| Name | Circuit | kW |
|---|
The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.
| Pipe | Mass flow [kg/s] | Density [kg/m³] | Inner diameter [mm] | Velocity [m/s] | Re | f | Length (+ allowance) [m] | Δp [kPa] | Δp per metre [Pa/m] | Pipe type, PS |
|---|---|---|---|---|---|---|---|---|---|---|
| #1 DN15 · Liquid: Refrigeration unit → Cold Room 1 | 0.1043 | 972.4 | 16.1 | 0.527 | 71,700 | 0.0278 | 6 (+1.8) | 1.82 | 233 | P265NL · PS 60 bar |
| #2 DN15 · Liquid: Cold Room 1 → Freezer 1 | 0.07272 | 972.4 | 16.1 | 0.367 | 50,000 | 0.0285 | 6 (+1.8) | 0.906 | 116 | P265NL · PS 60 bar |
| #3 DN15 · Liquid: Freezer 1 → Cold Room 2 | 0.05316 | 972.4 | 16.1 | 0.269 | 36,600 | 0.0293 | 6 (+1.8) | 0.498 | 63.9 | P265NL · PS 60 bar |
| #4 DN15 · Liquid: Cold Room 2 → Freezer 2 | 0.02948 | 972.4 | 16.1 | 0.149 | 20,300 | 0.0315 | 6 (+1.8) | 0.164 | 21.1 | P265NL · PS 60 bar |
| #5 DN15 · Liquid: Freezer 2 → MT Display Case | 0.01579 | 972.4 | 16.1 | 0.0797 | 10,900 | 0.0348 | 6 (+1.8) | 0.0522 | 6.69 | P265NL · PS 60 bar |
| #6 DN15 · MT Suction: Refrigeration unit → Cold Room 1 | 0.07103 | 70.26 | 16.1 | 4.97 | 406,000 | 0.0261 | 6 (+1.8) | 11 | 1,410 | P265NL · PS 52 bar |
| #7 DN15 · MT Suction: Cold Room 1 → Cold Room 2 | 0.03946 | 70.26 | 16.1 | 2.76 | 226,000 | 0.0265 | 6 (+1.8) | 3.43 | 439 | P265NL · PS 52 bar |
| #8 DN15 · MT Suction: Cold Room 2 → MT Display Case | 0.01579 | 70.26 | 16.1 | 1.1 | 90,300 | 0.0274 | 6 (+1.8) | 0.568 | 72.8 | P265NL · PS 52 bar |
| #9 DN15 · LT Suction: Refrigeration unit → Freezer 1 | 0.03326 | 32.8 | 16.1 | 4.98 | 216,000 | 0.0265 | 6 (+1.8) | 5.22 | 669 | P265NL · PS 30 bar |
| #10 DN15 · LT Suction: Freezer 1 → Freezer 2 | 0.01369 | 32.8 | 16.1 | 2.05 | 88,800 | 0.0274 | 6 (+1.8) | 0.917 | 118 | P265NL · PS 30 bar |
| #11 DN15 · Line to Cold Room 1 · Liquid | 0.03157 | 972.4 | 16.1 | 0.159 | 21,700 | 0.0312 | 5 (+1.5) | 0.156 | 23.9 | P265NL · PS 60 bar |
| #12 DN15 · Line to Cold Room 1 · MT Suction | 0.03157 | 70.26 | 16.1 | 2.21 | 181,000 | 0.0266 | 5 (+1.5) | 1.84 | 283 | P265NL · PS 52 bar |
| #13 DN15 · Line to Cold Room 2 · Liquid | 0.02368 | 972.4 | 16.1 | 0.12 | 16,300 | 0.0325 | 5 (+1.5) | 0.0913 | 14 | P265NL · PS 60 bar |
| #14 DN15 · Line to Cold Room 2 · MT Suction | 0.02368 | 70.26 | 16.1 | 1.66 | 135,000 | 0.0269 | 5 (+1.5) | 1.05 | 161 | P265NL · PS 52 bar |
| #15 DN15 · Line to MT Display Case · Liquid | 0.01579 | 972.4 | 16.1 | 0.0797 | 10,900 | 0.0348 | 5 (+1.5) | 0.0435 | 6.69 | P265NL · PS 60 bar |
| #16 DN15 · Line to MT Display Case · MT Suction | 0.01579 | 70.26 | 16.1 | 1.1 | 90,300 | 0.0274 | 5 (+1.5) | 0.473 | 72.8 | P265NL · PS 52 bar |
| #17 DN15 · Line to Freezer 1 · Liquid | 0.01956 | 972.4 | 16.1 | 0.0988 | 13,500 | 0.0335 | 5 (+1.5) | 0.0643 | 9.89 | P265NL · PS 60 bar |
| #18 DN15 · Line to Freezer 1 · LT Suction | 0.01956 | 32.8 | 16.1 | 2.93 | 127,000 | 0.027 | 5 (+1.5) | 1.53 | 236 | P265NL · PS 30 bar |
| #19 DN15 · Line to Freezer 2 · Liquid | 0.01369 | 972.4 | 16.1 | 0.0692 | 9,420 | 0.0358 | 5 (+1.5) | 0.0336 | 5.17 | P265NL · PS 60 bar |
| #20 DN15 · Line to Freezer 2 · LT Suction | 0.01369 | 32.8 | 16.1 | 2.05 | 88,800 | 0.0274 | 5 (+1.5) | 0.764 | 118 | P265NL · PS 30 bar |
ṁ = Q / (h″(t₀) − h′(t_liq))v = ṁ / (ρ · π·d²/4)Re = ρ·v·d / μf = 0.25 / [log₁₀(ε/(3.7·d) + 5.74/Re^0.9)]² (Re ≥ 2300); f = 64/Re (Re < 2300)Δp = f · (L/d) · ρ·v²/2, L = length × (1 + allowance %)| Size | P265NL – carbon steel, seamless (EN 10216-4) selected pipe type | 316L (1.4404) – stainless, seamless (EN 10216-5) | 316L (1.4404) – stainless, welded thin-wall (EN 10217-7) |
|---|---|---|---|
| DN10 17.2 mm | 451 bar 2.30 mm | 340 bar 2.00 mm | 233 bar 1.60 mm |
| DN15 21.3 mm | 407 bar 2.60 mm | 269 bar 2.00 mm | 185 bar 1.60 mm |
| DN20 26.9 mm | 314 bar 2.60 mm | 243 bar 2.30 mm | 144 bar 1.60 mm |
| DN25 33.7 mm | 308 bar 3.20 mm | 217 bar 2.60 mm | 144 bar 2.00 mm |
| DN32 42.4 mm | 273 bar 3.60 mm | 170 bar 2.60 mm | 113 bar 2.00 mm |
| DN40 48.3 mm | 237 bar 3.60 mm | 148 bar 2.60 mm | 99 bar 2.00 mm |
| DN50 60.3 mm | 204 bar 3.90 mm | 132 bar 2.90 mm | 79 bar 2.00 mm |
| DN65 76.1 mm | 207 bar 5.00 mm | 104 bar 2.90 mm | 62 bar 2.00 mm |
| DN80 88.9 mm | 198 bar 5.60 mm | 98 bar 3.20 mm | 53 bar MT, LT 2.00 mm |
| DN100 114.3 mm | 172 bar 6.30 mm | 85 bar 3.60 mm | 41 bar LT 2.00 mm |
| DN125 139.7 mm | 140 bar 6.30 mm | 77 bar 4.00 mm | 33 bar LT 2.00 mm |
| DN150 168.3 mm | 130 bar 7.10 mm | 72 bar 4.50 mm | 36 bar LT 2.60 mm |
| DN200 219.1 mm | 112 bar 8.00 mm | 77 bar 6.30 mm | 28 bar ⛔ 2.60 mm |
| DN250 273.0 mm | 99 bar 8.80 mm | 62 bar 6.30 mm | 26 bar ⛔ 3.00 mm |
| DN300 323.9 mm | 94 bar 10.00 mm | 59 bar MT, LT 7.10 mm | 21 bar ⛔ 3.00 mm |
P265NL – carbon steel, seamless (EN 10216-4): Low-temperature steel for CO2 — plain carbon steel (P235/P265GH) is not impact-tough at LT temperatures. Impact tested to −40 °C (EN 10216-4); below that, check EN 13480-2 Annex B or use stainless steel. Heavy wall and high pressure rating. Needs external corrosion protection.
316L (1.4404) – stainless, seamless (EN 10216-5): Acid-resistant stainless steel with a medium wall. No external corrosion protection needed and tough at low temperatures.
316L (1.4404) – stainless, welded thin-wall (EN 10217-7): Light thin-wall pipe, rated with a weld joint factor of 0.85. Only the smaller sizes handle CO2's pressure — see the ⛔ mark against your design pressure.
Source and method: EN 13480-3, p = 2·f·z·e / (D − e), where e is the minimum wall (nominal less the tolerance: −12.5 % seamless, −10 % welded), f the allowable stress (P265NL 170 MPa, 1.4404 150 MPa, Rp1.0/1.5 on the safe side) and z the weld joint factor (0.85 for welded). The walls are common stock sizes – check with your supplier before ordering.
The pressure ratings above follow European practice (EN 378, EN 13480-3). In other markets refrigerant piping is designed and approved to these codes instead. This calculator has not been checked against them – use the code that applies where the system is installed.
USA
Canada
Australia and New Zealand
Each line is sized from its mass flow and the allowed velocity: MT suction, LT suction and liquid. The calculator works out the mass flow from cooling capacity, evaporating temperature and superheat, picks the smallest DN size that meets the target velocity and shows the pressure drop section by section.
Calculate in the tool above ↑CO2 (R744) pipe sizing – copper →
The allowable pressure is calculated to EN 13480-3 (p = 2·f·z·e / (D − e)) using the minimum wall after the mill tolerance: −12.5 % for seamless and −10 % for welded pipe. The calculator shows the pressure rating of every size and warns with ⛔ when a pipe cannot take the design pressure you entered.
P265NL (EN 10216-4) is a seamless carbon steel, impact tested for low temperatures, and the usual choice for CO2 plants; plain P235GH/P265GH is not intended for LT temperatures. Stainless 1.4404 (316L) comes seamless (EN 10216-5) and longitudinally welded (EN 10217-7). It needs no painting, but welded pipe has a thinner wall and a lower pressure rating. P265NL is impact tested to −40 °C (EN 10216-4); below that, check EN 13480-2 Annex B or use stainless steel.
DN10 to DN300 with outside diameters to EN 10220, from 17.2 to 323.9 mm. The wall thickness follows the selected pipe type, and the bill of materials gives the order designation, for example "DN25 · 33.7 × 3.2". Check the wall thickness with your supplier before ordering.
K65 copper tube is available up to 2-1/8″ (54 mm). Larger lines, industrial CO2 refrigeration and parts with a high design pressure are therefore usually built in steel. For smaller systems there is the copper calculator, and a project file opens in both with the drawing kept.
Calculate in the tool above ↑CO2 (R744) pipe sizing – copper →