| Component | Inner volume (L) | Liquid (%) |
|---|---|---|
| Condenser | ||
| Evaporators | ||
| Receiver |
| Name | kW |
|---|
The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.
| Part | Volume (L) | Density (kg/m³) | Charge (kg) | Share |
|---|---|---|---|---|
| Liquid line | 3.5 | 471.0 | 1.641 | 90 % |
| Suction line | 16.9 | 7.3 | 0.123 | 7 % |
| Hot gas line | 2.3 | 24.6 | 0.058 | 3 % |
| Condenser | 0.0 | – | 0.000 | 0 % |
| Evaporators | 0.0 | – | 0.000 | 0 % |
| Receiver | 0.0 | – | 0.000 | 0 % |
| Other | – | – | 0.000 | 0 % |
| Total | 22.7 | 1.821 | 100 % |
| Pipe section | Mass flow [kg/s] | Density [kg/m³] | Inner diameter [mm] | Velocity [m/s] | Re | f | Length (+ fittings) [m] | Δp [kPa] | Δp per metre [Pa/m] | Note |
|---|---|---|---|---|---|---|---|---|---|---|
| Liquid, Main Stem: Condenser → Cold Room 1 | 0.06454 | 471 | 17.3 | 0.585 | 56,200 | 0.0206 | 6 (+1.8) | 0.75 | 125 | |
| Liquid, Main Stem: Cold Room 1 → Cold Room 2 | 0.03585 | 471 | 11.1 | 0.791 | 48,700 | 0.0214 | 6 (+1.8) | 2.22 | 371 | |
| Liquid, Main Stem: Cold Room 2 → Display Case | 0.01434 | 471 | 7.9 | 0.621 | 27,300 | 0.0245 | 6 (+1.8) | 2.19 | 366 | |
| Suction Line, Main Header: Compressor → Cold Room 1 | 0.06454 | 7.266 | 38.2 | 7.74 | 300,000 | 0.0148 | 6 (+1.8) | 0.658 | 110 | |
| Suction Line, Main Header: Cold Room 1 → Cold Room 2 | 0.03585 | 7.266 | 26 | 9.27 | 245,000 | 0.0155 | 6 (+1.8) | 1.45 | 242 | |
| Suction Line, Main Header: Cold Room 2 → Display Case | 0.01434 | 7.266 | 17.3 | 8.43 | 148,000 | 0.0171 | 6 (+1.8) | 2 | 334 | |
| Hot gas line: Compressor → Condenser | 0.06454 | 24.56 | 17.3 | 11.2 | 535,000 | 0.0142 | 10 (+3) | 16.6 | 1,660 | |
| Cold Room 1 – Liquid | 0.02868 | 471 | 11.1 | 0.633 | 39,000 | 0.0225 | 5 (+1.5) | 1.24 | 249 | |
| Cold Room 1 – Suction line | 0.02868 | 7.266 | 26 | 7.41 | 196,000 | 0.0161 | 5 (+1.5) | 0.803 | 161 | |
| Cold Room 2 – Liquid | 0.02151 | 471 | 11.1 | 0.475 | 29,200 | 0.0239 | 5 (+1.5) | 0.745 | 149 | |
| Cold Room 2 – Suction line | 0.02151 | 7.266 | 19.9 | 9.48 | 192,000 | 0.0163 | 5 (+1.5) | 1.74 | 348 | |
| Display Case – Liquid | 0.01434 | 471 | 7.9 | 0.621 | 27,300 | 0.0245 | 5 (+1.5) | 1.83 | 366 | |
| Display Case – Suction line | 0.01434 | 7.266 | 17.3 | 8.43 | 148,000 | 0.0171 | 5 (+1.5) | 1.67 | 333 |
Δp = f · (L/d) · ρv²/2 + ρ·g·hRe = ṁ·d / (A·µ)f = 0.25 / [log10(ε/(3.7·d) + 5.74/Re^0.9)]² (Re < 2300: f = 64/Re)L = L_pipe · (1 + 30 %)The calculator works out the mass flow from each evaporator's capacity and the refrigerant properties (CoolProp), then picks the smallest pipe that keeps the velocity below the target. Pressure drop is calculated with Darcy–Weisbach and shown in kPa and as saturation temperature drop (K). The results have been checked against Danfoss Coolselector 2.
The defaults are 10 m/s in the suction line, 0.8 m/s in the liquid line and 12 m/s in the hot gas line. A higher velocity gives smaller pipes but more pressure drop, and suction risers also need enough velocity for oil return.
Common guide values are about 1 K saturation temperature drop in the suction line and 0.5–1 K in the liquid and hot gas lines. The calculator converts every pressure drop to K and warns of flash gas when the liquid line drop exceeds the subcooling.
Mark the line as a riser. The calculator then picks a size in which the gas is fast enough to carry the oil upwards (criterion j*g ≥ 0.85) and shows the minimum velocity. If even the smallest allowed size is too large, a double suction riser is suggested.
R290 (propane), R600a (isobutane), R600 (butane), R1270 (propylene), R170 (ethane) and the blends R441A, R443A, R436A, R436B and R510A, all of safety class A3. Temperatures are entered as dew points; for zeotropic blends the glide, bubble point and liquid temperature are worked out automatically.
It depends on the refrigerant's lower flammability limit (LFL), the room volume, the location and the access category under EN 378-1 (Annex C), or on the product standard for factory-built units: IEC 60335-2-89 for commercial refrigerating appliances and IEC 60335-2-40 for heat pumps and air conditioners. The calculator estimates the charge and compares it with an indicative limit; it does not replace the standard. Small pipes and short lines mean a smaller charge. Always carry out a risk assessment.
Check the charge in the tool above →Heating, cooling & brine pipe sizing →