co2piping.com

HC (A3) Pipe Sizing

Suction, liquid and hot gas lines for a refrigeration system with a flammable HC refrigerant (A3): compressor, condenser, filter drier, sight glass, expansion valve and evaporators connected in parallel. Drag the evaporators into place and click a line to set its length, size or riser.
R290 · -10.0 °C / 40.0 °C · 18.00 kW

System Data

All refrigerants here are safety class A3 (higher flammability) per EN 378/ISO 817/ASHRAE 34. Changing the refrigerant resets the design pressures.
Evaporating and condensing temperatures are dew points (relevant for zeotropic blends with glide). The liquid temperature is the bubble point at the condensing pressure minus the subcooling; it sets the flash gas share and so the mass flow.
R290 (A3) · glide at evaporation 0.0 K · at condensing 0.0 K · liquid temperature 38.0 °C. Flammable (A3): the charge is limited by EN 378-1 and the product standards (IEC 60335-2-89/-40). Keep the charge low, avoid ignition sources and carry out a risk assessment (ATEX).
Useful superheat at the evaporator outlet. It counts as refrigerating effect, and the suction lines are sized for the lower density of the superheated gas.
Installed compressor capacity for comparison with connected evaporator loads. Enter compressor power for total heat rejection.
Directly controls pipe sizing — higher velocity yields smaller pipes.

Hot gas line

From the compressors to the condenser, carrying the whole circulated mass flow. Length 0 = no hot gas line. Tick Riser if the line runs upwards; its oil return is then checked.

Refrigerant charge

ComponentInner volume (L)Liquid (%)
Condenser
Evaporators
Receiver
Pipes 1.82 kg + components 0.00 kg + other 0.00 kg = 1.82 kg. R290 (A3, LFL 0.038 kg/m³): limit 0.15 kg (m1 – always allowed).
The pipes are calculated automatically: the liquid line full of liquid, the suction and hot gas lines full of gas. Enter the components' inner volume (manufacturers' data) and the share that is liquid in operation, or enter the charge directly under Other charge. The limits follow EN 378-1:2016+A1:2020 annex C (m1 = 4 m³ × LFL, m2 = 26 m³ × LFL, m3 = 130 m³ × LFL) and the product standards IEC 60335-2-40 and IEC 60335-2-89. The check is a guide – national rules may be stricter.
Advanced – Margins & Pipe Material
Increases the length in the pressure-drop calculation — shows up in the Δp column in the “Main Headers”/“Evaporator Branch Connections” tables below, not in the pipe size or the cards at the top.
Adds ordering margin to the Bill of Materials and Insulation Schedule totals only (offcuts, mistakes) — a different thing from “Extra length for fittings” above, and does not affect the pipe size or Δp.
Standard refrigeration tube (ACR). Enough for R290, R600a, R600, R1270 and the blends; R170 (ethane) has high pressures — see the ⛔ mark.
Pipes that cannot take this pressure are marked ⛔ and never chosen automatically. The defaults follow from the refrigerant per EN 378-2 (ambient up to 32 °C): the saturation pressure at 55 °C on the high side (liquid and hot gas) and at 32 °C on the low side, as gauge pressure. They are reset when you change refrigerant. Adjust them to your own system.
Optional. Risers are sized for oil return with the criterion j*g ≥ 0.85; here you can set your own lower limit, e.g. the manufacturer's recommendation. The higher of the two is used. Empty = the criterion only.
Pipes smaller than this threshold will never be selected automatically.
Select insulation specification (thickness/color) per header for the material bill.

Evaporators

NamekW
A pipe stub contains only ONE line (liquid or suction). A suction stub can be converted to an evaporator by assigning a kW load.
[ Annonsering / Advertisement ]

Project

.html
File
Share and print
Not saved yet.

The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.

Options · Units

Changes how values are shown and entered — all calculations still run in the background as before.

Flow Diagram

Suction line Liquid Hot gas Expansion valve Tapped off another pipe
100% 100%
Drag an evaporator freely to position it. Click any pipe segment to set its length or manually override size.
Click here, then on a pipe run, to place a power meter.
— m Size:
[ Annonsering / Advertisement ]

Refrigerant charge and flammable refrigerant (A3)

Limits for R290 (safety class A3)
Lower flammability limit LFL = 0.038 kg/m³ (EN 378-1 E / ISO 817)
m1 = 4 m³ × LFL = 0.152 kg · m2 = 26 m³ × LFL = 0.988 kg · m3 = 130 m³ × LFL = 4.940 kg
Limit: 0.152 kg (m1 – always allowed; EN 378-1:2016, table C.2 (AREA, Introduction to EN 378)). The charge is 999 % of the limit.
⚠ The charge 1.82 kg is above m1 = 0.15 kg: enter the volume of the smallest room with an evaporator to check the limit per EN 378-1, table C.2.

Measures

  • The liquid line holds 90 % of the charge: shorten it and choose a smaller size (higher target liquid velocity, as far as pressure drop and flash gas allow).
  • Place the unit close to the evaporators and choose components with a small inner volume (e.g. a microchannel condenser, a small receiver or none).
  • Split the plant into several circuits, each below the limit.
  • Go indirect: the HC unit in a machinery room or outdoors and a secondary fluid to the evaporators. Size the secondary network in Heating & cooling. → /hydronic/
  • Put the compressor, condenser and receiver in a ventilated machinery room or outdoors (location class II or III, machinery room per EN 378-3).

Requirements and references

  • Zoning: where flammable gas can occur, the area shall be classified per EN 60079-10-1 (ATEX directive 1999/92/EC), and equipment in a zone shall meet the ATEX directive 2014/34/EU. The calculator does not do the zoning.
  • Machinery rooms, ventilation, gas detection and alarms: EN 378-3.
  • Pipe joints and tightness: EN 378-2. Prefer permanent joints (brazed); mechanical joints shall be accessible and leak tested.
  • Ignition sources: no ignition sources (switches, relays, hot surfaces, open flames) where refrigerant can collect after a leak. Most HC refrigerants are heavier than air and collect near the floor.
  • The calculator does not replace a risk assessment. Check the limits against the standard text and national rules.
  • Certification: in the EU, Implementing Regulation (EU) 2024/2215 now also covers hydrocarbons (Art. 2(1)(b)–(c)). Certificate A1: F-gases and hydrocarbons, any charge; A2: under 3 kg (labelled hermetically sealed systems under 6 kg); B: CO2; C: ammonia. Old category I/II certificates become A1/A2 only after updated knowledge (Art. 10). National rules apply too – e.g. Germany: ChemKlimaschutzV, in force since 17 April 2026 (existing certificates valid until 12 March 2029). Sweden: the new certificates cannot be issued yet, so the requirement cannot yet be applied to natural refrigerants (Naturvårdsverket, 2026-10). First refresher training by 12 March 2029 throughout the EU (Regulation (EU) 2024/573, Art. 10(9)). (EUR-Lex – (EU) 2024/2215, LfU Bayern – ChemKlimaschutzV, Naturvårdsverket – övergångsperiod; checked 2026-10-29)

Safety standard in other countries

  • United Kingdom: BS EN 378 (the UK edition of EN 378, same charge limits). Hydrocarbons are outside the GB F-gas rules; the Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR, SI 2002/2776) require a risk assessment and zoning where flammable gas can occur. (legislation.gov.uk – DSEAR, SI 2002/2776; checked 2026-10-25)
  • Japan: High Pressure Gas Safety Act (Art. 5) and its Cabinet Order (Art. 2(5)(iii)–(iv), Art. 4) – propane, propene, isobutane, n-butane and ethane are flammable gases under the Refrigeration Safety Regulations (冷凍保安規則 Art. 2(1)(i)) and belong to "other gases": below 3 tons of refrigerating capacity per day outside the Act, 3 to under 20 tons per day a notification (届出) to the prefecture, 20 tons per day or more a permit (許可). The legal capacity (法定冷凍能力) is calculated from the compressor displacement, R = V/C (冷凍保安規則 Art. 5), not from the cooling capacity in kW; the commercial ton of about 3.86 kW is not the legal value. For flammable refrigerants Art. 7(1) requires explosion-proof electrical equipment, a gas detector with alarm and fire-extinguishing equipment. (e-Gov – 高圧ガス保安法, 施行令, 冷凍保安規則, Japanese Law Translation – High Pressure Gas Safety Act; checked 2026-10-29)
  • USA: ASHRAE 15-2022 and UL 60335-2-89 (2nd edition, 27 October 2021), which EPA SNAP refers to (40 CFR 82 subpart G, appendix R; SNAP Rule 26, 2024). SNAP accepts hydrocarbons only in new equipment designed for them, not in conversions, with use conditions per sector. The limits for R290 in new stand-alone commercial refrigeration come from UL 60335-2-89, not from the CFR text: about 300 g with doors or drawers, 500 g open. (eCFR – 40 CFR 82 subpart G, EPA – SNAP Rule 26 (2024); checked 2026-10-29)
  • Canada: CSA B52:23 Mechanical refrigeration code. It has legal force once a province adopts it, e.g. British Columbia (B.C. Reg. 104/2004: B52:23), Alberta (Alta Reg 49/2006, s. 6(b): CSA B52 as amended from time to time), Manitoba (2024) and Ontario (TSSA, from 1 October 2024). (CSA B52:23, SCC; checked 2026-10-29)
  • Australia and New Zealand: AS/NZS 5149.1:2016 (+Amd 1:2018) for refrigerating systems – ISO 5149-1 with national modifications (MOD), so charge limits can differ from ISO/EN – and AS/NZS 60335.2.89:2020 Amd 1:2024 (commercial refrigerating appliances). The Australian ARC refrigerant licence covers fluorocarbon refrigerants; work with hydrocarbons may need an additional state licence – check the rules of the state. (AS/NZS 5149.1:2016, AS/NZS 60335.2.89:2020 Amd 1:2024; checked 2026-10-29)
  • Switzerland: ChemRRV (SR 814.81) annex 2.10 bans or restricts refrigerants that are stable in air (fluorinated refrigerants, F-gases) and ozone-depleting substances; hydrocarbons are not covered and are often the alternative (tighter limits from 1 January 2027; transitional rules in no. 7 still allow some F-gas systems until 2028–2032). The exception refers to SN EN 378-1:2017+A1:2021, SN EN 378-2:2017, SN EN 378-3:2017+A1:2021, SN EN IEC 60335-2-89:2022/A11:2022 and IEC 60335-2-40:2022 (ed. 7): if these cannot be met with a natural refrigerant, BAFU may allow an F-gas. (Fedlex – ChemRRV, Anhang 2.10 (Fassung 2027), Fedlex – ChemRRV (SR 814.81), Anhang 2.10, BAFU – Kältemittel, BAFU – Stand April 2026; checked 2026-10-29)
  • South Africa: SANS 10147:2014 (edition 5) is the standard for refrigerating systems, including those of air-conditioning plants. Under the Pressure Equipment Regulations (regulation 17) the work shall be done by an Authorised Refrigeration Practitioner registered with SAQCC Gas (through SARACCA). Registration is valid for 3 years. The ODS Regulations (GN R351 of 2014, amended 2021) forbid releasing ozone-depleting substances into the atmosphere (reg. 7) and using HCFC-22 or other HCFCs in new refrigeration or air-conditioning systems since 1 January 2015 (reg. 5(2)(c)). (SABS – SANS 10147:2014 (Ed. 5.00), SAQCC Gas – SARACCA; checked 2026-10-29)
  • Chile: NCh3241:2017 for refrigeration and air-conditioning systems (based on ISO 5149-1:2014, ISO 817:2014 and ASHRAE 15) and NCh3301:2017 for installing and servicing systems with flammable refrigerants (A2L, A2 and A3). (INN – NCh3301:2017, MMA/INN – NCh3241:2017, NCh3301:2017; checked 2026-10-07)
  • Colombia: NTC 6228-1 to -4 (ICONTEC, 2019–2021), based on ISO 5149. (Minambiente – NTC 6228-1; checked 2026-10-07)
  • Rest of Latin America: ISO 5149-1 to -4 where the country has not adopted a standard of its own. (ISO 5149-1:2014; checked 2026-10-07)
ISO 5149-1 uses the same method for charge limits (m1, m2, m3 and room volume) as EN 378-1 annex C, which the app calculates with. Always check against the edition in force in the country.

Bill of Materials

Lengths include the waste allowance above, but not the fitting length allowance (which only affects Δp).

Insulation Schedule

Insulation types are selected under 'Advanced' in System Data.

Evaporator Branch Connections

"Own Load" is the evaporator's own kW value. "Load in Pipe" is the accumulated flow through that specific pipe — larger if other evaporators/pipes are tapped onto it. Never sum the "Load in Pipe" columns for a grand total; use "Own Load" instead.

Main Headers

Show calculation

Calculation per pipe section

Pipe sectionMass flow [kg/s]Density [kg/m³]Inner diameter [mm]Velocity [m/s]RefLength (+ fittings) [m]Δp [kPa]Δp per metre [Pa/m]Note
Liquid, Main Stem: Condenser → Cold Room 10.0645447117.30.58556,2000.02066 (+1.8)0.75125
Liquid, Main Stem: Cold Room 1 → Cold Room 20.0358547111.10.79148,7000.02146 (+1.8)2.22371
Liquid, Main Stem: Cold Room 2 → Display Case0.014344717.90.62127,3000.02456 (+1.8)2.19366
Suction Line, Main Header: Compressor → Cold Room 10.064547.26638.27.74300,0000.01486 (+1.8)0.658110
Suction Line, Main Header: Cold Room 1 → Cold Room 20.035857.266269.27245,0000.01556 (+1.8)1.45242
Suction Line, Main Header: Cold Room 2 → Display Case0.014347.26617.38.43148,0000.01716 (+1.8)2334
Hot gas line: Compressor → Condenser0.0645424.5617.311.2535,0000.014210 (+3)16.61,660
Cold Room 1 – Liquid0.0286847111.10.63339,0000.02255 (+1.5)1.24249
Cold Room 1 – Suction line0.028687.266267.41196,0000.01615 (+1.5)0.803161
Cold Room 2 – Liquid0.0215147111.10.47529,2000.02395 (+1.5)0.745149
Cold Room 2 – Suction line0.021517.26619.99.48192,0000.01635 (+1.5)1.74348
Display Case – Liquid0.014344717.90.62127,3000.02455 (+1.5)1.83366
Display Case – Suction line0.014347.26617.38.43148,0000.01715 (+1.5)1.67333

Basis of calculation

Method
Darcy–Weisbach per pipe section; the size is the smallest tube that keeps the velocity at or below the target. Gas lines are marched in 50 steps with the density following the local pressure (isothermal); liquid lines use a constant density.
Equations
  • Δp = f · (L/d) · ρv²/2 + ρ·g·h
  • Re = ṁ·d / (A·µ)
  • f = 0.25 / [log10(ε/(3.7·d) + 5.74/Re^0.9)]² (Re < 2300: f = 64/Re)
  • L = L_pipe · (1 + 30 %)
Friction factor
Swamee–Jain (explicit form of Colebrook–White), roughness of the chosen pipe type
Fluid data
CoolProp (HEOS; blends as CoolProp predefined mixtures, composition per ASHRAE 34) 8.0.0
Standards
EN 378-1:2016 (C.2, E) · EN 378-2:2016 · IEC 60335-2-89:2019 · IEC 60335-2-40 · ASHRAE 34
Notes
  • Density in the table is the inlet value; superheated suction and discharge gas from saturated vapour density corrected for the superheat.
  • Compared with Danfoss Coolselector 2 for R290, R600a and R1270 (12 cases, 36 sizes): mass flow within 0.05 %, Δp within 0.8 %.

Refrigerant pipe sizing – frequently asked questions

How do you size refrigerant lines for R290 and other HC refrigerants?

The calculator works out the mass flow from each evaporator's capacity and the refrigerant properties (CoolProp), then picks the smallest pipe that keeps the velocity below the target. Pressure drop is calculated with Darcy–Weisbach and shown in kPa and as saturation temperature drop (K). The results have been checked against Danfoss Coolselector 2.

Calculate in the tool above →

What velocity should suction, liquid and hot gas lines have?

The defaults are 10 m/s in the suction line, 0.8 m/s in the liquid line and 12 m/s in the hot gas line. A higher velocity gives smaller pipes but more pressure drop, and suction risers also need enough velocity for oil return.

Calculate in the tool above →

How much pressure drop is acceptable in a refrigerant line?

Common guide values are about 1 K saturation temperature drop in the suction line and 0.5–1 K in the liquid and hot gas lines. The calculator converts every pressure drop to K and warns of flash gas when the liquid line drop exceeds the subcooling.

Calculate in the tool above →

How do I make sure oil returns up a suction riser?

Mark the line as a riser. The calculator then picks a size in which the gas is fast enough to carry the oil upwards (criterion j*g ≥ 0.85) and shows the minimum velocity. If even the smallest allowed size is too large, a double suction riser is suggested.

Calculate in the tool above →

Which refrigerants are included, and how is glide handled?

R290 (propane), R600a (isobutane), R600 (butane), R1270 (propylene), R170 (ethane) and the blends R441A, R443A, R436A, R436B and R510A, all of safety class A3. Temperatures are entered as dew points; for zeotropic blends the glide, bubble point and liquid temperature are worked out automatically.

Calculate in the tool above →

What is the charge limit for a system with R290 or R600a?

It depends on the refrigerant's lower flammability limit (LFL), the room volume, the location and the access category under EN 378-1 (Annex C), or on the product standard for factory-built units: IEC 60335-2-89 for commercial refrigerating appliances and IEC 60335-2-40 for heat pumps and air conditioners. The calculator estimates the charge and compares it with an indicative limit; it does not replace the standard. Small pipes and short lines mean a smaller charge. Always carry out a risk assessment.

Check the charge in the tool above →Heating, cooling & brine pipe sizing →

Assumptions: Refrigerant data from CoolProp (reference equations of state, blends with the ASHRAE 34 composition). Evaporating −50…+15 °C and condensing +15…+65 °C, temperatures as dew points. Pressure drop by Darcy–Weisbach, also converted to a saturation temperature drop (K). Oil return in risers is checked with the criterion j*g ≥ 0.85. Pipe sizes are nominal ACR inch sizes. Verify wall thickness and design pressure against EN 378/PED before installation. The mass flow is based on the refrigerating effect: the enthalpy after the evaporator (evaporation plus useful superheat) minus h′ at the liquid temperature. Flash gas at the expansion is included and the useful superheat counts as refrigerating effect. The hot gas line carries the whole circulated mass flow.

Disclaimer: This tool does not guarantee correct results. Always verify pipe wall thickness, pressure rating, and other values manually before installation.

New feature – please report any errors: Report a bug

Help – how to use the calculator

The calculator sizes the pipes of a refrigeration system with a flammable HC refrigerant (A3): suction line, liquid line and hot gas line. The system is drawn as one circuit: compressor → hot gas → condenser → filter drier → sight glass → expansion valve → evaporators (in parallel) → suction line back to the compressor. Choose the refrigerant, fill in the system data, build the plant in the flow diagram and read off pipe sizes, pressure drops (also as saturation temperature drop, K) and the bill of materials. Each evaporator's capacity sets the flow in the pipe runs, and the pipes are chosen so the velocity does not exceed the target velocity.

1. System data

  • Choose the refrigerant. Enter the evaporating and condensing temperatures, both as dew points, and the subcooling. The liquid temperature is the bubble point at the condensing pressure minus the subcooling. The superheat affects the mass flow and the sizing of the suction line.
  • Set a separate target velocity for the suction line and the liquid line. A higher target velocity gives smaller pipes; a lower one gives larger pipes and lower pressure drop.
  • The installed rack capacity and compressor power are optional. They are used to compare with the evaporator loads and to show the total heat rejection.
  • Under “Advanced – Margins & Pipe Material”: extra length for fittings (affects only the pressure drop, not the pipe size), pipe type, minimum allowed pipe size, and insulation per header (used in the bill of materials).
  • Pipe type and design pressure together decide which sizes are allowed — ⛔ in the tables means that size doesn't meet the pressure you entered.

2. Evaporators and pipe stubs

  • Add an evaporator with “+ Add Evaporator” and enter its name and load. All evaporators are connected in parallel between the liquid line and the suction line. Use ▲ ▼ to change the order and × to remove a row.
  • A pipe stub is a single line (liquid or suction) that other evaporators can be tapped onto. Give a suction stub a load if it should become an evaporator.
  • One calculation = one refrigeration system (one compressor or rack and one condenser). A freezer and a cold room on separate systems never share a liquid line – calculate them separately.

3. The flow diagram

  • Drag an evaporator to move it. Click its name to rename it and its load value to change it.
  • The diagram is drawn as a standard refrigeration flow diagram: the compressor sends hot gas up to the condenser, the liquid line runs along the top through the filter drier and the sight glass, each evaporator has its own expansion valve, and the suction line runs along the bottom back to the compressor.
  • The liquid line and the suction line can be dragged up and down – grab the line, the condenser, the filter drier, the sight glass or the compressor. The condenser follows the liquid line and the compressor the suction line; the evaporators stay where they are and their pipes follow. A click (without dragging) opens the line's length and size as usual.
  • The buttons “Lines closer” and “Lines apart” change the distance between the liquid line and the suction line; the evaporators move with them. The lines can also be dragged one at a time.
  • Click a pipe to set its length, lock the length or choose the pipe size manually. A ✎ in the tables shows that the size was chosen manually.
  • Right-click a pipe to add an evaporator or a pipe stub at that spot.
  • The round handle at an evaporator's pipe can be dragged and dropped onto another evaporator's pipe of the same kind to tap into it, or onto empty space to connect straight to the header. The small squares are dragged along the evaporator's edge to change where the pipe enters it.
  • Select an evaporator or pipe and press Delete to remove it. Undo with “Undo” or Ctrl/Cmd+Z.

4. Navigating the drawing

  • Drag the background to pan. Zoom with the buttons, with Ctrl/Cmd + mouse wheel, or by pinching on a trackpad. A− and A+ change the text size in the drawing.
  • “Re-render” redraws the drawing. “Print Drawing” prints the flow diagram together with a summary.
  • Tick “Force 90° Bends” to route every pipe in clean right angles; untick it to connect and drag pipes freely, however you like.
  • Tick “Force Parallel Lines” so that pipes running directly from a stem connect in line with the evaporator's connection and become one straight line with no bend. The tap point on the stem then follows along when you move the evaporator or its connection.

5. Power meter

  • Click “Add Power Meter” and then a pipe. The meter shows how many kW flow on each side of the point.
  • Drag the dot to measure at another place, drag the box to move the readout, and click × to remove the meter.

6. Reading the results

  • The cards at the top show total cooling load, total mass flow and the pipe size of the three main headers.
  • The tables list, for each evaporator and pipe run, the load, chosen pipe size, velocity and pressure drop (Δp). The program picks the smallest pipe size that stays within the target velocity.
  • ⚠ means the flow needs a larger pipe than the largest size in the table. 🚩 means two pipes or evaporators have the same name.
  • The bill of materials and the insulation list add up pipe lengths per size, without the fitting allowance. Use them as a basis when ordering.

7. Saving and opening

  • “Save” and “Save As…” store the whole plant as a file, and “Open Project” loads it again.
  • In Chrome and Edge, “Save” and autosave (every 5 minutes) write to the same file once you have saved once. Other browsers download a new file each time.

8. Units

  • Under “Options · Units” you choose the unit for temperature, superheat, pressure, velocity, length, power and mass flow separately. This only changes how values are shown and entered, not the calculations.

9. HC: glide, pressure drop in K, risers and hot gas

  • Zeotropic blends (e.g. R441A, R443A, R436A, R436B) have glide: at the same pressure the bubble point is lower than the dew point. Temperatures are entered as dew points; the glide and the liquid temperature are shown below the temperature fields.
  • The pressure drop is shown both as Δp and as ΔT, the drop in saturation temperature: on the dew line for suction and hot gas lines and on the bubble line for the liquid line. Common guide values are about 1 K for the suction line and 0.5–1 K for the liquid and hot gas lines.
  • Click a suction line and tick “Riser” if it runs upwards. The program then picks a size that gives the gas enough velocity to carry the oil (dimensionless gas velocity j*g ≥ 0.85) and shows the minimum velocity in brackets. ⇡🛢 means that even the smallest allowed size is not enough — consider a double riser.
  • The hot gas line runs from the compressors to the condenser and carries the whole mass flow. Enter its length, target velocity and discharge temperature (the gas density is taken at the condensing pressure and that temperature), and tick “Riser” if it runs upwards.
  • The design pressures are set automatically from the refrigerant (EN 378-2, ambient up to 32 °C) but can be changed under “Advanced – Margins & Pipe Material”.
  • A line marked as a riser (the flow goes upwards over its whole length) gets the weight of the liquid or gas column added to its pressure drop, about 10 kPa per metre for liquid. An evaporator above the plant room gives a liquid riser, one below it a suction riser. The check boxes are in the panel that opens when you click a line.
  • If the pressure drop of the liquid line to an evaporator is worth more than the subcooling, the liquid starts to boil before the expansion valve (flash gas). The calculator then warns with ⚠; increase the subcooling or choose larger pipes.
  • Gas lines are calculated with the gas expanding as the pressure falls, so even large pressure drops come out right. The calculation has been compared with Danfoss Coolselector 2 and agrees within 1–3 %.
  • The “Extra length for fittings (%)” allowance is meant to cover bends and valves. A 90° bend is worth about 0.2 m of pipe, so the default 30 % covers many bends.
  • Refrigerant charge (A3): the pipes are calculated automatically, the components from their inner volume and liquid share. Choose the application: refrigerating system (EN 378-1 table C.2: location class, access category and the volume of the smallest room), comfort cooling/heat pump (EN 378-1 C.2 and IEC 60335-2-40: 2.5 × LFL^1.25 × h0 × √A) or factory-built display cabinet (IEC 60335-2-89: 13 × LFL). Up to m1 = 4 m³ × LFL is always allowed. Yellow warning from 80 % of the limit, red above it. The check is a guide.
Disclaimer: This tool does not guarantee correct results. Always verify pipe wall thickness, pressure rating, and other values manually before installation.