CO2 Pipe Sizing (R744)

Free pipe sizing tools for refrigeration and HVAC technicians, engineers and designers. Choose a calculator below – each one has its own help.

CO2 (R744) pipe sizing – copper →CO2 (R744) · 1/4″–6-1/8″ · standard, reinforced, K65 CO2 (R744) pipe sizing – steel →CO2 (R744) · DN10–DN300 · carbon steel, stainless HFC/HFO refrigerant pipe sizing →R404A, R448A, R449A, R134a, R32 and more · suction, liquid, hot gas HC (A3) refrigerant pipe sizing →R290, R600a, R1270, R170 and more · suction, liquid, hot gas Pipe routing on a floor plan →Floor plan (PDF, image, DXF) · pipes routed at right angles and sized · CO2, HFC, HC Heating, cooling & brine pipe sizing →Heating, cooling, brine · flow diagram, shunt groups, balancing Domestic water pipe sizing →Cold and hot water · probable flow · pressure at branch-offs Relief valve & discharge line (EN 13136 / EN ISO 24664) →Relief valve and discharge line · EN 13136 / EN ISO 24664 Capillary tube sizing →Fridges, freezers, small units · R600a, R290, R134a … · bore and length Cold room load →Coolers and freezer rooms · transmission, products, door, defrost · kW at the evaporating temperature GWP, ODP & CO2e of a refrigerant charge →GWP, ODP, tonnes CO2e · F-gas leak checks and bans Refrigerant retrofit: find alternatives →R404A, R134a, R22 … · alternatives ranked by suitability and GWP Troubleshooting: refrigeration and heat pumps →Symptom search · system diagram per machine type · step-by-step flowchart Knowledge base: laws and rules →F-gas, EN 378, leak checks · step-by-step guides · A–Z glossary Electrical calculator →Amps, watts, voltage drop, cable and fuse · motors Y/Δ · boats and ships Pipe insulation →Thickness against condensation · heat flow · minimum by country Project schedule (Gantt) →Gantt chart for projects · drag and drop · week numbers · dependencies

About CO2piping.com

CO2piping.com brings together free calculation tools for the refrigeration and HVAC trade: pipe sizing for CO2 (R744) in copper and steel, HFC/HFO and HC (A3) refrigerants, heating and cooling water and brine, domestic water and relief lines to EN 13136 / EN ISO 24664, plus GWP/CO2e under the F-gas Regulation and refrigerant retrofit. Every tool follows recognised standards, has printouts and is updated continuously.

Frequently asked questions

How do you size CO2 (R744) refrigeration pipes?

Pipes are chosen from the mass flow and the allowed velocity in each line: MT suction, LT suction and liquid. The calculator works out the mass flow from cooling capacity, evaporating temperature and superheat, picks the smallest pipe that meets the target velocity and shows the pressure drop (Darcy–Weisbach) section by section.

CO2 (R744) pipe sizing – copper →CO2 (R744) pipe sizing – steel →

Which pipes can handle CO2 system pressures?

Standard copper tube often cannot take the design pressure of a CO2 system. K65 (CuFe2P) is rated 120 bar from 3/8″ to 2-1/8″; larger sizes use steel such as P265NL or 316L stainless. The calculator warns with ⛔ when the chosen pipe type is not rated for the pressure you entered.

CO2 (R744) pipe sizing – copper →CO2 (R744) pipe sizing – steel →

What velocity should CO2 lines be sized for?

Common guide values are 8–12 m/s in suction lines and about 1 m/s in liquid lines. The calculator starts from 12 m/s and 1.2 m/s, and every value can be changed to suit the system's limits on pressure drop, noise and oil return.

CO2 (R744) pipe sizing – copper →CO2 (R744) pipe sizing – steel →

Which other tools does the site offer?

Besides CO2 in copper and steel, there are calculators for HFC/HFO and HC refrigerants (R290, R600a and others), heating and cooling water and brine, domestic water, safety valves and relief lines to EN 13136 / EN ISO 24664, GWP and CO2 equivalent under the F-gas Regulation, and conversion to another refrigerant. There are also tools for capillary tubes, pipe routing on a floor plan, electrical calculations, troubleshooting refrigeration and heat pumps, project schedules (Gantt) and a knowledge base on laws and standards.

HFC/HFO refrigerant pipe sizing →HC (A3) refrigerant pipe sizing →Pipe routing on a floor plan →Heating, cooling & brine pipe sizing →Domestic water pipe sizing →Relief valve & discharge line (EN 13136 / EN ISO 24664) →Capillary tube sizing →Cold room load →Pipe insulation →GWP, ODP & CO2e of a refrigerant charge →Refrigerant retrofit: find alternatives →Troubleshooting: refrigeration and heat pumps →Knowledge base: laws and rules →Electrical calculator →Project schedule (Gantt) →

Is it free, and do I need an account?

It is free and needs no login. Projects are saved as a file on your computer, and the printout gives a report and a flow diagram that fill an A4, A3 or A1 sheet.

[ Annonsering / Advertisement ]

About Us & Contact

The website co2piping.com is independently developed and operated to provide free, accessible, and technically precise calculation tools for the HVAC&R industry.

Contact & Support:
E-post: Co2Calc@proton.me

Privacy Policy

We value your privacy. This policy explains how information is collected and used on co2piping.com.

Cookies and Analytics:
This website uses cookies for visitor statistics (Google Analytics) and for advertising via Google AdSense. Consent is managed with Google's certified consent management platform in accordance with the ePrivacy rules and the EU General Data Protection Regulation (GDPR). You can change your choice via Cookie settings at the bottom of the page.

Third-Party Advertising:
Google and other third-party vendors use cookies to serve ads based on your prior visits to this or other websites. You may manage or revoke your consent anytime via the cookie banner at the bottom of the page.