GWP, ODP and CO2 Equivalent of Refrigerants

Pick a refrigerant and a charge: GWP, ODP and tonnes CO₂e, what the charge means under the F-gas Regulation (EU) 2024/573, the charge of each part of the plant and a comparison with other refrigerants.
R404A · 25.0 kg · 98.04 t CO₂e

Circuit / unit

R125 44 % · R143a 52 % · R134a 4 % · safety class A1 · HFCs and HFC blends
Enter the unit's rated cooling or heating capacity: it decides the 12 kW, 40 kW and 50 kW limits for new equipment.

Rule set and GWP values

Applies in the EU member states.
The legal requirements always use the rule set's own values. EU 2024/573: AR4 for HFCs and AR6 for HFOs. Other rule sets: AR4.

Project

.html
File
Share and print

The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.

Circuits and units in the project

Summary of all circuits

What the charge means – EU 2024/573

Timeline: Circuit 1

Dated bans already in force: 1. Next ban: 1 January 2032.

  • 1 January 2025 Ban Service ban: from 1 January 2025 virgin refrigerant with GWP ≥ 2500 may not be used to service or maintain refrigeration equipment, whatever the charge. Reclaimed or recycled refrigerant may be used until 31 December 2029. [Art. 13]
  • 1 January 2032 Ban Service ban: from 1 January 2032 virgin refrigerant with GWP ≥ 750 may not be used to service stationary refrigeration equipment (chillers excepted). Reclaimed or recycled refrigerant may still be used in existing equipment. [Art. 13]

Composition – Circuit 1 (R404A)

Alternative refrigerants – Circuit 1 (R404A, 25.0 kg)

The same charge of each refrigerant. Click a heading to sort. Retrofit and new unit are indicative: the manufacturer must approve the change, and the charge often changes.

Flow diagram – charge per part

Click a part to enter its charge. The parts add up to the charge of the circuit; the colour shows each part's share.
The diagram shows the charge spread as in operation, as you entered it.

Comparison – the same charge in other refrigerants

Sources

  • EU – Regulation (EU) 2024/573
  • Regulation (EU) 2024/573 on fluorinated greenhouse gases: Art. 5 (leak checks), Art. 6 (leakage detection systems), Art. 13 (bans on use for servicing), Annexes I and II (GWP), Annex IV (prohibitions on placing on the market). eur-lex.europa.eu
  • Regulation (EU) 2024/590 on substances that deplete the ozone layer (replaces (EC) No 1005/2009).
  • IPCC AR4 WG1 (2007) table 2.14, AR5 WG1 (2013) table 8.A.1, AR6 WG1 (2021) table 7.SM.7: 100-year GWP.
  • Montreal Protocol, Annexes A and C: ODP.
  • ANSI/ASHRAE 34 and ISO 817: refrigerant designation, composition and safety class.
  • Outside the EU: Kigali Amendment (2016) to the Montreal Protocol and US EPA AIM Act (2020).

GWP of refrigerants: R744, R290, R449A, R404A, R410A, R32, R134a, R22 (AR4, AR5, AR6)

Global warming potential over 100 years (GWP) of the refrigerants in the calculator, under the three IPCC assessment reports and as legally binding in the EU. The CO2 equivalent of a charge is the charge in kg times the GWP, divided by 1000.

RefrigerantSafety classGWP AR4 (IPCC 2007)GWP AR5 (IPCC 2013)GWP AR6 (IPCC 2021)GWP in the EU, (EU) 2024/573
R134aA11,4301,3001,5301,430
R404AA13,9223,9434,7283,922
R407AA12,1071,9232,2622,107
R407CA11,7741,6241,9081,774
R407FA11,8251,6741,9651,825
R407HA11,4951,3781,6151,495
R417AA12,3462,1272,5082,346
R442AA11,8881,7542,0421,888
R410AA12,0881,9242,2562,088
R32A2L675677771675
R422DA12,7292,4732,9172,729
R427AA12,1382,0242,3972,138
R448AA11,3871,2731,4941,386
R449AA11,3971,2821,5041,396
R452AA12,1401,9452,2922,139
R507AA13,9853,9854,7753,985
R1234yfA2L4< 10.5010.501
R1234ze(E)A2L7< 11.371.37
R1233zd(E)A1113.883.88
R454AA2L239238270237
R450AA1605547643601
R452BA2L698676779697
R454BA2L466467531465
R454CA2L148146166146
R455AA2L148146166146
R513AA1631573673629
R515BA1293299322288
R744A11111
R290A33330.020
R600aA33330
R1270A32220
R717B2L0000
R22A11,8101,7601,9601,810
R12A110,90010,20012,50010,900
R502A14,6574,7865,8724,657

Sources: IPCC Fourth Assessment Report (AR4) WG1 table 2.14, Fifth (AR5) table 8.A.1 and Sixth (AR6) table 7.SM.7; (EU) 2024/573 Annex I (HFCs, AR4), Annex II section 1 (HFOs, AR6) and Annex VI (propane 0.02, butane 0.006, isobutane, propylene and ammonia 0). Blends are the mass-weighted mean of their components; for HFOs without an AR4 value the figure of (EU) 517/2014 is used, and the AR5 value "< 1" is counted as 1. Propane, isobutane and propylene are not in the IPCC tables: literature values 3, 3 and 2 are shown. Safety class per ISO 817.

Frequently asked questions about GWP, CO2 equivalent and F-gases

What is GWP?

GWP (Global Warming Potential) states how much one kilogram of a substance warms the climate over 100 years compared with one kilogram of carbon dioxide (CO2), which has GWP 1. R134a has GWP 1430 according to AR4: one kilogram leaked equals 1430 kg of CO2. The values come from the IPCC assessment reports (AR4, AR5, AR6).

Calculate it in the tool above ↑

What is CO2 equivalent (CO2e)?

CO2 equivalent (CO2e) is a leak or a refrigerant charge converted into the amount of carbon dioxide that would have the same climate impact. It is calculated as kg × GWP and usually given in tonnes (t CO2e). For example, 10 kg R410A (GWP 2088) = 20.88 t CO2e. The F-gas thresholds for leak checks and bans are given in t CO2e.

Calculate it in the tool above ↑

How do you calculate the CO2 equivalent of a refrigerant charge?

Multiply the charge in kg by the GWP of the refrigerant and divide by 1000 to get tonnes CO2 equivalent (t CO2e). Example: 25 kg of R404A with GWP 3922 gives 25 × 3922 / 1000 = 98.05 t CO2e.

Calculate it in the tool above ↑

Which GWP value is legally binding in the EU?

The F-gas Regulation (EU) 2024/573 uses the GWP of the IPCC Fourth Assessment Report (AR4) for the HFCs of Annex I and AR6 for the HFOs of Annex II. Blends use the mass-weighted mean. Newer AR5 and AR6 values for HFCs can be shown for comparison but do not decide the legal requirements.

Calculate it in the tool above ↑

How often must a system be leak checked?

From 5 t CO2e at least every 12 months, from 50 t CO2e every 6 months and from 500 t CO2e every 3 months. A leak detection system doubles the intervals. For pure HFOs the thresholds are 1, 10 and 100 kg. Hermetically sealed systems below 10 t CO2e (or 2 kg of HFO) are exempt (Article 5).

Calculate it in the tool above ↑Knowledge base: laws and rules →

Which refrigerants are banned for servicing?

Since 1 January 2025 virgin refrigerant with GWP ≥ 2500, for example R404A, R507A and R422D, may not be used to service refrigeration equipment. Reclaimed or recycled refrigerant may be used until the end of 2029. For air conditioning and heat pumps the same limit applies from 2026. From 2032 the limit is GWP 750 for stationary refrigeration except chillers (Article 13).

Calculate it in the tool above ↑Refrigerant retrofit: find alternatives →

What is ODP?

ODP (ozone depletion potential) tells how much a substance depletes the ozone layer compared with CFC-11. R12 has ODP 1 and R22 has 0.055. HFCs, HFOs and natural refrigerants have ODP 0. Ozone-depleting substances are banned in the EU under Regulation (EU) 2024/590.

Calculate it in the tool above ↑

What does a switch to a low-GWP refrigerant give?

The same charge of R744 (GWP 1), R290 (GWP 0.02 under Annex VI of the F-gas Regulation, about 3 in the literature) or R1234ze(E) (GWP 1.37) gives only a fraction of the CO2e of R404A. Leak checks under the F-gas Regulation are then often not required at all. The comparison in the app shows the effect for your own charge.

Calculate it in the tool above ↑Refrigerant retrofit: find alternatives →

What is the GWP of R449A?

R449A is a blend of R32, R125, R1234yf and R134a. Its GWP is 1397 with the IPCC AR4 values (the basis of the F-gas Regulation for HFCs), 1282 with AR5 and 1504 with AR6. The value that is legally binding in the EU under (EU) 2024/573 is 1396 (AR4 for the HFCs, AR6 for the HFO R1234yf). A charge of 10 kg is about 14 t CO2e.

Calculate it in the tool above ↑

What is the GWP of R404A?

R404A has GWP 3922 in the EU (AR4: 3922, AR5: 3943, AR6: 4728). A charge of 10 kg is 39.2 t CO2e. Because the GWP is 2500 or more, virgin R404A may not be used to service refrigeration equipment since 1 January 2025.

Calculate it in the tool above ↑

What is the GWP of R410A?

R410A (R32 and R125, 50 % each) has GWP 2088 with AR4, which is the value used in the EU, 1924 with AR5 and 2256 with AR6. A charge of 10 kg is 20.9 t CO2e, so the leak check interval is 12 months from 5 t CO2e.

Calculate it in the tool above ↑

What is the GWP of R134a?

R134a (HFC-134a) has GWP 1430 with AR4, which is the value used in the EU, 1300 with AR5 and 1530 with AR6. A charge of 10 kg is 14.3 t CO2e.

Calculate it in the tool above ↑

What is the GWP of R32?

R32 (HFC-32, difluoromethane) has GWP 675 with AR4, which is the value used in the EU, 677 with AR5 and 771 with AR6. A charge of 10 kg is 6.75 t CO2e.

Calculate it in the tool above ↑

What is the GWP and ODP of R22?

R22 (HCFC-22) has GWP 1810 with AR4, 1760 with AR5 and 1960 with AR6, and ODP 0.055. It is an ozone-depleting substance: production and import are banned, and in the EU it may no longer be used to service equipment (Regulation (EU) 2024/590).

Calculate it in the tool above ↑

What is the GWP of R744 (CO2)?

R744 is carbon dioxide. Its GWP is 1 by definition in all the assessment reports, so a charge of 10 kg is 0.01 t CO2e. As a natural refrigerant it is not an F-gas and is not covered by the leak check intervals of the F-gas Regulation.

Calculate it in the tool above ↑

What is the GWP of R290 (propane)?

Propane is not in the IPCC tables. The literature value is about 3, and Annex VI of (EU) 2024/573 gives 0.02 for propane when the GWP of a blend is calculated. Either way a charge of 1 kg is negligible: 0.003 t CO2e or less. R290 is flammable (A3), so the charge is limited by the safety standards.

Calculate it in the tool above ↑

Assumptions: t CO₂e = kg × GWP / 1000. 100-year GWP; blends as the mass-weighted mean of their components. The legal requirements are assessed per circuit (piece of equipment) with the chosen rule set's GWP values and today's date. Charge in kg, g, lb or oz.

Disclaimer: This tool is an aid and does not replace the text of the Regulation. Always check requirements, dates and exemptions against the legislation in force and national rules. No warranty is given for the correctness of the results.

Help – GWP, ODP and CO2 equivalent

The calculator shows the GWP and ODP of a refrigerant, converts the charge into tonnes CO2 equivalent and shows what the charge means under the F-gas Regulation (EU) 2024/573.

1. Refrigerant and charge

  • Pick the refrigerant in the list. Below the list you see its composition in mass-% and its safety class.
  • Enter the charge in kg, g, lb or oz. It is spread over the parts of the flow diagram in the same proportions as before.
  • Pick the type of equipment and tick hermetically sealed, leak detection system, cooling below −50 °C and new equipment where they apply. They change the requirements.

2. Several circuits

  • Each refrigeration circuit or unit is assessed on its own, because the requirements apply per piece of equipment. Add more with + New circuit.
  • Click a row of the table to select that circuit. The table shows the total per circuit and for the whole project.

3. GWP values

  • Choose the rule set (country): EU, United Kingdom, Norway, Türkiye, USA, Japan or other countries. The requirements, limits and GWP values follow the choice.
  • GWP values shown: the rule set's own values (legally binding) or AR4, AR5 and AR6 for comparison. The legal requirements always use the rule set's values.
  • Alternative refrigerants shows the same charge in possible replacements. Click a heading to sort, for example by GWP.

4. Flow diagram

  • The diagram shows the compressor rack, discharge line, condenser, receiver, liquid line, evaporators and suction line.
  • Click a part and enter its charge in the table below the diagram. The parts add up to the charge of the circuit.
  • Add or remove evaporators with the buttons below the diagram. The colour shows each part's share of the charge and of the CO2e.

5. Requirements, comparison and print

  • What the charge means lists leak checks, leak detection systems and service bans with the article. Red text means a ban applies now.
  • The comparison shows the same charge in every refrigerant of the app, sorted by GWP.
  • Save and Open save and open the project as a file. Print gives a report, with the flow diagram on a page of its own.