Tip: drag the yellow handle on the insulation in or out – it snaps to the stocked thicknesses. Material, jacket and vapour barrier apply to the whole project.
| Pipe | Pipe OD [mm] | Thickness [mm] | θm [°C] | λ [W/(m·K)] | De [mm] | hcv [W/(m²·K)] | hr [W/(m²·K)] | R′ins [m·K/W] | R′se [m·K/W] | θs [°C] | θd [°C] | q′ [W/m] | Bare pipe [W/m] | sd [m] | Length [m] | Notes |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Chilled water supply | 35 | 6 | 12.3 | 0.0342 | 47 | 4.29 | 5.24 | 1.37 | 0.711 | 18.5 | 16.7 | 9.13 | 19.5 | 42 | 25 | |
| Suction line | 28.6 | 9 | 3.45 | 0.0333 | 46.57 | 4.54 | 5.19 | 2.33 | 0.702 | 16.9 | 16.7 | 11.5 | 32.7 | 63 | 15 | |
| Split AC liquid/suction | 15.9 | 13 | 16.8 | 0.0347 | 41.87 | 22.8 | 5.65 | 4.45 | 0.267 | 28.6 | 28.2 | 5.3 | 35.5 | 91 | 12 | |
| Heating flow | 33.7 | 0 | 55 | 0.0385 | 33.7 | 6.83 | 6.28 | 0 | 0.72 | 55 | 16.7 | -41.6 | -39.4 | 0 | 30 | Surface 55.0 °C: touch protection |
| Hot water circulation | 22 | 0 | 60 | 0.039 | 22 | 7.89 | 6.44 | 0 | 1.01 | 60 | 16.7 | -34.7 | -29.5 | 0 | 15 | Surface 60.0 °C: touch protection |
| Cold water | 18 | 6 | 15.1 | 0.0345 | 30 | 4.43 | 5.28 | 2.36 | 1.09 | 20.2 | 16.7 | 4.35 | 8.53 | 42 | 10 | |
| Liquid line | 22.2 | 6 | 13.7 | 0.0344 | 34.23 | 4.45 | 5.26 | 2 | 0.957 | 19.5 | 16.7 | 5.75 | 11.7 | 42 | 15 | |
| Hot gas line | 22.2 | 0 | 70 | 0.04 | 22.22 | 8.38 | 6.76 | 0 | 0.945 | 70 | 16.7 | -47.6 | -40.5 | 0 | 10 |
q′ = (θa − θf) / (R′ins + R′se)R′ins = ln(De/Do) / (2π·λ(θm)), θm = (θf + θs)/2R′se = 1 / (hse·π·De), hse = hcv + hrhcv = 1,25·(ΔT/De)^0,25 (De³ΔT ≤ 10) | 1,21·ΔT^(1/3) | 8,1·10⁻³/De + 3,14·√(v/De) | 8,9·v^0,9/De^0,1hr = ε·σ·(Ts⁴ − Ta⁴)/(Ts − Ta)θs = θa − q′·R′se ≥ θd + Δθθd: Magnus, a = 17,62, b = 243,12 °Cd = D/2·[exp(λ/λref·ln((D + 2·dref)/D)) − 1]sd = μ·d, Z ≈ 5·sd MPa·m²·s/gThick enough that the outer surface stays at or above the dew point of the surrounding air. At 25 °C and 60 % relative humidity the dew point is about 16.7 °C; a 28 mm copper chilled water pipe at 6 °C in still air then needs about 4 mm of elastomeric foam with a black surface (in practice the thinnest stocked size) and about 7 mm under a bright aluminium jacket. More humidity, a colder fluid or a draught-free corner quickly needs more. The calculator finds the smallest thickness for each pipe (EN ISO 12241).
A bright metal surface radiates very little heat (emissivity about 0.05–0.15 against 0.9 for rubber or paint), so the outside heat transfer coefficient is lower and the surface stays closer to the pipe temperature. On cold pipes that means a colder surface and more insulation to stay above the dew point.
Yes. Water vapour diffuses from the warm air towards the cold pipe and condenses inside the insulation if the material lets it through. Closed-cell materials such as flexible elastomeric foam or cellular glass act as their own barrier; mineral wool and PIR need a sealed vapour barrier on the outside (EN ISO 15758). Spain's RITE asks for more than 50 MPa·m²·s/g, Australia's NCC J6D9 for a barrier on all cooling fluids.
Some countries have tables in the law: Germany (GModG Annex 8), Spain (RITE IT 1.2.4.2.1), England (Approved Document L), Australia (NCC J6D9 as R-value) and the Swiss cantons. Others, such as Sweden, Finland and Norway, have no table and count the losses in the building's energy performance. The legal tables are energy requirements: the calculator always also checks condensation and uses the larger thickness.