| Pos. | Set pressure (gauge) (bar) | Connection (hose/pipe) | Required capacity Qmd (kg/h) | Qty | Valve capacity Qm (kg/h) | % of set | Status |
|---|---|---|---|---|---|---|---|
| V1 | 60.0 | DN10 | 500 | 1 | – | 9.6 % | OK |
| Flow in the common discharge line | 500 | ||||||
| Common discharge line to the outlet | DN15 · 10.0 m · 4 × 90° | ||||||
The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.
| Valve | Set pressure (bar) | Flow (kg/h) | Branch | Pressure at tee (bar) | Back pressure (bar) | % of set | Segment after tee | Kb | Inlet | Status |
|---|---|---|---|---|---|---|---|---|---|---|
| V1 | 60.00 | 500.0 | DN10 | 5.50 | 5.76 | 9.6 % | DN15 | 1.000 | 0.02 % | OK |
| Pipe | Mass flow [kg/s] | Density [kg/m³] | Inner Ø [mm] | Velocity [m/s] | Re | f | Length (+ equivalent) [m] | Δp [bar] | Δp/m [Pa/m] | Note |
|---|---|---|---|---|---|---|---|---|---|---|
| Inlet V1 | 0.1389 | 269.3 | 13.6 | 3.55 | 623,000 | 0.0271 | 0.1 (+0.251) | 0.0119 | 11,900 | 0.02 % / 3.0 % |
| Branch V1 | 0.1389 | 11.49 | 13.6 | 83.2 | 623,000 | 0.0271 | 0.3 | 0.264 | 88,100 | 9.6 % / 10 % |
| Common line V1 → outlet | 0.1389 | 2.482 | 17.3 | 238 | 490,000 | 0.0255 | 10 (+1.8) | 5.5 | 55,000 | choked · 5.50 bar |
Qm = 0.2883 · C · Kb · A · Kdr · √(p0/v0)C = 3.948 · √(κ · (2/(κ+1))^((κ+1)/(κ−1)))p1² − p2² = G² · R·T · (f·L/D + ΣK + 2·ln(p1/p2))p* = G · √(R·T) (choked end)Δp_inlet = (f·L/D + ΣK) · ρ·v²/2K_bend = 21.3 · fT (Crane TP-410)L_eq = ΣK · D / fFirst the required discharge capacity: for fire 10 kW/m² times the vessel's outer surface divided by the latent heat, otherwise the compressor flow or the heat input. EN 13136 then gives the valve area from Qm = 0.2883·C·Kb·A·Kdr·√(p0/v0) at the set pressure plus 10 %.
Calculate it in the tool above
Conventional safety valves usually allow at most 10 % of the set pressure; balanced valves allow more, as the maker states. The inlet line may lose at most 3 %. The calculator finds the discharge line back pressure with compressible flow and choking.
Calculate it in the tool above
Each valve's back pressure is checked with all valves relieving at once (fire) or one at a time. The segments between the tees carry the flow of the valves upstream and may differ in size; a common rule of thumb is a header area at least the sum of the branch areas.
Calculate it in the tool above
The pressures are high and on the high-pressure side CO2 is often supercritical, so the valve is sized for gas at a temperature. When CO2 expands below 5.2 bar dry ice forms, so the discharge line must be short and self-draining with no low points.
Calculate it in the tool above
Yes for HFC/HFO and CO2 if the pipe withstands the back pressure: refrigeration copper to EN 12735-1, or plumbing copper EN 1057 and press systems with fittings approved for the refrigerant. Copper is not allowed with ammonia; use steel or stainless.
Calculate it in the tool above
Often above 100 dB(A) near the outlet. The calculator estimates the noise to API 521 and picks a bigger line when a noise requirement is set; if that is not enough, move the outlet or fit a silencer.