scale; a 'wet' colour means moisture in the system.
- Read the liquid. Look for a full, clear liquid column, foam or streams of bubbles. Note that a completely clear glass can also mean it is full of vapour in a nearly empty system; confirm with subcooling.
✓ Check: You can say whether the glass is full of liquid, and subcooling confirms it.
- Judge the bubbles. Bubbles are normal at start, after defrost, during capacity changes and when the liquid flashes because of pressure drop, a vertical lift or warm surroundings. Persistent bubbles in stable operation call for a subcooling measurement and a check for restriction before you suspect undercharge.
✓ Check: You know whether the bubbles come from the operating state, a restriction or too little refrigerant.
- Act on the result. Moisture: find the cause (leak, poor evacuation), replace the filter drier and evacuate. Too little refrigerant: never add refrigerant to clear bubbles; leak test, repair, recover and weigh in the correct charge. Work that opens the circuit needs F-gas certified personnel.
✓ Check: After the action the glass is full of liquid in stable operation and the indicator returns to 'dry'.
- Confirm the symptoms. In stable operation, measure superheat and subcooling. A restriction typically gives high superheat and low suction pressure while subcooling before the restriction is normal or high.
- 4
The liquid line runs through a cold space or touches the suction line and is cooled from outside.
Remedy: Measure the pressure before and after: if it is the same there is no restriction. Insulate or move the line.
🛠 How do I do it? Step by step
Only qualified personnel may work on refrigeration and electrical systems. Follow the manufacturer's manual and local rules; the steps are guidance, not a replacement for training.
Find a restriction in the liquid line
A partly blocked filter drier, strainer or valve makes the liquid flash and starves the evaporator. Pressure drop shows up as a temperature drop at the restriction.
- Confirm the symptoms. In stable operation, measure superheat and subcooling. A restriction typically gives high superheat and low suction pressure while subcooling before the restriction is normal or high.
✓ Check: The measurements fit a restriction rather than a simple shortage of refrigerant.
- Look and feel along the line. Follow the liquid line from the condenser or receiver. Look for sweating or frost and feel for a cold spot right after a component. Wear gloves against cold burns.
✓ Check: You have found any spot that is clearly colder than the line before it.
- Measure across each component. Clamp thermometers before and after the filter drier, solenoid valve, strainer, sight glass and shut-off valves, one component at a time.
✓ Check: The temperature is the same on both sides of a free component; a noticeable drop of more than a degree or two marks the restriction.
- Measure the pressure drop. Where there are service ports before and after the filter drier or valve, measure the pressure on both sides and compare with the maker's permitted pressure drop.
✓ Check: The pressure drop is within the maker's data, or the component is confirmed as restricted.
- Check the sight glass and valves. Bubbles after a component but clear liquid before it point to that component. Check that hand and shut-off valves are fully open and that the solenoid valve opens fully when energised.
✓ Check: All valves are fully open and you know where flashing starts.
- Repair. Replacement opens the circuit and needs F-gas certified personnel: pump down or recover, never trap liquid between closed valves (especially CO2), braze with nitrogen flowing, pressure test, evacuate and recharge by weight.
✓ Check: After repair there is no temperature drop across the component and superheat is back to normal.
Connect gauges and read pressures
Correct pressures are the basis of almost every fault diagnosis. Connect the gauges so that no refrigerant is released and the reading can be trusted.
- Choose gauges and protection. Check the refrigerant and the system PS on the nameplate. Choose gauges and hoses rated above PS and suitable for the refrigerant; CO2 needs at least 130 bar on the high side. Use tools rated for flammable refrigerants on A2L/A3 systems. Wear goggles and gloves.
✓ Check: Gauges and hoses are marked for the refrigerant and a pressure above the system PS.
- Inspect hoses and couplers. Check hose seals and that the low-loss couplers are closed. Zero the digital manifold at atmospheric pressure.
✓ Check: Seals are intact, couplers closed and the gauges read zero when open to air.
- Connect to the service ports. Remove the caps and fit the couplers to the suction port and the discharge or liquid port by hand, then open them. Keep away from ignition sources on A2L/A3 systems.
✓ Check: The couplers are tight and a leak detector finds nothing at the connections.
- Remove air from the hoses. Evacuate the hoses with a vacuum pump, or use short low-loss hoses that do not need purging. Never purge hoses by blowing refrigerant to the air.
✓ Check: No air is in the hoses and no refrigerant has been released.
- Read and convert. Read the pressures in stable operation and note whether they are gauge or absolute. Convert to saturation temperature for the right refrigerant: dew point for suction and bubble point for liquid with zeotropic blends. On CO2 above 31 °C / 73.8 bar (the critical point) there is no saturation temperature on the high side.
✓ Check: You have pressures and saturation temperatures for the correct refrigerant.
- Disconnect without loss. Close the couplers, remove them and refit the caps, which are a secondary seal. Leak test the ports.
✓ Check: The caps are on and no leak is detected at the ports.
- Confirm the symptoms. In stable operation, measure superheat and subcooling. A restriction typically gives high superheat and low suction pressure while subcooling before the restriction is normal or high.
Checks from the manufacturers’ manuals (2)
Values and checks the manufacturers give for their own products; they apply to the product named.
- Hussmann parallel racks: On a new installation the liquid drier and suction filter cores catch dirt in the first days; Hussmann replaces them 24 hours after start-up and again after 48 hours, and whenever the system has been opened.[3]
- Fujitsu split air conditioners and heat pumps: On Fujitsu splits, sweat or frost on the small (expansion) line at the outdoor unit usually means the system is undercharged.[4]
📝 Fill in a service report
Service report
Fill in and print, or save as PDF. The details are only stored in this browser.
Calculate it yourself
Terms in this article
Sources