| Name | Circuit | kW |
|---|
The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.
| Pipe | Mass flow [kg/s] | Density [kg/m³] | Inner diameter [mm] | Velocity [m/s] | Re | f | Length (+ allowance) [m] | Δp [kPa] | Δp per metre [Pa/m] | Pipe type, PS |
|---|---|---|---|---|---|---|---|---|---|---|
| #1 1/2" · Liquid: Refrigeration unit → Cold Room 1 | 0.1043 | 972.4 | 11.2 | 1.09 | 103,000 | 0.0185 | 6 (+1.8) | 7.44 | 954 | K65 · PS 60 bar |
| #2 1/2" · Liquid: Cold Room 1 → Freezer 1 | 0.07272 | 972.4 | 11.2 | 0.759 | 71,900 | 0.0198 | 6 (+1.8) | 3.87 | 496 | K65 · PS 60 bar |
| #3 3/8" · Liquid: Freezer 1 → Cold Room 2 | 0.05316 | 972.4 | 8.4 | 0.986 | 70,100 | 0.0201 | 6 (+1.8) | 8.84 | 1,130 | K65 · PS 60 bar |
| #4 3/8" · Liquid: Cold Room 2 → Freezer 2 | 0.02948 | 972.4 | 8.4 | 0.547 | 38,900 | 0.0226 | 6 (+1.8) | 3.06 | 392 | K65 · PS 60 bar |
| #5 3/8" · Liquid: Freezer 2 → MT Display Case | 0.01579 | 972.4 | 8.4 | 0.293 | 20,800 | 0.026 | 6 (+1.8) | 1.01 | 129 | K65 · PS 60 bar |
| #6 1/2" · MT Suction: Refrigeration unit → Cold Room 1 | 0.07103 | 70.26 | 11.2 | 10.3 | 584,000 | 0.0146 | 6 (+1.8) | 37.7 | 4,830 | K65 · PS 52 bar |
| #7 3/8" · MT Suction: Cold Room 1 → Cold Room 2 | 0.03946 | 70.26 | 8.4 | 10.1 | 433,000 | 0.0155 | 6 (+1.8) | 52 | 6,670 | K65 · PS 52 bar |
| #8 3/8" · MT Suction: Cold Room 2 → MT Display Case | 0.01579 | 70.26 | 8.4 | 4.05 | 173,000 | 0.0173 | 6 (+1.8) | 9.29 | 1,190 | K65 · PS 52 bar |
| #9 1/2" · LT Suction: Refrigeration unit → Freezer 1 | 0.03326 | 32.8 | 11.2 | 10.3 | 310,000 | 0.0157 | 6 (+1.8) | 19 | 2,430 | K65 · PS 30 bar |
| #10 3/8" · LT Suction: Freezer 1 → Freezer 2 | 0.01369 | 32.8 | 8.4 | 7.53 | 170,000 | 0.0174 | 6 (+1.8) | 15 | 1,920 | K65 · PS 30 bar |
| #11 3/8" · Line to Cold Room 1 · Liquid | 0.03157 | 972.4 | 8.4 | 0.586 | 41,600 | 0.0223 | 5 (+1.5) | 2.88 | 443 | K65 · PS 60 bar |
| #12 3/8" · Line to Cold Room 1 · MT Suction | 0.03157 | 70.26 | 8.4 | 8.11 | 346,000 | 0.0159 | 5 (+1.5) | 28.4 | 4,370 | K65 · PS 52 bar |
| #13 3/8" · Line to Cold Room 2 · Liquid | 0.02368 | 972.4 | 8.4 | 0.439 | 31,200 | 0.0237 | 5 (+1.5) | 1.72 | 265 | K65 · PS 60 bar |
| #14 3/8" · Line to Cold Room 2 · MT Suction | 0.02368 | 70.26 | 8.4 | 6.08 | 260,000 | 0.0164 | 5 (+1.5) | 16.5 | 2,540 | K65 · PS 52 bar |
| #15 3/8" · Line to MT Display Case · Liquid | 0.01579 | 972.4 | 8.4 | 0.293 | 20,800 | 0.026 | 5 (+1.5) | 0.84 | 129 | K65 · PS 60 bar |
| #16 3/8" · Line to MT Display Case · MT Suction | 0.01579 | 70.26 | 8.4 | 4.05 | 173,000 | 0.0173 | 5 (+1.5) | 7.74 | 1,190 | K65 · PS 52 bar |
| #17 3/8" · Line to Freezer 1 · Liquid | 0.01956 | 972.4 | 8.4 | 0.363 | 25,800 | 0.0247 | 5 (+1.5) | 1.23 | 189 | K65 · PS 60 bar |
| #18 3/8" · Line to Freezer 1 · LT Suction | 0.01956 | 32.8 | 8.4 | 10.8 | 243,000 | 0.0165 | 5 (+1.5) | 24.3 | 3,740 | K65 · PS 30 bar |
| #19 3/8" · Line to Freezer 2 · Liquid | 0.01369 | 972.4 | 8.4 | 0.254 | 18,100 | 0.0269 | 5 (+1.5) | 0.654 | 101 | K65 · PS 60 bar |
| #20 3/8" · Line to Freezer 2 · LT Suction | 0.01369 | 32.8 | 8.4 | 7.53 | 170,000 | 0.0174 | 5 (+1.5) | 12.5 | 1,920 | K65 · PS 30 bar |
ṁ = Q / (h″(t₀) − h′(t_liq))v = ṁ / (ρ · π·d²/4)Re = ρ·v·d / μf = 0.25 / [log₁₀(ε/(3.7·d) + 5.74/Re^0.9)]² (Re ≥ 2300); f = 64/Re (Re < 2300)Δp = f · (L/d) · ρ·v²/2, L = length × (1 + allowance %)| Size | Standard Copper (Cu-DHP) | Reinforced Copper (Cu-DHP) | K65 Copper (CuFe2P) selected pipe type |
|---|---|---|---|
| 1/4" 6.4 mm | 98 bar 0.76 mm | 123 bar 0.95 mm | – |
| 3/8" 9.5 mm | 70 bar 0.81 mm | 88 bar 1.02 mm | 120 bar 0.56 mm |
| 1/2" 12.7 mm | 53 bar MT, LT 0.81 mm | 66 bar 1.02 mm | 120 bar 0.75 mm |
| 5/8" 15.9 mm | 46 bar LT 0.89 mm | 57 bar MT, LT 1.11 mm | 120 bar 0.93 mm |
| 3/4" 19.0 mm | 38 bar LT 0.89 mm | 48 bar LT 1.11 mm | 120 bar 1.19 mm |
| 7/8" 22.2 mm | 42 bar LT 1.14 mm | 53 bar MT, LT 1.43 mm | 120 bar 1.38 mm |
| 1-1/8" 28.6 mm | 36 bar LT 1.27 mm | 46 bar LT 1.59 mm | 120 bar 1.78 mm |
| 1-3/8" 34.9 mm | 33 bar LT 1.40 mm | 41 bar LT 1.75 mm | 120 bar 2.17 mm |
| 1-5/8" 41.3 mm | 30 bar LT 1.52 mm | 38 bar LT 1.91 mm | 120 bar 2.56 mm |
| 2-1/8" 54.0 mm | 27 bar ⛔ 1.78 mm | 34 bar LT 2.22 mm | 120 bar 3.35 mm |
| 2-5/8" 66.7 mm | 25 bar ⛔ 2.03 mm | 31 bar LT 2.54 mm | – |
| 3-1/8" 79.4 mm | 24 bar ⛔ 2.29 mm | 30 bar ⛔ 2.86 mm | – |
| 3-5/8" 92.1 mm | 23 bar ⛔ 2.54 mm | 28 bar ⛔ 3.18 mm | – |
| 4-1/8" 104.8 mm | 22 bar ⛔ 2.79 mm | 27 bar ⛔ 3.49 mm | – |
| 5-1/8" 130.2 mm | 20 bar ⛔ 3.18 mm | 25 bar ⛔ 3.97 mm | – |
| 6-1/8" 155.6 mm | 19 bar ⛔ 3.56 mm | 23 bar ⛔ 4.45 mm | – |
Standard Copper (Cu-DHP): Common refrigerant pipe (ACR). Only the smallest sizes handle CO2's pressure — see the ⛔ mark against your design pressure.
Reinforced Copper (Cu-DHP): Same material but about 25% heavier wall, for a higher allowable pressure than standard copper.
K65 Copper (CuFe2P): High-strength copper alloy for CO2, 120 bar. Standard choice for subcritical and transcritical systems. Only made from 3/8″ to 2-1/8″ — larger sizes need a different pipe material.
Source and method: standard and reinforced copper by the thin-wall formula P = 2·S·t/D with S = 41 MPa (6,000 psi), the allowable stress of annealed copper tube up to 38 °C. Brazing anneals the tube at every joint, so brazed systems are rated on the annealed value (Copper Tube Handbook, ASME B31.5); the hard-drawn value of about 69 MPa applies only to flare or compression joints. K65: the manufacturer's (Wieland) stated 120 bar for the CuFe2P alloy to EN 14276, 3/8″–2-1/8″. Always check against your supplier's data before installation.
The pressure ratings above follow European practice (EN 378, EN 14276, EN 13480-3; copper walls to ASTM B280/B88). In other markets refrigerant piping is designed and approved to these codes instead. This calculator has not been checked against them – use the code that applies where the system is installed.
USA
Canada
Australia and New Zealand
The calculator works out the mass flow from each evaporator's cooling capacity and the CO2 properties at the evaporating and liquid temperatures, then picks the smallest tube size that keeps the velocity below your target. Pressure drop is calculated with Darcy–Weisbach and also shown as the equivalent temperature drop (K).
Calculate in the tool above ↑CO2 (R744) pipe sizing – steel →
The defaults are 12 m/s in the MT and LT suction lines and 1.2 m/s in the liquid line. A higher velocity gives smaller pipes but a larger pressure drop, and suction risers need enough velocity to carry the oil back to the compressors. Every value can be changed.
CO2 systems run at far higher pressures than HFC systems. K65 (CuFe2P alloy, EN 14276) is rated for 120 bar in sizes 3/8" to 2-1/8" and is the default here. Standard ACR copper has a much lower rating in the larger sizes; a size that cannot take the design pressure you enter is marked ⛔ and never selected automatically.
Calculate in the tool above ↑CO2 (R744) pipe sizing – steel →
The defaults – 52 bar MT suction, 30 bar LT suction and 60 bar liquid – are common starting values for a transcritical CO2 booster system based on EN 378-2. Always use the PS of your own system according to EN 378 and the PED.
Calculate in the tool above ↑Relief valve & discharge line (EN 13136 / EN ISO 24664) →
Yes. On the low-pressure side it sizes MT suction, LT suction and the liquid line from the receiver to the evaporators, where CO2 is subcritical (−50 to +10 °C). Tick “Line to gas cooler” to size the high-pressure side as well: the discharge line to the gas cooler and the return line from it (75–140 bar, CO2 data from CoolProp). The pressure ratings are calculated at room temperature, so check the discharge line's rating at its actual temperature.
It is free and needs no login. You get tube size, velocity and pressure drop for every pipe section, a materials list per size, insulation, and a flow diagram that prints on A4 to A1 and can be saved as a project file.