Electrical Calculator

Current, power, voltage, impedance, motors, cables and fuses – for buildings, boats and ships. Choose the grid, the calculation and fill in the fields; "?" explains each one.
A calculation aid only. Electrical installation work may only be done by a qualified, authorised electrician. Electrical installation work may only be carried out by a qualified, authorised electrician according to the rules of the country (and on ships the class society's rules). Check every result against the standards, the manufacturer's data and the actual installation.

1Country / grid type

2Calculation

Basics – current, power, voltage
Motors and power factor
Cables, fuses and voltage drop
Distribution board, RCD and IP code
Battery and DC on boats

3Input

Project

.html
File
Share and print

The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened. Like the project file, it contains all project data – share it only with people who may see it.

Results

Wiring diagram

Click a part of the diagram – supply, board, cable, load … – to rename it or change its values.
Single-line view of the calculation: source, protective device, cable and load. Conductors: L/L1–L3 phase, N neutral, PE protective earth; DC + and −.

Formulas

    Sources

    • USA, homes: 120/240 V single-phase three-wire (split phase), 60 Hz – ANSI C84.1 (range A ±5 %). Installations: NFPA 70 National Electrical Code (NEC); voltage drop: NEC 210.19(A) informational note, 3 % for a branch circuit and 5 % for feeder plus branch. Edition: NEC 2023 in most states; NEC 2026 is being adopted (e.g. Washington from 2026-12-31) – check the edition your state has adopted.
    • IEC 60038:2009 – IEC standard voltages.
    • IEC 60364-4-43 – Protection against overcurrent (433.1: Ib ≤ In ≤ Iz, I2 ≤ 1.45 Iz).
    • IEC 60364-5-52:2009+AMD1:2024 – Selection and erection of wiring systems: annex B (current-carrying capacity, tables B.52.2–B.52.5, B.52.14, B.52.17), annex G (voltage drop), table 52.2 (minimum cross-sections).
    • IEC 60228 – Conductors of insulated cables (resistance of copper and aluminium).
    • IEC 60034-1 – Rotating electrical machines, rating and performance; IEC 60947-4-1 – Contactors and motor starters.
    • IEC 60898-1 (circuit breakers) and IEC 60269 (fuses); IEC 60831 (shunt power capacitors).
    • NFPA 70 National Electrical Code (NEC): 210.19, 210.20, 240.4, 240.6, 310.15, 310.16, 430.22, 430.32, 430.52.
    • IEC 60092 series – Electrical installations in ships (101, 201, 202, 352, 503); SOLAS chapter II-1 part D.
    • ISO 13297:2020 – Small craft, AC and DC electrical systems; ABYC E-11 – AC and DC electrical systems on boats.
    • IEC 60364-4-41 (protection against electric shock: table 41.1 disconnection times, 411.3.3 additional protection), IEC 60364-5-53 (RCD types), IEC 60364-7-701, -7-709, -7-722.
    • IEC 60909-0 (short-circuit currents, voltage factor cmin 0.95); IEC 60269-1 (conventional test currents of fuses); IEC 60076 (power transformers); IEC 60034-30-1 (efficiency classes IE).
    • BS 7671:2018+A4:2026 table 4D5 (flat twin and earth), table 41.2; 電気設備の技術基準の解釈 第149条; NEC table 430.250 (motor full-load currents).
    • ABYC E-11 table VI and 33 CFR 183.425 table 5 (USCG; allowable amperage of conductors, boats; same values); IEC 60092-352 table A.1 (ships, 45 °C).

    Frequently asked questions

    How many amps does a three-phase motor draw?

    I = P / (√3 · U · cos φ · η), with P the rated output on the nameplate. Example: 90 W, 400 V, star (Y), cos φ 0.80, η 85 %: I = 90 / (1.732 · 400 · 0.80 · 0.85) ≈ 0.19 A. A 7.5 kW motor at 400 V with cos φ 0.85 and η 90 % draws about 14 A. The nameplate current is the best figure; the formula is for checking or when it is missing.

    Calculate it in the tool above: Motor current from the nameplate

    How do I calculate current from power?

    DC: I = P / U. Single-phase: I = P / (U · cos φ). Three-phase: I = P / (√3 · U · cos φ), with U the line voltage. 2 kW at 230 V with cos φ 1.0 is 8.7 A; 10 kW three-phase at 400 V with cos φ 0.85 is 17 A; 60 W at 12 V DC is 5 A.

    Calculate it in the tool above: Current, power and impedance

    Should the motor be connected in star or delta?

    The nameplate gives two voltages, e.g. 230/400 V Δ/Y. Connect in delta when the grid's line voltage equals the lower one and in star when it equals the higher one. A 230/400 V motor on a 400 V grid is connected in star; a 400/690 V motor on 400 V in delta – and only that motor can be started star-delta. The same load takes three times the power in delta as in star.

    Calculate it in the tool above: Star/delta (Y/Δ) connection

    How much voltage drop is allowed?

    IEC 60364-5-52 annex G recommends 3 % for lighting and 5 % for other loads from a public low-voltage supply; the US NEC recommends 3 % for a branch circuit and 5 % in total; Australia and New Zealand allow 5 % (AS/NZS 3000). On boats ISO 13297 and ABYC E-11 allow 3 % for critical DC loads and 10 % for others; on ships 6 % (IEC 60092-352). The national rules always apply.

    Calculate it in the tool above: Voltage drop in a cable

    What size capacitor do I need for power factor correction?

    Qc = P · (tan φ1 − tan φ2). Raising 50 kW from cos φ 0.75 to 0.95 needs 50 · (0.882 − 0.329) ≈ 27.7 kvar. At 400 V 50 Hz in delta, each of the three capacitors is Qc / (3 · 2π · 50 · 400²) ≈ 183 µF. Aim for 0.95–0.98, not higher, and use detuned banks where there are frequency converters.

    Calculate it in the tool above: Power factor correction (capacitor)

    Which voltages are used on boats and ships?

    Leisure boats: 12 V or 24 V DC from batteries, and 230 V 50 Hz (Europe) or 120/240 V 60 Hz (USA) from shore power or an inverter (ISO 13297, ABYC E-11). Ships: mostly 440 V 60 Hz three-phase, also 400 V 50 Hz and 690 V, as insulated (IT) systems without neutral and with earth-fault monitoring, lighting at 230 V or 115 V through transformers; large ships 6.6 kV or 11 kV (IEC 60092, SOLAS).

    Calculate it in the tool above: Battery and DC consumption

    Assumptions: Sinusoidal voltage and balanced three-phase loads. Three-phase voltage U is the line-to-line voltage. Cable resistance at the conductor temperature (70 °C PVC, 90 °C XLPE for sizing), reactance 0.08 mΩ/m. Current-carrying capacity: the table and installation method of the chosen country (IEC 60364-5-52, BS 7671, NEC table 310.16, 電技解釈, ABYC E-11, IEC 60092-352), copper; aluminium from the IEC aluminium columns (about 0.75 × copper). Fuse ratings are standard series; the device's own data apply.

    Disclaimer: The results are guidance for design and checking. They do not replace the national installation rules, a qualified electrician's assessment or the manufacturer's instructions. CO2piping.com accepts no liability for installations based on the calculator.

    New feature – please report any errors: Report a bug

    Help

    Choose the country or grid type, simple or advanced mode and a calculation. Fill in the fields – "?" next to each one explains what to enter. Results, wiring diagram and formulas update at once.

    Grid and country

    • The grid sets voltage, frequency, earthing system, voltage-drop limit and the cable and fuse tables (IEC or NEC). The source is shown under the menu and in the source list.
    • Boats: 12/24 V DC and shore power. Ships: 400 V 50 Hz, 440 V and 690 V 60 Hz insulated (IT) systems.
    • Own values: any voltage and frequency, with IEC tables.

    Simple mode

    • Current, power and impedance: from voltage, cos φ and one known quantity.
    • Ohm's law: any two of U, I, R and P.
    • Frequency, speed and reactance; efficiency and power factor.
    • Cable table: the largest breaker and fuse for every cable size, by country and installation method.

    Advanced mode

    • Motor current from the nameplate with star/delta connection and starting current; starting methods compared.
    • Star/delta: the same load in Y and Δ.
    • Voltage drop; cable size and fuse with correction for ambient temperature and grouping.
    • Power factor correction and battery capacity.
    • Short circuit: earth-fault current at the load and whether the device disconnects in 0.4 s / 5 s.
    • Distribution board: groups per phase, simultaneity and main fuse; transformer; selectivity; RCD selection.

    Units

    • Power in W, kW or hp, length in m or ft. Three-phase voltage is always the line voltage (e.g. 400 V).

    Files and print

    • Save stores the calculation as a file, Open opens it again.
    • Print: report with results and formulas; the wiring diagram on a page of its own, with www.co2piping.com. Choose A4, A3 or larger in the print dialog – the report fills the sheet.