co2piping.com

Capillary Tube Sizing

Bore and length of the capillary tube for small refrigerating systems – fridges, freezers, bottle coolers and small units.

Refrigerant and operating point

Compressor

Heat exchange with the suction line

Refrigerant charge

Sizes and units

Units

Check an existing tube

Project

.html
File
Share and print

The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.

Capillary tube per bore

The length each bore needs to pass the compressor's mass flow. ★ = recommended (length closest to the middle of your wanted range). Click a row to show it in the profile and the flow diagram.
Length band: the length for a bore 0.02 mm larger – 0.02 mm smaller (a typical tolerance; check the supplier's). Outlet: 'choked' = the flow reaches critical (sonic) speed at the tube end, the pressure there is shown; otherwise the tube ends at the evaporating pressure. x out = vapour fraction at the outlet. Wanted range 1.50 m–4.00 m.

Pressure and temperature along the tube – 0.6 mm × 5.87 m

Refrigerant charge of the circuit

Show calculation

Calculation per part of the tube

PartMass flow [kg/s]Density [kg/m³]Inner diameter [mm]Velocity [m/s]Ref (Darcy)Length [m]Δp [bar]Δp/m [Pa/m]Note
Entrance3.15e-4528.50.62.11––00.0177–loss K = 0.5 plus acceleration to the liquid velocity
Liquid part3.15e-4528.50.62.115,2800.03735.744.2674,100single-phase liquid until the saturation pressure is reached
Two-phase part3.15e-428.660.638.9––0.130.759586,000vapour fraction 0 → 0.09; density and velocity at the outlet Choked flow at the outlet.

Basis of the calculation

Method
Homogeneous two-phase model for the chosen bore and the compressor's mass flow: an entrance loss, single-phase liquid friction until the liquid reaches its saturation pressure, then two-phase flow with liquid and vapour at the same speed, marched in 200 pressure steps until the evaporating pressure or choked flow.
Equations
  • Entrance: Δp = (1 + K)·G²/(2ρ), K = 0.5
  • Momentum: −dp = f·G²·v/(2d)·dz + G²·dv
  • Energy: h + w²/2 = constant (minus the heat taken by the suction line heat exchanger)
  • Two-phase: v = (1 − x)·v_L + x·v_V, 1/μ = x/μ_V + (1 − x)/μ_L (McAdams)
  • Choked when (p_i − p_i+1) − G²·(v_i+1 − v_i) ≤ 0
Friction factor
Churchill (1977), smooth drawn copper, Re = G·d/μ
Property data
CoolProp 8.0.0
Sources
ASHRAE Handbook – Refrigeration, ch. 11 · Stoecker & Jones (1982), ch. 12 · Bansal & Rupasinghe (1998) · Churchill (1977) · McAdams et al. (1942) · Gnielinski (1976) · EN 12900:2013
Notes
  • The parts add up to the pressure drop from 5.03 bar(g) at the inlet to -0.00 bar(g) at the outlet of the tube.
  • With the suction line heat exchanger the liquid stays subcooled longer, so the liquid part is longer; its heat is taken out of the energy balance along the soldered part.

Flow diagram

How the app calculates

Cycle: t₀ and tc are dew points (EN 12900). The liquid leaves the condenser at the bubble point minus the subcooling and enters the capillary at the condensing pressure. The evaporator delivers vapour at p₀ and t₀ + superheat. Properties from CoolProp 8 (reference equations of state; blends with their glide).

Capillary: the homogeneous model described in the ASHRAE Handbook – Refrigeration and by Stoecker & Jones: an entrance loss (K = 0.5), single-phase liquid friction until the pressure reaches the saturation pressure of the liquid, then adiabatic two-phase flow with liquid and vapour at the same speed (h + w²/2 constant), marched in 200 pressure steps with friction and acceleration. Two-phase viscosity after McAdams, friction factor after Churchill (smooth drawn copper).

Choked flow: when the pressure drop no longer gives any length (−dp/dv = G²) the flow is critical; if that happens above the evaporating pressure the tube ends there and the rest of the expansion takes place in the jet into the evaporator – the normal state of a capillary system.

Suction line heat exchanger: calculated from its geometry – the soldered length, where it starts and the inner diameter of the suction line. Heat passes from the capillary to the suction gas in counterflow with UA per metre = 1/(1/(h_i·π·d) + 1/(h_g·π·D)); both film coefficients after Gnielinski (laminar Nu = 3.66), the suction gas side being the dominant resistance, the solder joint left out. The gas is followed cell by cell from the evaporator outlet along the capillary's own temperature profile, and the capillary and the gas are iterated until the return gas temperature and the heat taken from the capillary agree (as in the first-principles models of Hermes, Melo & Gonçalves). A measured return gas temperature can be entered instead. A heat exchanger that keeps the liquid subcooled delays the flashing and makes the tube considerably longer for the same flow.

Limits: the model lets the liquid flash exactly at saturation (no metastable delay), which makes the length somewhat too short when the subcooling is large; oil, bends and coiling are left out. Published comparisons of homogeneous models with measurements show deviations of the order of 10–20 % in mass flow Against the worked examples in the ASHRAE Handbook – Refrigeration 2006, ch. 44, the app gives 4–5 % more flow for an adiabatic R134a tube and about 8 % more with a suction line heat exchanger; always confirm the charge and the superheat in a test run.

Sources

  • ASHRAE Handbook – Refrigeration (2022), chapter 11 Refrigerant-control devices, section Capillary tubes. ASHRAE, Atlanta.
  • Stoecker, W.F., Jones, J.W. (1982). Refrigeration and Air Conditioning, 2nd ed., McGraw-Hill, chapter 12 Expansion devices (capillary tube calculation).
  • Bansal, P.K., Rupasinghe, A.S. (1998). An homogeneous model for adiabatic capillary tubes. Applied Thermal Engineering 18(3–4), 207–219.
  • Bolstad, M.M., Jordan, R.C. (1948). Theory and use of the capillary tube expansion device. Refrigerating Engineering 56(12), 519–523.
  • Churchill, S.W. (1977). Friction-factor equation spans all fluid-flow regimes. Chemical Engineering 84(24), 91–92.
  • McAdams, W.H., Woods, W.K., Heroman, L.C. (1942). Vaporization inside horizontal tubes – II. Trans. ASME 64, 193–200.
  • Bell, I.H., Wronski, J., Quoilin, S., Lemort, V. (2014). Pure and pseudo-pure fluid thermophysical property evaluation and the open-source thermophysical property library CoolProp. Ind. Eng. Chem. Res. 53(6), 2498–2508 (CoolProp 8.0).
  • EN 12900:2013 Refrigerant compressors – Rating conditions, tolerances and presentation of manufacturer's performance data.
  • EN 378-1:2016+A1:2020, IEC 60335-2-24 (household refrigerating appliances) and IEC 60335-2-89 (commercial refrigerating appliances): charge limits for flammable refrigerants.
  • US EPA (2024). SNAP rule 26, fact sheet: https://epa.gov/system/files/documents/2024-05/snap-final-rule-26-factsheet.pdf (checked 2026-10-14).
  • US 40 CFR part 82, subpart G, appendices R and V (SNAP, hydrocarbons in household refrigerators and freezers): https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-G (checked 2026-10-25).
  • ASERCOM (2023). Components for flammable refrigerants: https://www.asercom.org/wp-content/uploads/2023/04/En_Components-for-Flammable-Refrigerants.pdf (charge limit of IEC 60335-2-24).
  • Gnielinski, V. (1976). New equations for heat and mass transfer in turbulent pipe and channel flow. International Chemical Engineering 16(2), 359–368.
  • Hermes, C.J.L., Melo, C., Gonçalves, J.M. (2008). Modeling of non-adiabatic capillary tube flows: a simplified approach and comparison with empirical data. International Journal of Refrigeration 31(8), 1358–1367.
  • ASHRAE Handbook – Refrigeration (2006, SI), chapter 44 Refrigerant-control devices, section Capillary tubes: rating charts and worked examples after Wolf et al. (1995) and Wolf & Pate (2002), used to check the app.

Frequently asked questions

How do I size a capillary tube?

Start from the compressor: its mass flow at the design point (evaporating and condensing temperature, subcooling) must pass through the capillary. For every bore the app finds the length that gives exactly that flow; a longer tube passes less, a larger bore more. Choose a bore whose length is practical, typically 1.5–4 m in fridges and freezers.

Calculate it in the tool above ↑

Which bore should I choose?

A larger bore with a longer tube is less sensitive to tolerances, dirt and oil than a short tube with a small bore: ±0.02 mm on a 0.6 mm bore changes the flow by about 8 %. Very short tubes (under 0.5 m) are hard to get right; very long ones are impractical. The app recommends the size whose length is closest to the middle of your wanted range.

Calculate it in the tool above ↑

Why solder the capillary to the suction line?

The cold suction gas cools the liquid in the capillary: more cooling capacity per kg, less flash gas, and the suction line does not sweat or frost. The liquid then stays liquid longer and the tube passes more refrigerant per metre, so a soldered tube is longer than an adiabatic one for the same flow. The app calculates the exchanger from the soldered length and the suction line diameter; a measured return gas temperature can be entered instead.

Calculate it in the tool above ↑

What does choked flow mean?

The speed of the two-phase mixture rises as it flashes. At a certain point it reaches the critical (sonic) speed: lowering the evaporating pressure further does not raise the flow. Most capillary systems run choked; then the tube length decides the flow and the evaporating pressure only changes the jet at the outlet.

Calculate it in the tool above ↑

Can I use the results for R600a and R290?

Yes, the properties of isobutane and propane come from CoolProp's reference equations of state. Remember that hydrocarbons are flammable (A3): appliance standards limit the charge per circuit, and a capillary system has no receiver, so the charge has to be weighed in exactly.

Calculate it in the tool above ↑HC (A3) refrigerant pipe sizing →

How accurate is the calculation?

Published comparisons of homogeneous models with measurements on adiabatic tubes show deviations of the order of 10–20 % in mass flow; with a suction line heat exchanger the uncertainty is larger. Against the worked examples in the ASHRAE Handbook (2006, ch. 44) the app is within +4…9 % in mass flow. The bore tolerance alone gives several per cent. Use the result as a starting point and confirm the superheat and the pressures in a test run.

Assumptions: Homogeneous two-phase flow, no metastable flashing, smooth drawn copper tube, straight or loosely coiled, no oil. t₀ and tc as dew points (EN 12900). The pressure drop of the condenser and liquid line is left out. Properties from CoolProp 8.

Disclaimer: The calculation is a guide for design. Check the result against the compressor manufacturer's data and confirm the charge, superheat and pressures in a test run. CO2piping.com takes no responsibility for the use of the results.

New feature – please report any errors: Report a bug

Help – capillary tube sizing

Fill in the refrigerant, the operating point and the compressor on the left. The table on the right gives the length every standard capillary bore needs; the recommended size is marked with ★.

1. Refrigerant and operating point

  • Choose the refrigerant and the application (freezer, fridge, high back pressure); the application fills in typical temperatures you can change.
  • Evaporating and condensing temperatures are dew points, as in compressor data sheets (EN 12900).
  • Subcooling is the liquid's temperature below the bubble point at the condenser outlet; superheat is that at the evaporator outlet.

2. Compressor

  • Give the cooling capacity at the operating point, the mass flow, or the displacement and speed of the compressor.
  • With the displacement the app estimates the volumetric efficiency of a small reciprocating compressor; enter the real value if you have it.

3. Suction line heat exchanger

  • Tick the box if the capillary is soldered to the suction line (most fridges and freezers).
  • The app calculates how much heat the exchanger takes from the capillary from the soldered length, where it starts and the suction line's inner diameter, and shows the resulting return gas temperature. If you have measured it, enter it instead.

4. Result

  • Every row is one bore: the length, the length band for a bore tolerance of ±0.02 mm, the liquid part, the outlet state and the exit velocity.
  • Click a row to see its pressure and temperature along the tube and to draw it in the flow diagram.
  • Under 'Check an existing tube' you enter the bore and length of a tube you have: the app gives its mass flow and cooling capacity at the operating point and compares it with the compressor.

5. Save, open, print

  • Save saves the project as a link file (.html): a double click opens it on co2piping.com, and Open reads it back (older .json files too). Copy link copies a link to the project. Both contain everything in the project.
  • Print gives the report with the table and the profile, then the flow diagram on a landscape page of its own.