Domestic Water Pipe Sizing

Size the cold and hot water riser with its branch-offs: probable flow by the chosen method, groups used all at once and continuous flows (emergency cooling), a pressure budget from the mains pressure with water meter and height, and size and velocity for every section.
DIN 1988-300 · 6.75 l/s · 600 kPa

Simultaneity

DIN 1988-300 (by building type)
V̇S = a·(ΣV̇R)^b − c [l/s] with the constants of the chosen building type.

Nominal flow per outlet

OutletPipeNominal flow (l/s)
Wash basinCW + HW
ShowerCW + HW
BathCW + HW
Kitchen sinkCW + HW
WC cisternCW
Washing machineCW
DishwasherCW
Hose tapCW
Flow per pipe. A mixing outlet counts with its full flow in both the cold and the hot water pipe. The values follow the chosen method (Swedish Säker Vatten and DS 439, or DIN 1988-300 table 2) and can be changed to the manufacturer's figures.

Water

Pressure and incoming main

Ask the water utility for the lowest and highest pressure at the connection point. The lowest pressure is used for sizing, the highest for the static pressure check.
EN 806-2 gives 500 kPa; follow national rules and the manufacturer's requirements.
The meter is chosen so that the design flow ≤ Q3, and its loss is taken as Δp at Q3 · (Q/Q3)². 63 kPa is the highest allowed by EN ISO 4064 (class Δp63); the manufacturer's value is often lower. Pressure reducing valve 0 = none.

Pipes and sizing

Europe's most common metal pipe for drinking water. Exposed runs, risers and plant rooms.
✓ Cold and hot water🌍 EuropeSizes 12×1 – 159×3
Usually at most 2 m/s. Hot water in copper: at most about 1.5 m/s to avoid erosion corrosion.
Added to each section's length for bends, tees and valves when the pressure drop is calculated.

Project

.html
File
Share and print

The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.

Units

Flow diagram

Cold water Hot water
100%
Drag from the + at a box or a branch-off to build pipes outwards: drop on empty space for a new branch-off, on a load to connect it. Right-click a pipe to add a load or a branch-off. Click a pipe, a branch-off or a load to change it. Drag boxes and branch-offs to move them.

Results per section

Show calculation

Calculation per pipe section

Pipe sectionMass flow [kg/s]Density [kg/m³]Inner diameter [mm]Velocity [m/s]ReFriction factor λLength (+ fittings) [m]Δp total [kPa]Δp per metre [Pa/m]Size · note
Cold water Incoming cold water → T14.698999.8601.6676,3000.019210 (+3)5.7344164×2
Cold water T1 → T24.028999.8601.4265,4000.019815 (+4.5)6.5333564×2
Cold water T2 → T33.028999.8501.5459,0000.020310 (+3)6.2648254×2
Cold water T3 → T41.78999.8391.4944,5000.021620 (+6)1661442×1,5
Cold water T4 → Changing room1.78999.8391.4944,5000.02163 (+0.9)2.3961442×1,5
Cold water T3 → T81.248999.8321.5538,0000.02243 (+0.9)3.2984235×1,5
Cold water T8 → Flats floor 10.7417999.825.61.4428,2000.0245 (+1.5)6.3297228×1,2
Cold water T8 → T101.132999.8321.4134,5000.02293 (+0.9)2.7670835×1,5
Cold water T10 → Flats floor 20.7417999.825.61.4428,2000.0245 (+1.5)6.3297228×1,2
Cold water T10 → T120.9784999.825.61.937,3000.02253 (+0.9)6.21,59028×1,2
Cold water T12 → Flats floor 30.7417999.825.61.4428,2000.0245 (+1.5)6.3297228×1,2
Cold water T12 → T140.7417999.825.61.4428,2000.0243 (+0.9)3.7997228×1,2
Cold water T14 → Flats floor 40.7417999.825.61.4428,2000.0245 (+1.5)6.3297228×1,2
Cold water T2 → Emergency cooling (mains-water-cooled HX)0.9998999.825.61.9438,1000.02243 (+0.9)6.441,65028×1,2
Cold water T1 → Laundry0.6699999.825.61.325,5000.02453 (+0.9)3.1781228×1,2
Hot water Water heater → T52.85985.8501.47144,0000.01695 (+1.5)2.3536154×2
Hot water T5 → T62.781985.8501.44141,0000.01725 (+7.5)11.234554×2
Hot water T6 → T71.755985.8391.49114,0000.017720 (+6)12.949842×1,5
Hot water T7 → Changing room1.755985.8391.49114,0000.01773 (+0.9)1.9449842×1,5
Hot water T6 → T91.026985.8321.2981,1000.0193 (+0.9)1.9249135×1,5
Hot water T9 → Flats floor 10.574985.825.61.1356,7000.02055 (+1.5)3.2950628×1,2
Hot water T9 → T110.9224985.8321.1672,9000.01943 (+0.9)1.5840535×1,5
Hot water T11 → Flats floor 20.574985.825.61.1356,7000.02055 (+1.5)3.2950628×1,2
Hot water T11 → T130.7853985.8320.99162,0000.02013 (+0.9)1.1930435×1,5
Hot water T13 → Flats floor 30.574985.825.61.1356,7000.02055 (+1.5)3.2950628×1,2
Hot water T13 → T150.574985.825.61.1356,7000.02053 (+0.9)1.9750628×1,2
Hot water T15 → Flats floor 40.574985.825.61.1356,7000.02055 (+1.5)3.2950628×1,2
Hot water T5 → Laundry0.069985.8100.89117,4000.02713 (+0.9)4.131,06012×1

Basis of calculation

Method
DIN 1988-300 (by building type)
Equations
  • Δp = λ · (L + L_eq)/d · ρv²/2
  • L_eq = L · 30 %
  • Δp_total = Δp + Δp_comp
  • Δp_h = ρ · g · Δh
Friction factor
Colebrook–White (Re ≥ 4000), 64/Re (Re < 2300)
Water properties
IAPWS-95 (CoolProp) 8.0.0
Standards
DIN 1988-300:2012 · EN 806-3 · EN 806-2
Notes
  • V̇S = a·(ΣV̇R)^b − c [l/s] with the constants of the chosen building type.
  • Copper EN 1057, ε = 0.0015 mm

Pressure at the loads

Pipe list

FAQ – domestic water pipe sizing

How do you size a domestic water supply pipe?

Add up the design flow rates of all outlets the pipe serves, convert the sum into a probable (simultaneous) flow and pick the smallest size that keeps the velocity below the limit. Then check that the pressure is enough at the worst outlet: the lowest mains pressure minus water meter, backflow preventer, height and pipe friction. The calculator does this for every pipe in the flow diagram.

Calculate it in the tool above

What are loading units and probable flow?

Each outlet has a design flow rate, e.g. 0.2 l/s for a shower and 0.1 l/s for a basin; in EN 806-3 this is expressed as loading units (1 LU = 0.1 l/s). Because not all outlets run at once, the pipe is sized for the probable flow, worked out from the sum with the Swedish probability formula, DS 439 or DIN 1988-300.

Calculate it in the tool above

How do I size the pipe for showers used all at once?

In changing rooms, school showers, laundries and industry everything really runs at the same time. Mark the load “all at once” and the full flow is used. Continuous flows, such as emergency cooling with a mains-water-cooled heat exchanger, are always added in full.

Calculate it in the tool above

What pressure loss can a water supply take?

A flow pressure of about 100 kPa at the outlet is a common requirement, more for some mixers and heat exchangers. Every metre of height costs about 10 kPa, plus the water meter, backflow preventer, filter and pipe friction. The static pressure at an outlet should not exceed 500 kPa (EN 806-2); above that a pressure reducing valve is needed.

Calculate it in the tool above

Can I use EN 806-3 pipe sizing with loading units?

EN 806-3 is the European basis for sizing water installations. The conversion curve of its simplified loading-unit method is not in the calculator yet. Use the Swedish method, DS 439 or DIN 1988-300 (which complements EN 806 in Germany) instead; the flow rates per outlet can be changed to match your data.

Calculate it in the tool above

What velocity should cold and hot water pipes be sized for?

Usually at most 2 m/s in cold water pipes and about 1.5 m/s for hot water in copper to avoid erosion corrosion. Lower velocities may be needed in homes to keep noise down. The limits can be changed in the calculator.

Calculate it in the tool above

Assumptions: Darcy–Weisbach with the Colebrook–White friction factor; water properties to IAPWS-95 at the cold and hot water temperature. Probable flow by the chosen method; branch-offs used all at once and continuous flows are added in full. The pressure is followed from the connection point (lowest pressure, no booster pumps) through the meter, backflow preventer, filter, pipes, components and height. If it is not enough, the section with the largest loss is upsized step by step. Inside diameters from the usual wall series of each standard – check with your supplier.

Disclaimer: The tool does not guarantee correct results. Always check sizes, pressures, pressure ratings and the applicable rules (EN 806, EN 1717 and national codes) manually before installation.

New feature – please report any errors: Report a bug

Help – domestic water pipe sizing

The calculator sizes a domestic water riser with branch-offs from the connection point outwards. It works out the probable flow and the pressure at every branch-off and proposes sizes for cold and hot water.

1. Method and nominal flows

  • Choose the calculation method. Click ? to read what the methods mean and when they are used. The method fills in the nominal flow per outlet, which you can change.
  • The probable flow is worked out again for every pipe from the sum of the nominal flows further out – the flows of the loads are never simply added.
  • Every menu has a ? that explains what the choice means and when it is used.

2. Pressure

  • Enter the lowest pressure at the connection point (for sizing) and the highest static pressure (for the EN 806-2 check).
  • The water meter is chosen from the design flow; enter the losses of the backflow preventer, filter and water heater. The calculator works without a booster pump.

3. The flow diagram

  • On the far left are the incoming cold water (blue) and the water heater (red). Drag from the + to build pipes outwards; drop on empty space for a branch-off, on a load to connect it.
  • Right-click a pipe and pick a load (shower, flat, mains-water-cooled HX …). A load that needs hot water is connected to the nearest hot water pipe by itself. “+ Load” places a free load that you connect afterwards.
  • Click a pipe for its length, height change, components and size; a load for its outlets, “Continuous flow, cold (emergency cooling, process)”, “Required flow pressure” and “All outlets at once (changing room, laundry)”.
  • Every load discharges to an unlimited drain. If the pressure is not enough, the pipe with the largest loss is upsized until it is. Delete removes the selection, “↩ Undo” undoes.
  • “Force 90° bends” gives right-angled pipes, “Force straight pipes” slides the branch-offs so the branches are straight. With “Move with the branch” (or Shift + drag) a riser or the heater moves with everything after it. The drawing area grows in every direction, so you can build upwards, downwards and sideways.

4. Results

  • The pressure is shown on every load. The tables show flow, size, velocity and pressure loss per pipe, the pressure at every load and a pipe list; click a row to find it in the diagram.
  • “Save” downloads the project as a file, “Open” opens it again, “Print” prints the diagram and the results.