| Name | kW |
|---|
The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.
| Pipe | Mass flow [kg/s] | Density [kg/m³] | Inner diameter [mm] | Velocity [m/s] | Re | Friction factor | Length (+ fittings) [m] | Δp [kPa] | Δp per metre [Pa/m] | Note |
|---|---|---|---|---|---|---|---|---|---|---|
| Liquid: Condenser → Cold Room 1 | 0.1152 | 1,062 | 14.1 | 0.695 | 83,800 | 0.0191 | 6 (+1.8) | 2.71 | 347 | 5/8" |
| Liquid: Cold Room 1 → Cold Room 2 | 0.06401 | 1,062 | 11.1 | 0.626 | 59,300 | 0.0206 | 6 (+1.8) | 3.02 | 387 | 1/2" |
| Liquid: Cold Room 2 → Display Case | 0.0256 | 1,062 | 6.31 | 0.771 | 41,600 | 0.0225 | 6 (+1.8) | 8.78 | 1,130 | 5/16" |
| Suction line: Compressor → Cold Room 1 | 0.1152 | 14.79 | 32.1 | 9.61 | 405,000 | 0.0142 | 6 (+1.8) | 2.36 | 303 | 1-3/8" |
| Suction line: Cold Room 1 → Cold Room 2 | 0.06401 | 14.79 | 26 | 8.13 | 278,000 | 0.0152 | 6 (+1.8) | 2.23 | 286 | 1-1/8" |
| Suction line: Cold Room 2 → Display Case | 0.0256 | 14.79 | 17.3 | 7.39 | 168,000 | 0.0168 | 6 (+1.8) | 3.07 | 394 | 3/4" |
| Hot gas: Compressor → Condenser | 0.1152 | 59.03 | 17.3 | 8.33 | 607,000 | 0.014 | 10 (+3) | 21.7 | 1,670 | 3/4" |
| Cold Room 1 · Liquid | 0.0512 | 1,062 | 11.1 | 0.501 | 47,400 | 0.0215 | 5 (+1.5) | 1.69 | 259 | 1/2" |
| Cold Room 1 · Suction line | 0.0512 | 14.79 | 26 | 6.5 | 222,000 | 0.0158 | 5 (+1.5) | 1.23 | 189 | 1-1/8" |
| Cold Room 2 · Liquid | 0.0384 | 1,062 | 7.9 | 0.738 | 49,900 | 0.0215 | 5 (+1.5) | 5.12 | 788 | 3/8" |
| Cold Room 2 · Suction line | 0.0384 | 14.79 | 19.9 | 8.32 | 218,000 | 0.016 | 5 (+1.5) | 2.67 | 411 | 7/8" |
| Display Case · Liquid | 0.0256 | 1,062 | 6.31 | 0.771 | 41,600 | 0.0225 | 5 (+1.5) | 7.31 | 1,130 | 5/16" |
| Display Case · Suction line | 0.0256 | 14.79 | 17.3 | 7.39 | 168,000 | 0.0168 | 5 (+1.5) | 2.56 | 393 | 3/4" |
ṁ = Q / (h″(t₀ + Δt_sh) − h′(t_liq))G = ṁ / A, v = G / ρ, Re = G·d / µf = 0.25 / [log₁₀(ε / (3.7·d) + 5.74 / Re^0.9)]² (Re ≥ 2300); f = 64 / Re (Re < 2300)Δp = f · (L·(1 + x) / d) · ρ·v² / 2 (gas: 50 steps, ρ ∝ p)Δp_static = ρ · g · h (riser)The calculator works out the mass flow from each evaporator's capacity and the refrigerant properties (CoolProp), then picks the smallest pipe that keeps the velocity below the target. Pressure drop is calculated with Darcy–Weisbach and shown in kPa and as saturation temperature drop (K). The results have been checked against Danfoss Coolselector 2.
Calculate it in the tool above
The defaults are 10 m/s in the suction line, 0.8 m/s in the liquid line and 12 m/s in the hot gas line. A higher velocity gives smaller pipes but more pressure drop, and suction risers also need enough velocity for oil return.
Calculate it in the tool above
Common guide values are about 1 K saturation temperature drop in the suction line and 0.5–1 K in the liquid and hot gas lines. The calculator converts every pressure drop to K and warns of flash gas when the liquid line drop exceeds the subcooling.
Calculate it in the tool above
Mark the line as a riser. The calculator then picks a size in which the gas is fast enough to carry the oil upwards (criterion j*g ≥ 0.85) and shows the minimum velocity. If even the smallest allowed size is too large, a double suction riser is suggested.
Calculate it in the tool above
R134a, R404A, R407C, R407F, R410A, R32, R448A, R449A, R452A, R454B, R454C, R455A, R513A, R1234yf and R1234ze(E). Temperatures are entered as dew points; for zeotropic blends the glide, bubble point and liquid temperature are worked out automatically.
Calculate it in the tool aboveGWP, ODP & CO2e of a refrigerant chargeRefrigerant retrofit: find alternatives