co2piping.com
Troubleshooting

Alarm and fault codes of common controllers

A selection of common alarm and fault codes, ordered by cause, with what they mean, what to check and which symptom to troubleshoot further.

Field mode: large buttons, questions first and the screen kept on.
Codes and meanings vary between controller models and firmware versions. Always check the manufacturer's manual for your unit. For guidance only; work on refrigeration and electrical systems must be carried out by qualified personnel. Terms of use
💡 Find a light signal (blinking or steady lamp)

All light signals of the chosen manufacturer (or of all) are shown below as lamps that blink as on the unit: faults and status lamps. Narrow them down with the colour and the number of flashes, and tap the one that matches to see what it means.

Temperature too high

ControllerCode
Danfoss ERC 21X[1]A01
Danfoss EKC 202A/B/C[2]A1
Danfoss AK-CC 550A[3]A1
Carel MPX[6]HI
Carel MasterCella[7]HI
Dixell XW270L/XW271L[9]HA
Zanotti GM/GS[10]AH1
Carel ir33[11]HI
Carel ir33[11]HA
Carel ir33[11]HF
Dixell XR60CX[12]HA
Eliwell ID 974[13]AH1
Carel Heos[18]HI
Carel ir33 universale[19]E04
Carel ir33 universale[19]E15
Carel ir33+ VCC[20]HI
Carel ir33+ VCC[20]HA
Carel MPXone[21]HI
Carel MPXone[21]HA
Carel SmartCella / SmartCella 3PH[24]HI
Carel SmartCella / SmartCella 3PH[24]HA
Carel SmartCella / SmartCella 3PH[24]HF
Copeland EXD-SH1/2[26]tAH1
Heatcraft Beacon II[30]A1
Heatcraft Beacon II[30]BOXHI
Danfoss AK-CC 450[32]A1
Danfoss AK-CC 450[32]A13
Danfoss AK-CC 450[32]A70
Danfoss AK-CC 450[32]A72
Danfoss AK-CC 550 / 550B[33]A1
Danfoss AK-CC 550 / 550B[33]A13
Danfoss AK-CC 550 / 550B[33]A70
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A01
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A13
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A70
Danfoss AK-CC55 Water Loop[35]A01
Danfoss AK-CC 750[36]High air temp.
Danfoss AK-CC 750[36]High Prod. temp.
Danfoss Optyma control AK-RC 113[39]EH
Danfoss EKC 202D1[41]A1
Danfoss EKC 202D1[41]A8
Danfoss EKE 1A/1B/1C/1D[43]A993
Danfoss EKE 100[44]A28
Danfoss AK-RC 251[47]AH
Danfoss AK-RC 251[47]HCP
Dixell XM669K/XM679K[50]HA
Dixell XM669K/XM679K[50]HA2
Dixell XR06CX[51]HA
Dixell XR35CX[52]HA
Dixell XR460C[53]HA
Dixell XR70CX[54]HA
Dixell XW60K/XW60L[55]HA
Dixell XWi70K[56]HA
Carel µC2SE for process chiller[59]Ht
Carel µChiller[60]A15
Secop SLV controller 105N46xx[81]A20
Secop SLV controller 105N46xx[81]A60
Secop SLV controller 105N46xx[81]A75
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E20
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E21
AHT GD-Cooler (GD-XLS, GD-XL)[84]HA
AHT plug-in cases with Danfoss controller (Paris, Ibiza, Malta, Manhattan)[85]Hi
Pego ECP200 EXPERT PULSE[89]EH
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]EH
RDM DMTouch / miniDM[91]Probe OT
RDM DMTouch / miniDM[91]Pack CPT Fault
RDM Mercury 3 Twin Coil[92]Ot AL
Störk-Tronic ST121 / ST501 / ST551[93]Hi
Evco EV3203[107]AH
Evco EV3 300 series[108]AL
Evco EVK214[109]AH
Full Gauge TC-900E POWER / TC-900E 2HP[117]Ahi
Full Gauge TC-900E Log[118]Athi
Full Gauge TC-940R[119]AHi
Full Gauge MT-514E Faston[122]Athi
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A05
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Ot
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Ot AL
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LgOt
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Ot
RDM Mercury / Intuitive Mercury thermostats and monitors[129]OT 1–OT 5
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Ot 1–Ot 6
RDM Mercury AC and roof top unit controllers[130]Evap. Out Temp. OT Alarm
RDM Mercury AC and roof top unit controllers[130]Evap. In Temp. OT Alarm
RDM Mercury AC and roof top unit controllers[130]Over Temperature
RDM Mercury AC and roof top unit controllers[130]Ot AL
RDM ML Controller case controller[134]AL
RDM ML Controller case controller[134]PrAL
RDM DMTouch / miniDM[91]CPT OT
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Hi
Danfoss ETC (True cabinets)[142]Hi
Danfoss EETa (True cabinets, LED blink codes)[143]1+1 flashes
Carel PQ (True cabinets)[144]HI
Dixell XR/XW (True cabinets)[145]HA
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]hi
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]AH1
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]BARREL TEMP 2 HIGH
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HPR>41°F (5°C) AFTER 4 HR
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BRL>41°F (5°C) AFTER 4 HR
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HPR>45°F (7°C) AFTER 1 HR
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HPR>59°F (15°C)
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]HPR>41F (5C) AFTER 4 HR
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BRL>41F (5C) AFTER 4 HR
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]HPR>41F (5C) AFTER PF
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BRL>41F (5C) AFTER PF
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]HPR>45F (7C) AFTER 1 HR
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BRL>45F (7C) AFTER 1 HR
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]HPR>59F (15C)
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BRL>59F (15C)
Taylor R160 frozen food dispenser[156]HA
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]HA
Carel MPXzero (Hillphoenix display cases)[160]HI
Carel MPXzero (Hillphoenix display cases)[160]HI2
Carel MPXzero (Hillphoenix display cases)[160]HA
Carel MPXzero (Hillphoenix display cases)[160]HF
Carel iJF with VCC (Hillphoenix SMD-H)[161]HI
Carel iJF with VCC (Hillphoenix SMD-H)[161]HA
Carel iJF with VCC (Hillphoenix SMD-H)[161]HF
Copeland (CPC) E2 RX/BX/CX controller[163]Case Temp Hi Limit Exceeded
LAE AT1-5/AT2-5[166]HI
Pego 202BASE electronic board[167]EH
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_LvgWaterTempHigh
BAC TrilliumSeries adiabatic cooler TRF[174]18
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]HI
Carel MPXone[21]HACCP LED flashingA HACCP alarm (HA/HF, temperature too high for too long) has occurred. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon HACCP onHACCP alarm (high temperature during operation or after power failure) is active. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Warning lamp 5 redOptional warning lamp: the cabinet is too warm (also lit after restart until the temperature is reached).
AHT electronic controller (plug-in cases, standard)[82]Display flashing temperatureElectronic controller: excessive temperature alarm. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon HACCP steadyHACCP alarm active: room above h1 for longer than h2. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon HACCP flashingA HACCP alarm has been recorded and not yet confirmed; press mute to confirm. (The manual does not give the colour.)
Carel µChiller[60]Cooling mode icon flashingWater temperature is too high. (The manual does not give the colour.)

The air temperature has been above the set high temperature limit for longer than the alarm delay.

Check: Check that compressor, fans and defrost work and that the door is closed. Compare the sensor with a calibrated thermometer.

Temperature too low

ControllerCode
Danfoss ERC 21X[1]A02
Danfoss EKC 202A/B/C[2]A2
Danfoss AK-CC 550A[3]A2
Carel MPX[6]LO
Carel MasterCella[7]LO
Dixell XW270L/XW271L[9]LA
Zanotti GM/GS[10]AL1
Carel ir33[11]LO
Dixell XR60CX[12]LA
Eliwell ID 974[13]AL1
Carel Heos[18]Lo
Carel ir33 universale[19]E05
Carel ir33 universale[19]E16
Carel ir33+ VCC[20]LO
Carel MPXone[21]LO
Carel SmartCella / SmartCella 3PH[24]LO
Copeland EXD-SH1/2[26]tAL1
Heatcraft Beacon II[30]A2
Heatcraft Beacon II[30]BOXLO
Danfoss AK-CC 450[32]A2
Danfoss AK-CC 450[32]A14
Danfoss AK-CC 450[32]A71
Danfoss AK-CC 450[32]A73
Danfoss AK-CC 550 / 550B[33]A2
Danfoss AK-CC 550 / 550B[33]A14
Danfoss AK-CC 550 / 550B[33]A71
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A02
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A14
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A71
Danfoss AK-CC55 Water Loop[35]A02
Danfoss AK-CC 750[36]Low air temp.
Danfoss AK-CC 750[36]Frost protection, too low S4
Danfoss AK-CC 750[36]Low prod. temp.
Danfoss Optyma control AK-RC 113[39]EL
Danfoss EKC 202D1[41]A2
Danfoss EKC 202D1[41]A9
Danfoss EKE 1A/1B/1C/1D[43]A992
Danfoss EKE 100[44]A29
Danfoss AK-RC 251[47]AL
Dixell XM669K/XM679K[50]LA
Dixell XM669K/XM679K[50]LA2
Dixell XR06CX[51]LA
Dixell XR35CX[52]LA
Dixell XR460C[53]LA
Dixell XR70CX[54]LA
Dixell XW60K/XW60L[55]LA
Dixell XWi70K[56]LA
Carel µC2SE for process chiller[59]Lt
Secop SLV controller 105N46xx[81]A43
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E43
AHT GD-Cooler (GD-XLS, GD-XL)[84]LA
AHT plug-in cases with Danfoss controller (Paris, Ibiza, Malta, Manhattan)[85]Lo
Pego ECP200 EXPERT PULSE[89]EL
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]EL
RDM DMTouch / miniDM[91]Probe UT
RDM Mercury 3 Twin Coil[92]Ut AL
Störk-Tronic ST121 / ST501 / ST551[93]Lo
Evco EV3203[107]AL
Evco EVK214[109]AL
Full Gauge TC-900E POWER / TC-900E 2HP[117]Alo
Full Gauge TC-900E Log[118]Atlo
Full Gauge TC-940R[119]ALo
Full Gauge MT-514E Faston[122]Atlo
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A02
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Ut
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Ut AL
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LgUt
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Ut
RDM Mercury / Intuitive Mercury thermostats and monitors[129]UT 1–UT 5
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Ut 1–Ut 6
RDM Mercury AC and roof top unit controllers[130]Evap. Out Temp. UT Alarm
RDM Mercury AC and roof top unit controllers[130]Evap. In Temp. UT Alarm
RDM Mercury AC and roof top unit controllers[130]Under Temperature
RDM Mercury AC and roof top unit controllers[130]Ut AL
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Lo
Danfoss ETC (True cabinets)[142]Lo
Carel PQ (True cabinets)[144]LO
Dixell XR/XW (True cabinets)[145]LA
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Lo
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]AL1
Taylor R160 frozen food dispenser[156]LA
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LA
Carel MPXzero (Hillphoenix display cases)[160]LO
Carel MPXzero (Hillphoenix display cases)[160]LO2
Carel iJF with VCC (Hillphoenix SMD-H)[161]LO
Copeland (CPC) E2 RX/BX/CX controller[163]Case Temp Low Limit Exceeded
LAE AT1-5/AT2-5[166]LO
Pego 202BASE electronic board[167]EL
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_LvgWaterTempLow
BAC TrilliumSeries adiabatic cooler TRF[174]5
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]LO

The air temperature has been below the set low temperature limit for longer than the alarm delay.

Check: Check that the control cuts out and that the solenoid valve and contactor release. Compare the sensor with a thermometer.

Door open too long

ControllerCode
Danfoss ERC 21X[1]A04
Danfoss EKC 202A/B/C[2]A4
Zanotti GM/GS[10]OPd
Copeland EazyCool ZX (XCM25D)[5]E66
Carel ir33[11]dor
Dixell XR60CX[12]dA
Eliwell ID 974[13]OPd
Carel Heos[18]dr
Carel ir33+ VCC[20]dor
Carel MPXone[21]dor
Carel SmartCella / SmartCella 3PH[24]dor
Danfoss AK-CC 450[32]A4
Danfoss AK-CC 550 / 550B[33]A4
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A04
Danfoss AK-CC55 Water Loop[35]A04
Danfoss AK-CC 750[36]Door open alarm
Danfoss Optyma control AK-RC 113[39]Ed
Danfoss EKC 202D1[41]A4
Danfoss AK-RC 251[47]Ad0
Dixell XM669K/XM679K[50]dA
Dixell XR06CX[51]dA
Dixell XR35CX[52]dA
Dixell XR460C[53]dA
Dixell XR70CX[54]dA
Dixell XW60K/XW60L[55]dA
Dixell XWi70K[56]dA
Secop SLV controller 105N46xx[81]A04
Pego ECP200 EXPERT PULSE[89]Ed
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]Ed
RDM Mercury 3 Twin Coil[92]door
Störk-Tronic ST121 / ST501 / ST551[93]E5
Evco EV3203[107]id
Evco EVK214[109]id
Full Gauge TC-900E POWER / TC-900E 2HP[117]AOPn
Full Gauge TC-900E Log[118]AOPn
Full Gauge MT-514E Faston[122]AOPn
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]door
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]dor
Carel PQ (True cabinets)[144]dOr
Dixell XR/XW (True cabinets)[145]dA
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]do
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]OPd
Taylor C392/C393/C394 frozen beverage freezers[150]Product Door Off
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]PRODUCT DOOR OFF
Taylor 736 soft serve freezer[153]DOOR O.
Taylor Icetro ISI-161TH/ISI-161TI[154]Er18
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er18
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]dA
Carel MPXzero (Hillphoenix display cases)[160]dor
Carel iJF with VCC (Hillphoenix SMD-H)[161]dor
HTPG EcoNet enabled unit coolers[162]T003
LAE AT1-5/AT2-5[166]DO
Pego 202BASE electronic board[167]Ed
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]do
Taylor R280 fry dispenser[158]Temperature flashingThe cabinet door is ajar; after 15 minutes the compressor stops until it is closed. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon door flashingDoor has been open longer than parameter A12. (The manual does not give the colour.)
Staff BTX/BFX automatic batch freezers (BTX150, BFX150, BFX200, BFX201, BFX400, BFX600, BFX1000, BFX1500)[193]Continuous beepThe lid of the freezing cylinder is open.
Carel MPXone[21]Display reading flashing (door open too long)Door has been open longer than parameter Add: control restarts, light stays on, buzzer and alarm relay are activated. (The manual does not give the colour.)

The door contact has signalled an open door for longer than the set time.

Check: Close the door and check the door contact, its cable and the door alarm setting.

Condenser temperature too high

ControllerCode
Danfoss ERC 21X[1]A61
Danfoss ERC 21X[1]A80
Danfoss Optyma Plus[4]A80
Zanotti GM/GS[10]AH3
Copeland EazyCool ZX (XCM25D)[5]E46
Carel ir33[11]cht
Carel ir33[11]CHt
Dixell XR60CX[12]HA2
Eliwell ID 974[13]COH
Carel ir33+ VCC[20]cht
Carel ir33+ VCC[20]CHt
Carel SmartCella / SmartCella 3PH[24]cht
Carel SmartCella / SmartCella 3PH[24]CHt
Copeland Large ZX 22–30 HP[29]E46
Danfoss AK-CC55 Water Loop[35]AA4
Danfoss AK-PC 781A[37]Air flow reduced cond. A
Danfoss EKC 202A/B/C[2]A61
Dixell XR35CX[52]HA2
Dixell XR70CX[54]HA2
Dixell XW60K/XW60L[55]HA2
Dixell XWi70K[56]HA2
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]HIGH RETURN
NIBE F1255 ground source heat pump[78]162
NIBE F1255 ground source heat pump[78]163
Secop SLV controller 105N46xx[81]A37
RDM DMTouch / miniDM[91]Cond N TD Alarm
Evco EV3203[107]COH
Evco EV3203[107]CSd
Evco EVK214[109]CSd
Evco EV3 HP / EVD HP (heat pump)[110]AHtr
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AHtr
Thermia Atella / Robust[114]HIGH RETURN
Full Gauge TC-900E POWER / TC-900E 2HP[117]AC1
Full Gauge TC-900E POWER / TC-900E 2HP[117]AC2
Full Gauge TC-900E Log[118]AtC1
Full Gauge TC-900E Log[118]AtC2
RDM Mercury AC and roof top unit controllers[130]Cond. Out Temp. OT Alarm
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 0A
ActronAir Nexus Touch Controller WTC-01[139]PC0A
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Con
Danfoss EETa (True cabinets, LED blink codes)[143]1+3 flashes
Dixell XR/XW (True cabinets)[145]HA2
Taylor Icetro ISI-161TH/ISI-161TI[154]Er13
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er13
Carel iJF with VCC (Hillphoenix SMD-H)[161]CHt
Carel iJF with VCC (Hillphoenix SMD-H)[161]cht
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]HC

The condenser sensor measures too high a temperature. With the block alarm (ERC 21X: A80) the compressor stops and the alarm must be reset manually.

Check: Clean the condenser and check the fan and the airflow. Reset only when the cause has been fixed.

Condensing or discharge pressure too high

ControllerCode
Carel EVD evolution / EVD evolution twin[16]HiTcond
Carel Heos[18]HP
Carel pRack pR300[22]ALB04
Carel pRack pR300[22]ALB21
Carel pRack pR300[22]ALW01
Carel pRack pR300T (transcritical CO2)[23]ALB21
Carel µRack[25]A14
Carel µRack[25]A27
Carel µRack[25]A28
Copeland EazyCool ZX (XCM25D)[5]E45
Danfoss AK-PC 781A[37]High pressure Pc
Danfoss AK-PC 782A/782B[38]High pressure Pc
Danfoss EKE 1A/1B/1C/1D[43]A989
Danfoss Optyma iCO2[46]A17
Dixell XC645D[48]F-HA
Carel µChiller[60]A26
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 2
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 2
Daikin RA / SkyAir / VRV (malfunction codes)[75]F6
LG Multi V 5 VRF outdoor units[77]CH34
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]High Discharge
Hussmann transcritical CO2 rack (rack controller alarms)[87]High Discharge Pressure
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]DISCHARGE PRESSURE HIGH
Temperzone UC8 unit controller[100]HP
Temperzone UC7 unit controller[101]HP
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]5 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U1
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Ud
Goodman DX20VC inverter condensing unit[105]E13
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]High Pressure Alarm
Hitachi multi-split heat pump[113]46
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P20
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P20
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A27
RDM Intuitive / Mercury pack and condenser controllers[131]HP
RDM Intuitive / Mercury pack and condenser controllers[131]hiPr
RDM Intuitive / Mercury pack and condenser controllers[131]triP
RDM Intuitive Superpack / Transcritical Superpack[132]HP
RDM Intuitive Superpack / Transcritical Superpack[132]triP
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]69
Temperzone UC6 unit controller[135]4
ActronAir Advance / VCC / Genesis 13–17 kW[136]E44
ActronAir Aires and Advance 19–25 kW[137]E44
ActronAir Nexus Touch Controller WTC-01[139]PH90
True Ice TI/TCIM ice machines[147]E6
True Ice TI/TCIM ice machines[147]E20
Taylor Icetro ISI-161TH/ISI-161TI[154]Er08
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er08
Copeland (CPC) E2 RX/BX/CX controller[163]High Discharge Limit Exceeded
Copeland (CPC) E2 RX/BX/CX controller[163]Discharge Trip
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Discharge Pressure Trip
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red dark / yellow dark / green litHigh pressure switch open.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 6 flashesU1/Ud high pressure (63H) or overheating protection (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
IVT AirX air-to-water heat pump[175]5299High pressure caused by too little heating-water flow (air in the system, clogged particle filter or closed radiator thermostats).
IVT AirX air-to-water heat pump[175]5292Dirty or blocked outdoor air coil or a stopped fan, detected on high pressure transmitter JR1.
IVT AirX air-to-water heat pump[175]5298High pressure warning on JR1 caused by too little heating-water flow.
IVT AirSplit 200/300 split air-to-water heat pump[176]5292Dirty or blocked outdoor air coil or a stopped fan, detected on high pressure transmitter JR1.
IVT AirSplit 200/300 split air-to-water heat pump[176]5298High pressure warning on JR1 caused by too little heating-water flow.
IVT AirSplit 200/300 split air-to-water heat pump[176]5299High pressure alarm on JR1 caused by too little heating-water flow.
IVT AirSplit 200/300 split air-to-water heat pump[176]5640Condensing temperature above 65 °C, outdoor unit code 61 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5641Condensing temperature above 65 °C, outdoor unit code 61 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5298High pressure warning on JR1 caused by poor heating-water circulation.
IVT Geo 500/600 series ground source heat pump[177]5299High pressure alarm on JR1 caused by poor heating-water circulation.
IVT Geo 312/412 ground source heat pump[178]5298High pressure warning on JR1 caused by poor heating-water circulation.
IVT Geo 312/412 ground source heat pump[178]5299High pressure alarm on JR1 caused by poor heating-water circulation.
IVT Vent 202/302/402 exhaust air heat pump[179]5292Dirty or blocked outdoor air coil or a stopped fan, detected on high pressure transmitter JR1.
IVT Vent 202/302/402 exhaust air heat pump[179]5298High pressure warning on JR1 caused by too little heating-water flow.
IVT Vent 202/302/402 exhaust air heat pump[179]5299High pressure alarm on JR1 caused by too little heating-water flow.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 7 + Timer 3High pressure protection in cooling (code 24): check the outdoor fan, blocked condenser air, closed valves and overcharge.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 7 + Timer 3Abnormal pressure rise in cooling (14 on these models).
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]14Abnormal pressure rise in cooling on multi-zone RML models; the older UK guide lists an outdoor EEPROM fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]24High pressure protection in cooling: outdoor fan, blocked condenser air, closed valve or overcharge.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]EE:00High pressure problem (listed only in the unknown-publisher list).
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 6High pressure protection.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 8 + LED 2 steadyHigh pressure trip.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]A4High pressure abnormal (E.A4.1 sensor, E.A4.2 pressure switch): 3 high pressure stops within 60 min.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.A4.1High pressure abnormal: P2 stop (4.00 MPa or more from the sensor) 3 times within 60 min. Cooling: liquid-side service valve, outdoor fan, coil, ambient and recirculation, EEV1 and strainer, SV2, sensor, overcharge. Heating: gas-side valve, indoor EEVs and strainers.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]P2Stopped by high pressure protection: sensor 4.00 MPa or more (or pressure switch open at 4.2 MPa); restarts after 5 min below 3.50 MPa (switch: below 3.2 MPa). Three times in 60 min gives E.A4.1/E.A4.2.
Störk-Tronic ST121 / ST501 / ST551[93]ST551 LED2 on (default)With factory settings LED2 on the ST551 shows a high-pressure alarm. (The manual does not give the colour.)

The condensing (or gas cooler) pressure measured by the transmitter is above the alarm limit.

Check: Check condenser fans, a dirty condenser, recirculating air, overcharge and non-condensables; compare the transmitter with a gauge.

CO2 gas cooler pressure or temperature

ControllerCode
Carel pRack pR300T (transcritical CO2)[23]ALB03
Carel pRack pR300T (transcritical CO2)[23]ALB04
Danfoss EKC 326A[42]A82
Danfoss EKC 326A[42]A83
Danfoss EKC 326A[42]A94
RDM Intuitive Superpack / Transcritical Superpack[132]gOt
RDM Intuitive Superpack / Transcritical Superpack[132]gHPS
RDM Intuitive Superpack / Transcritical Superpack[132]gLPS
RDM Intuitive Superpack / Transcritical Superpack[132]gbHP

The gas cooler outlet pressure or temperature in a transcritical CO2 system is outside its limits.

Check: Check gas cooler fans and cleanliness, the high pressure valve and its control, and the outdoor temperature.

Receiver pressure or level

ControllerCode
Carel pRack pR300T (transcritical CO2)[23]ALT18
Danfoss AK-PC 781A[37]Recv. High pressure alarm
Danfoss AK-PC 781A[37]Recv. Low pressure alarm
Danfoss AK-PC 782A/782B[38]Recv. High pressure alarm
Danfoss AK-PC 782A/782B[38]Recv. Low pressure alarm
Danfoss AK-PC 782A/782B[38]Rec. High liquid level alarm
Danfoss EKC 326A[42]A84
Danfoss EKC 326A[42]A95
Danfoss Optyma iCO2[46]A85
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]Low Liquid Level
Hussmann transcritical CO2 rack (rack controller alarms)[87]Low Liquid Level
Hussmann transcritical CO2 rack (rack controller alarms)[87]High Flash Tank Pressure
Hussmann transcritical CO2 rack (rack controller alarms)[87]Low Flash Tank Pressure
Hussmann pumped liquid CO2 secondary system (E2 rack controller alarms)[88]LOW RECEIVER LIQUID LEVEL SHUT DOWN
Hussmann pumped liquid CO2 secondary system (E2 rack controller alarms)[88]HIGH CO2 RECEIVER PRESSURE
Hussmann pumped liquid CO2 secondary system (E2 rack controller alarms)[88]LOW CO2 RECEIVER PRESSURE
RDM Intuitive Superpack / Transcritical Superpack[132]rcHP
RDM Intuitive Superpack / Transcritical Superpack[132]rcLP
RDM Intuitive Superpack / Transcritical Superpack[132]rHIL
RDM Intuitive Superpack / Transcritical Superpack[132]rLOL

The receiver (flash tank) pressure or liquid level is too high or too low.

Check: Check the flash gas (bypass) valve and its control, the high pressure valve and the charge; at standstill check the auxiliary cooling.

High pressure or bypass valve fault (HPV/RPRV)

ControllerCode
Carel pRack pR300T (transcritical CO2)[23]ALT07
Carel pRack pR300T (transcritical CO2)[23]ALT08

The high pressure valve or the receiver bypass (flash gas) valve of a CO2 system does not control or is faulty.

Check: Check the valve coil, cable and driver, the signal from the controller and that the valve moves; compare with the pressure readings.

Four-way (reversing) valve fault

ControllerCode
Daikin RA / SkyAir / VRV (malfunction codes)[75]EA
LG Multi V 5 VRF outdoor units[77]CH151
Temperzone UC8 unit controller[100]F35
Temperzone UC7 unit controller[101]F35
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]PL
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P19
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P19
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.590
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 13 flashesPL refrigerant circuit abnormal (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
IVT AirX air-to-water heat pump[175]5296Four-way valve fault; cooling mode is not possible.
IVT AirX air-to-water heat pump[175]5297Four-way valve fault; heating mode is not possible.
IVT AirSplit 200/300 split air-to-water heat pump[176]5296Four-way valve fault; cooling mode is not possible.
IVT AirSplit 200/300 split air-to-water heat pump[176]5297Four-way valve fault; heating mode is not possible.
IVT Vent 202/302/402 exhaust air heat pump[179]5296Four-way valve fault; cooling mode is not possible.
IVT Vent 202/302/402 exhaust air heat pump[179]5297Four-way valve fault; heating mode is not possible.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 7 + Timer 4Four-way valve abnormal: the unit does not get the expected change between heating and cooling (code 2C).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 20 flashesFour-way valve fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]2CFour-way valve abnormal.

The unit sees that the four-way valve has not switched as commanded, or that the pressure difference between the high and low side stays too small, so the valve is probably stuck halfway, leaking internally or not powered.

Check: Check the coil voltage and coil resistance and the plug on the pilot valve. Compare discharge and suction pressures and feel the temperatures of the four pipes on the valve: a hot suction pipe or two equally warm pipes point to a valve stuck in the middle or leaking across. Try switching mode a few times with a good pressure difference; if it does not move, replace the valve.

Condenser temperature too low

ControllerCode
Dixell XR60CX[12]LA2
Carel pRack pR300[22]ALB03
Carel µRack[25]A13
Dixell XC645D[48]F-LA
Dixell XR35CX[52]LA2
Dixell XR70CX[54]LA2
Dixell XW60K/XW60L[55]LA2
Dixell XWi70K[56]LA2
Temperzone UC8 unit controller[100]F43
RDM Mercury AC and roof top unit controllers[130]Cond. Out Temp. UT Alarm

The condenser sensor has measured a temperature below the set low limit for longer than the alarm delay; depending on settings the compressor may be stopped.

Check: Check the condenser sensor position and reading, the condenser fan control and the outdoor temperature, and whether head pressure control is needed in cold weather.

Suction pressure too low

ControllerCode
Carel EVD evolution / EVD evolution twin[16]Low suction temperature
Carel EVD ice / EVD mini[17]E4
Carel Heos[18]LSA
Carel Heos[18]LP
Carel MPXone[21]LSA
Carel pRack pR300[22]ALB16
Carel pRack pR300T (transcritical CO2)[23]ALB16
Carel µRack[25]A15
Copeland EXD-SH1/2[26]AFE
Copeland EXD-SH1/2[26]LOP
Copeland EazyCool ZX (XCM25D)[5]E43
Sanhua SEC60x[31]LoP
Sanhua SEC60x[31]FrE
Danfoss AK-PC 781A[37]Low pressure P0
Danfoss AK-PC 782A/782B[38]Low pressure P0
Danfoss AK-PC 782A/782B[38]Low pressure Psuc-MT
Danfoss Optyma Plus[4]A2
Danfoss Optyma iCO2[46]A2
Dixell XC645D[48]E01L
Dixell XC645D[48]C1-LA
Dixell XEV12D[49]LPL
Carel µChiller[60]A27
LG Multi V 5 VRF outdoor units[77]CH35
Hussmann transcritical CO2 rack (rack controller alarms)[87]Low Suction Pressure
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]SUCTION PRESSURE LOW
Temperzone UC8 unit controller[100]LP
Temperzone UC7 unit controller[101]LP
Mitsubishi Electric City Multi (M-NET error codes)[102]1505
Mitsubishi Electric City Multi (M-NET error codes)[102]1605
Goodman DX20VC inverter condensing unit[105]E15
Hitachi multi-split heat pump[113]44
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]H06
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]H06
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A06
RDM Intuitive / Mercury pack and condenser controllers[131]LP
RDM Intuitive / Mercury pack and condenser controllers[131]LoPr
RDM Intuitive / Mercury pack and condenser controllers[131]Sd
RDM Intuitive / Mercury pack and condenser controllers[131]LoSh
RDM Intuitive Superpack / Transcritical Superpack[132]LP
RDM Intuitive Superpack / Transcritical Superpack[132]Sd
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]68
Temperzone UC6 unit controller[135]3
ActronAir Advance / VCC / Genesis 13–17 kW[136]E42
ActronAir Aires and Advance 19–25 kW[137]E42
True Ice TI/TCIM ice machines[147]E32
True Ice TI/TCIM ice machines[147]E11
True Ice TI/TCIM ice machines[147]E13
Copeland (CPC) E2 RX/BX/CX controller[163]Low Suction Limit Exceeded
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Suction Pressure Trip
alpha innotec WWB 190 DHW heat pump[169]E7
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red dark / yellow blink / green darkLow pressure switch open.
IVT AirX air-to-water heat pump[175]5515Low evaporating pressure on transmitter JR0; first check that the outdoor fan and coil are not blocked.
IVT AirX air-to-water heat pump[175]5514Evaporating pressure JR0 too low: low outdoor temperature or too little air flow; clean the outdoor coil.
IVT AirSplit 200/300 split air-to-water heat pump[176]5514Evaporating pressure JR0 too low: low outdoor temperature or too little air flow; clean the outdoor coil.
IVT AirSplit 200/300 split air-to-water heat pump[176]5515Evaporating pressure JR0 too low; make sure there is enough air flow through the outdoor coil.
IVT AirSplit 200/300 split air-to-water heat pump[176]5666Evaporating pressure too low, LG code 35 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5667Evaporating pressure too low, LG code 35 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5514Low evaporating pressure on JR0; IVT points first to heating-side flow (thermostats, filter, air), check the brine side too.
IVT Geo 500/600 series ground source heat pump[177]5515Low evaporating pressure on JR0; IVT points first to heating-side flow (thermostats, filter, air), check the brine side too.
IVT Geo 312/412 ground source heat pump[178]5514Low evaporating pressure on JR0; IVT points first to heating-side flow (thermostats, filter, air), check the brine side too.
IVT Geo 312/412 ground source heat pump[178]5515Low evaporating pressure on JR0; IVT points first to heating-side flow (thermostats, filter, air), check the brine side too.
IVT Vent 202/302/402 exhaust air heat pump[179]5514Evaporating pressure JR0 too low; clean the air filter and check the air flow (info).
IVT Vent 202/302/402 exhaust air heat pump[179]5515Evaporating pressure JR0 too low; clean the air filter and check the air flow (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5666Evaporating pressure too low; check the air filter and the air flow (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5667Evaporating pressure too low; check the air filter and the air flow (alarm).
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]A5Low pressure abnormal (E.A5.1): 5 low pressure stops within 3 h.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.A5.1Low pressure abnormal: P3 stop (0.05 MPa or less, or 0.10 MPa or less for 10 min) 5 times within 3 h; the unit locks out. Cooling: gas-side valve, indoor EEVs and strainers, SV2, sensor, leak. Heating: liquid-side valve, too low ambient, outdoor fan and coil, EEV1 and strainer.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]P3Stopped by low pressure protection: 0.05 MPa or less, or 0.10 MPa or less for 10 min; restarts after 3 min above 0.17 MPa. Five times in 3 h gives E.A5.1.
Störk-Tronic ST121 / ST501 / ST551[93]ST551 LED3 on (default)With factory settings LED3 on the ST551 shows a low-pressure alarm. (The manual does not give the colour.)

The suction pressure or evaporating temperature measured by the transmitter is below the alarm limit.

Check: Troubleshoot as a low pressure trip: air flow, ice, refrigerant charge, restrictions and the expansion valve; compare the transmitter with a gauge.

Suction pressure too high

ControllerCode
Carel pRack pR300[22]ALB15
Carel pRack pR300T (transcritical CO2)[23]ALB15
Carel µRack[25]A16
Danfoss AK-PC 781A[37]High pressure P0
Danfoss AK-PC 782A/782B[38]High pressure P0
Danfoss AK-PC 782A/782B[38]High pressure Psuc-MT
Dixell XC645D[48]C1-HA
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]High Suction
Hussmann transcritical CO2 rack (rack controller alarms)[87]High Suction Pressure
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]SUCTION PRESSURE HIGH
Temperzone UC8 unit controller[100]HI-SL
Temperzone UC7 unit controller[101]HI-SL
Temperzone UC8 unit controller[100]F42
Copeland (CPC) E2 RX/BX/CX controller[163]High Suction Limit Exceeded

The suction pressure measured by the transmitter is above the alarm limit, for example from high load or too little compressor capacity.

Check: Check the load, the compressor capacity steps and whether the compressors pump; compare the transmitter with a gauge.

Pressure switch has tripped

ControllerCode
Danfoss Optyma Plus[4]A17
Copeland EazyCool ZX (XCM25D)[5]E40
Copeland EazyCool ZX (XCM25D)[5]E41
Carel μC2SE[8]HP1
Carel μC2SE[8]LP1
Dixell XW270L/XW271L[9]PAL
Zanotti GM/GS[10]HPA
Zanotti GM/GS[10]LPA
Zanotti GM/GS[10]PA
Carel ir33[11]LP
Dixell XR60CX[12]CA
Eliwell ID 974[13]nPA
Eliwell ID 974[13]PAL
Carpigiani AES PSP[15]AL11
Carel ir33+ VCC[20]LP
Carel pRack pR300[22]ALB01
Carel pRack pR300[22]ALB02
Carel pRack pR300T (transcritical CO2)[23]ALB01
Carel pRack pR300T (transcritical CO2)[23]ALB02
Carel pRack pR300T (transcritical CO2)[23]ALC92
Carel SmartCella / SmartCella 3PH[24]LP
Carel µRack[25]A10
Carel µRack[25]A12
Copeland EazyCool ZX (XCM25D)[5]L40
Copeland Large ZX 22–30 HP[29]E40
Copeland Large ZX 22–30 HP[29]L40
Copeland Large ZX 22–30 HP[29]E41
Heatcraft Beacon II[30]E7
Heatcraft Beacon II[30]SHTDN
Danfoss AK-PC 781A[37]Comp. x disch. Press. Cut out
Danfoss AK-PC 782A/782B[38]Comp. x disch. Press. Cut out
Danfoss Optyma iCO2[46]A97
Dixell XC645D[48]E0L1
Dixell XC645D[48]E0H
Dixell XM669K/XM679K[50]PAL
Dixell XR35CX[52]CA
Dixell XR70CX[54]CA
Dixell XW60K/XW60L[55]CA
Dixell XWi70K[56]CA
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]34
Carel µC2SE for process chiller[59]HP1
Carel µC2SE for process chiller[59]LP1
Carel µChiller[60]A25
Carel µChiller[60]A29
Copeland CoreSense Diagnostics (scroll AC)[64]LED yellow 2
Copeland CoreSense Diagnostics (scroll AC)[64]LED red 2
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 3
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 3
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED yellow 2
Danfoss CDS303/CDS803[69]A68
Daikin RA / SkyAir / VRV (malfunction codes)[75]E3
Daikin RA / SkyAir / VRV (malfunction codes)[75]E4
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]HIGH PRESSURE ERROR
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]LOW PRESSURE ERROR
LG Multi V 5 VRF outdoor units[77]CH24
NIBE F1255 ground source heat pump[78]50
NIBE F1255 ground source heat pump[78]51
NIBE F1255 ground source heat pump[78]58
Störk-Tronic ST121 / ST501 / ST551[93]E6
Störk-Tronic ST121 / ST501 / ST551[93]E7
Goodman DX20VC inverter condensing unit[105]E24
Evco EV3 HP / EVD HP (heat pump)[110]AHP1
Evco EV3 HP / EVD HP (heat pump)[110]ALP1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AHP1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]ALP1
Evco EV3 MVC / EVD MVC (air handling)[112]AL07
Evco EV3 MVC / EVD MVC (air handling)[112]AL08
Hitachi multi-split heat pump[113]02
Thermia Atella / Robust[114]LOW PRESSURE ERROR
Thermia Atella / Robust[114]HIGH PRESSURE ERROR
Copeland Electronic Unit Controller[116]HP
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P04
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P04
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]21
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A23
RDM Mercury AC and roof top unit controllers[130]HP/LP Fault
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]90
ActronAir Advance / VCC / Genesis 13–17 kW[136]E09
ActronAir Advance / VCC / Genesis 13–17 kW[136]E11
ActronAir Aires and Advance 19–25 kW[137]E9
ActronAir Aires and Advance 19–25 kW[137]E11
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 03
ActronAir Nexus Touch Controller WTC-01[139]PC03
Dixell XR/XW (True cabinets)[145]PAL
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]CHK REFRIG SYS PSI
Taylor C392/C393/C394 frozen beverage freezers[150]Compressor Hi/Lo Pres Cut out
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]COMPRESSOR HPCO
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HPCO H/C
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HO
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]HPCO COMPRESSOR
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]COMPRESSOR HPCO
Taylor R200 fry dispenser[157]Error 6
Taylor R280 fry dispenser[158]Err 6
Carel iJF with VCC (Hillphoenix SMD-H)[161]LP
alpha innotec BWP 190S/260S DHW heat pump[168]Er6
alpha innotec WWB 190 DHW heat pump[169]E6
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.302
Danfoss Optyma iCO2[46]Display S34Safe stop: a pressure or temperature safety switch on DI1 has opened.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D801 yellow (3 s on / 0.5 s off)Current error: High pressure switch error (21).
Dixell XC645D[48]LED LP steadyLow-pressure switch alarm. (The manual does not give the colour.)
Dixell XC645D[48]LED HP steadyHigh-pressure switch alarm. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault G-onHigh-pressure switch open (red off, yellow off, green on).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault Y-blinkLow-pressure switch open (red off, yellow blink, green off).
IVT AirX air-to-water heat pump[175]5507High pressure switch MR1 warning: heating-water flow too low, e.g. a closed or partly closed heating system.
IVT AirX air-to-water heat pump[175]5508High pressure switch MR1 tripped: heating-water flow too low, e.g. a closed or partly closed heating system.
IVT AirSplit 200/300 split air-to-water heat pump[176]5507High pressure switch MR1 warning: heating-water flow too low, e.g. a closed or partly closed heating system.
IVT AirSplit 200/300 split air-to-water heat pump[176]5508High pressure switch MR1 tripped: heating-water flow too low.
IVT Geo 500/600 series ground source heat pump[177]5507High pressure switch MR1 tripped from a flow problem on the heating side (filter, closed thermostats, air).
IVT Geo 500/600 series ground source heat pump[177]5508High pressure switch MR1 tripped from a flow problem on the heating side (filter, closed thermostats, air).
IVT Geo 312/412 ground source heat pump[178]5507High pressure switch MR1 tripped from a flow problem on the heating side (filter, closed thermostats, air).
IVT Geo 312/412 ground source heat pump[178]5508High pressure switch MR1 tripped from a flow problem on the heating side (filter, closed thermostats, air).
IVT Vent 202/302/402 exhaust air heat pump[179]5507High pressure switch MR1 warning: heating-water flow too low, e.g. a closed or partly closed heating system.
IVT Vent 202/302/402 exhaust air heat pump[179]5508High pressure switch MR1 tripped: heating-water flow too low.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 7 + Timer 5Pressure switch open (code 16); clears by itself when the pressure is normal again: check condenser air flow, outdoor fan and charge.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 7 + Timer 6High pressure switch open (16).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 9 flashesHigh pressure switch 1 open.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 10 flashesHigh pressure switch 2 open.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]16Pressure switch open.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 3, test button: Red 2 + Green blinkingPressure switch open.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 8Pressure switch open.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 9Pressure switch open.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 8 flashesPressure switch open (as models 9–30).
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 9 flashesPressure switch A open.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 10 flashesPressure switch B open.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 6 short (F)High or low pressure switch has tripped.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C1 45High pressure switch PS(H)1 on circuit 1 has opened (4.15 MPa off, 3.2 MPa on, automatic reset): check the discharge pressure, a dirty or blocked condenser, the condenser fan and the air inlet temperature.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C2 45High pressure switch PS(H)2 on circuit 2 has opened (4.15 MPa off, 3.2 MPa on, automatic reset): check the discharge pressure, a dirty or blocked condenser, the condenser fan and the air inlet temperature.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C1 47Low pressure switch PS(L)1 on circuit 1 has opened (0.40 MPa off, 0.70 MPa on, automatic reset): check the suction pressure, refrigerant charge, air filter and evaporator air flow.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C2 47Low pressure switch PS(L)2 on circuit 2 has opened (0.40 MPa off, 0.70 MPa on, automatic reset): check the suction pressure, refrigerant charge, air filter and evaporator air flow.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.86.4High pressure switch found open at power-on. Check the switch connector and wiring and that the switch closes (it resets at about 3.2 MPa); then the main PCB.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.A4.2High pressure protection 1: the high pressure switch (opens at 4.2 MPa) tripped 3 times within 60 min. Same checks as E.A4.1 plus the check valve at the oil separator outlet and the switch itself.
Thermia Atella / Robust[114]Symbol squareThe operating pressure switch has tripped or the hot gas temperature has reached its maximum. (The manual does not give the colour.)

A high or low pressure switch has opened. After several trips in a short time many controllers lock the compressor until the alarm is reset manually.

Check: Measure the pressure and troubleshoot the high or low pressure. Reset only when the cause has been found.

Pump-down fault

ControllerCode
Carel ir33[11]Pd
Carel ir33[11]AtS
Carel ir33+ VCC[20]Pd
Carel ir33+ VCC[20]AtS
Carel SmartCella / SmartCella 3PH[24]Pd
Carel SmartCella / SmartCella 3PH[24]AtS
Danfoss AK-RC 251[47]Pd
Danfoss AK-RC 251[47]LP
Carel iJF with VCC (Hillphoenix SMD-H)[161]Pd
Carel iJF with VCC (Hillphoenix SMD-H)[161]AtS

The compressor did not reach the low-pressure switch within the maximum pump-down time, or it had to restart because the suction pressure rose again while the liquid line valve was closed.

Check: Check that the solenoid valve on the liquid line closes tightly, that the low-pressure switch is set correctly and that the compressor pumps; repeated restarts usually point to a leaking valve.

Discharge temperature too high

ControllerCode
Danfoss Optyma Plus[4]A96
Copeland EazyCool ZX (XCM25D)[5]E44
Danfoss VLT FC 103[14]W19
Carel Heos[18]Hid
Copeland Stream condensing units (Next Gen CoreSense)[27]3 flashes
Copeland ZSI scroll condensing units[28]LED4
Copeland EazyCool ZX (XCM25D)[5]L44
Copeland Large ZX 22–30 HP[29]E44
Copeland Large ZX 22–30 HP[29]L44
Danfoss AK-PC 781A[37]Comp. x disch. Temp cut out
Danfoss AK-PC 781A[37]High disch. temp. SdA
Danfoss AK-PC 782A/782B[38]Comp. x disch. Temp cut out
Danfoss AK-PC 782A/782B[38]High disch. temp. SdA
Danfoss Optyma Plus Module B Plus (P02)[45]Y1-R1
Danfoss Optyma Plus Module B Plus (P02)[45]Y1-R2
Danfoss Optyma iCO2[46]A96
Dixell XC645D[48]dtL
Carel µChiller[60]A46
Copeland Digital Compressor Controller[61]2 flashes
Copeland PerformanceAlert diagnostic module[62]1 flash
Copeland CoreSense Protection (Discus)[63]LED yellow 3
Copeland CoreSense Protection (Discus)[63]LED red 3
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 4
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED yellow 1
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED red 1
Daikin RA / SkyAir / VRV (malfunction codes)[75]F3
LG Multi V 5 VRF outdoor units[77]CH32
NIBE F1255 ground source heat pump[78]55
NIBE F1255 ground source heat pump[78]155
Kriwan INT69 F Diagnose[94]LED red 3 / orange 1
Kriwan INT69 PYF Diagnose[95]LED red 3 / orange 1
Kriwan INT69 PYF Diagnose[95]LED red 3 / orange 2
Kriwan INT69 YF Diagnose[98]LED red 3 / orange 1
Kriwan INT69 YF Diagnose[98]LED red 3 / orange 2
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]DISCHARGE TEMPERATURE HIGH
Temperzone UC8 unit controller[100]HI-t
Temperzone UC7 unit controller[101]HI-t
Mitsubishi Electric City Multi (M-NET error codes)[102]1504
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]3 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U2
Goodman DX20VC inverter condensing unit[105]E22
Evco EV3 HP / EVD HP (heat pump)[110]AdS1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AdS1
Hitachi multi-split heat pump[113]08
Hitachi multi-split heat pump[113]23
Copeland Electronic Unit Controller[116]DLT
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P03
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P03
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]1E
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A25
RDM Intuitive / Mercury pack and condenser controllers[131]di Ot
RDM Intuitive Superpack / Transcritical Superpack[132]dtFt
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]78
Temperzone UC6 unit controller[135]9
ActronAir Advance / VCC / Genesis 13–17 kW[136]E06
ActronAir Aires and Advance 19–25 kW[137]E6
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 02
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 06
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Discharge Temp Trip
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.286
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.823
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.303
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P82
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]E45
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 3 + timer flashingCompressor top temperature, IPM temperature or high pressure protection (PC 02). (The manual does not give the colour.)
Kriwan INT69 F Diagnose[94]LED green 3 / orange 1Warning: temperature input 1 (e.g. discharge) is above its permitted value.
Kriwan INT69 YF Diagnose[98]LED green 3 / orange 1Warning: temperature input 1 is above its permitted value.
Kriwan INT69 YF Diagnose[98]LED green 3 / orange 2Warning: temperature input 2 is above its permitted value.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D801+D803 yellow (3 s on / 0.5 s off)Current error: Discharge temperature error (1E).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 5 flashesU2 high discharge temperature / 49C tripped / low refrigerant (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
IVT AirX air-to-water heat pump[175]5310Discharge (hot gas) temperature too high (warning).
IVT AirX air-to-water heat pump[175]5311Discharge (hot gas) temperature too high (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5310Discharge (hot gas) temperature too high (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5311Discharge (hot gas) temperature too high (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5618Discharge (hot gas) temperature too high, LG code 32 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5619Discharge (hot gas) temperature too high, LG code 32 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5310Discharge (hot gas) temperature too high, often temporary (warning).
IVT Geo 500/600 series ground source heat pump[177]5311Discharge (hot gas) temperature too high (alarm).
IVT Geo 312/412 ground source heat pump[178]5310Discharge (hot gas) temperature too high, often temporary (warning).
IVT Geo 312/412 ground source heat pump[178]5311Discharge (hot gas) temperature too high (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5310Discharge (hot gas) temperature too high (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5311Discharge (hot gas) temperature too high (alarm).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 7 + Timer 2Discharge temperature protection (code 0F): look for closed service valves, low charge or leaks, and restrictions in the line set.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 7 + Timer 6Compressor body above about 108 °C (code 2b): check service valves, EEV, charge, compressor thermistor, outdoor fan and a dirty outdoor coil.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 7 + Timer 2Discharge temperature too high (0F).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 18 flashesDischarge temperature too high.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 19 flashesCompressor temperature too high.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]0FDischarge temperature too high: closed service valves, gas shortage, leak or restriction.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]2bCompressor temperature too high (about 108 °C on the 2019 models).
Fujitsu wired remote controller, older models (E-codes with unit address)[184]EF:00Discharge temperature too high, usually gas shortage or contamination in the pipework.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 7Discharge or compressor temperature too high.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 7 + LED 2 steadyDischarge temperature too high.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 9 + LED 2 steadyCompressor temperature too high.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 7 short (F)Discharge temperature too high.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]A1Discharge temperature abnormal (E.A1.1): discharge reached 115 °C twice within 40 min.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]A3Compressor temperature abnormal (E.A3.1): compressor body reached 110 °C twice within 40 min.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.A1.1Discharge temperature abnormal: P1 stop (115 °C or more) twice within 40 min; the unit locks out. Check the service valve (gas side in cooling, liquid side in heating), the EEVs and strainers, outdoor fan and coil, TH1 and the charge (leak). Reset by power cycle and error reset.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.A3.1Compressor temperature abnormal: P4 stop (compressor body 110 °C or more) twice within 40 min; the unit locks out. Same checks as E.A1.1, with TH10 instead of TH1.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]P1Stopped by discharge temperature protection: discharge 115 °C or more; restarts after 3 min once it is 80 °C or less. Twice within 40 min gives E.A1.1.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]P4Stopped by compressor temperature protection: compressor body 110 °C or more; restarts after 3 min with discharge 80 °C or less. Twice within 40 min gives E.A3.1.
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]Square symbol by the hot gas (delivery pipe) temperatureAppears when the discharge pipe temperature has reached the set DELIVERY PIPE limit. (The manual does not give the colour.)

The sensor on the discharge pipe measures a temperature above the limit, and the compressor is stopped for protection.

Check: Measure superheat, suction and high pressure and troubleshoot high discharge temperature.

Low superheat

ControllerCode
Carel EVD evolution / EVD evolution twin[16]LowSH
Carel EVD ice / EVD mini[17]E3
Carel Heos[18]LSh
Carel MPXone[21]LSH
Carel pRack pR300[22]ALW10
Carel pRack pR300[22]ALE02
Carel pRack pR300T (transcritical CO2)[23]ALT15
Copeland EXD-SH1/2[26]LSH
Copeland EazyCool ZX (XCM25D)[5]E50
Copeland Large ZX 22–30 HP[29]E50
Heatcraft Beacon II[30]E6
Heatcraft Beacon II[30]SUPLO
Sanhua SEC60x[31]LSH
Danfoss AK-PC 781A[37]Low superheat section A
Danfoss AK-PC 782A/782B[38]Low superheat section A
Danfoss EKE 1A/1B/1C/1D[43]A987
Danfoss EKE 100[44]A25
Dixell XC645D[48]PrSH
Dixell XC645D[48]ALSH
Dixell XEV12D[49]LSH
Dixell XM669K/XM679K[50]LSH
Carel µC2SE for process chiller[59]SH1
Carel µChiller[60]A35
Daikin RA / SkyAir / VRV (malfunction codes)[75]F4
LG Multi V 5 VRF outdoor units[77]CH150
Hussmann transcritical CO2 rack (rack controller alarms)[87]Superheat Alarm
Pego ECP200 EXPERT PULSE[89]LSH
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]SUCTION SUPERHEAT LOW
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]DISCHARGE SUPERHEAT LOW
Temperzone UC8 unit controller[100]Lo-dSH
Temperzone UC7 unit controller[101]Lo-dSH
Mitsubishi Electric City Multi (M-NET error codes)[102]1502
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]7 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U7
Goodman DX20VC inverter condensing unit[105]E21
Hitachi multi-split heat pump[113]07
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P13
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Superheat Low
RDM Intuitive Superpack / Transcritical Superpack[132]ShUt
Copeland (CPC) E2 RX/BX/CX controller[163]Low Pack Superheat
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D801+D802+D804 yellow (3 s on / 0.5 s off)Current error: PMV (expansion valve) error, superheat -8 K or less.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 10 flashesU7 low discharge superheat (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
IVT AirX air-to-water heat pump[175]5366Refrigerant superheat too low (warning).
IVT AirX air-to-water heat pump[175]5367Refrigerant superheat too low (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5366Refrigerant superheat too low (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5367Refrigerant superheat too low (alarm).
IVT Geo 500/600 series ground source heat pump[177]5366Low superheat; IVT links it to poor heating-side flow (thermostats, air, filter).
IVT Geo 500/600 series ground source heat pump[177]5367Low superheat; IVT links it to poor heating-side flow (thermostats, air, filter).
IVT Geo 312/412 ground source heat pump[178]5366Low superheat; IVT links it to poor heating-side flow (thermostats, air, filter).
IVT Geo 312/412 ground source heat pump[178]5367Low superheat; IVT links it to poor heating-side flow (thermostats, air, filter).
IVT Vent 202/302/402 exhaust air heat pump[179]5366Refrigerant superheat too low (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5367Refrigerant superheat too low (alarm).

Superheat at the evaporator outlet has been below the low limit for longer than the delay, so liquid may reach the compressor.

Check: Check the superheat with gauge and thermometer, the sensor position and insulation, and whether the valve closes; a valve that hangs open or a sensor reading too warm are common causes.

High superheat

ControllerCode
Carel Heos[18]HSh
Copeland EXD-SH1/2[26]HSH
Sanhua SEC60x[31]HSH
Danfoss AK-PC 781A[37]High superheat suction A
Danfoss AK-PC 782A/782B[38]High superheat suction A
Danfoss EKE 1A/1B/1C/1D[43]A988
Danfoss EKE 100[44]A24
Dixell XEV12D[49]HSH
Dixell XM669K/XM679K[50]HSH
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]SUCTION TEMPERATURE HIGH
Temperzone UC8 unit controller[100]Hi-dSH
Temperzone UC7 unit controller[101]HI-dSH
RDM Intuitive Superpack / Transcritical Superpack[132]ShOt
Temperzone UC8 unit controller[100]HI-SL
Temperzone UC7 unit controller[101]HI-SL
Temperzone UC7 unit controller[101]Hi-dSH
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D802+D804 yellow (3 s on / 0.5 s off)Current error: PMV (expansion valve) error, superheat 20 K or more.
IVT Geo 500/600 series ground source heat pump[177]5543Superheat above the optimum, usually temporary (warning).
IVT Geo 312/412 ground source heat pump[178]5543Superheat above the optimum, usually temporary (warning).

Superheat has been above the high limit for longer than the delay, so the evaporator is underfed.

Check: Check refrigerant charge, sight glass, filter drier and valve capacity, and that the valve opens as commanded.

Maximum operating pressure (MOP)

ControllerCode
Carel EVD evolution / EVD evolution twin[16]MOP
Carel EVD ice / EVD mini[17]E1
Carel Heos[18]MOP
Carel ir33+ VCC[20]Eht
Carel MPXone[21]MOP
Carel pRack pR300[22]ALE02
Sanhua SEC60x[31]MoP
Danfoss EKE 1A/1B/1C/1D[43]A991
Danfoss EKE 100[44]A22
Dixell XEV12D[49]MOP
Dixell XM669K/XM679K[50]MOP
Carel µC2SE for process chiller[59]nO1
Carel µChiller[60]A37
Pego ECP200 EXPERT PULSE[89]MOP
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]MOP Alarm
Dixell XEV12D[49]LED MOP alarm onSuction pressure is above the Maximum Operating Pressure threshold.
Copeland EXD-SH1/2[26]Superheat value blinkingThe superheat reading blinks while the controller is limiting in MOP mode (suction pressure above MOP). (The manual does not give the colour.)

The evaporating pressure or temperature is above the MOP limit, so the valve driver throttles to protect the compressor.

Check: Check the load (warm start-up, defrost return, open doors) and the MOP setting; a lasting alarm can point to a valve that does not close or too high a suction pressure.

Low operating pressure (LOP)

ControllerCode
Carel EVD evolution / EVD evolution twin[16]LOP
Carel EVD ice / EVD mini[17]E2
Carel Heos[18]LOP
Carel MPXone[21]LOP
Carel pRack pR300[22]ALE02
Danfoss EKE 1A/1B/1C/1D[43]A990
Danfoss EKE 100[44]A23
Dixell XEV12D[49]LOP
Dixell XM669K/XM679K[50]LOP
Carel µC2SE for process chiller[59]LO1
Carel µChiller[60]A36
Pego ECP200 EXPERT PULSE[89]LOP
Dixell XEV12D[49]LED low pressure alarm onSuction pressure has fallen to the LOP threshold.

The evaporating pressure or temperature is below the LOP limit, so the valve driver opens to avoid a low pressure trip or freezing.

Check: Check air flow and ice on the evaporator, refrigerant charge and the LOP setting.

Injection problem

ControllerCode
Danfoss AK-CC 550 / 550B[33]A10
Danfoss AK-CC 750[36]Injection problem
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Superheat problem

The controller cannot keep the superheat under control with the electronic expansion valve, for example because the valve is too small or too large, the refrigerant supply is poor or the evaporator sensors give misleading values.

Check: Check the liquid supply to the valve (sight glass, subcooling, filter drier), the valve size and orifice, and that the pressure transmitter and outlet sensor are mounted correctly and read plausible values.

Expansion valve out of capacity

ControllerCode
Danfoss EKE 1A/1B/1C/1D[43]A986
Danfoss EKE 100[44]A26

The expansion valve has stayed close to fully open for longer than the delay without reaching the superheat reference, so the evaporator is underfed.

Check: Look for flash gas in the liquid line (undercharge, too little subcooling), a blocked filter drier, too low condensing pressure, and check that the valve type set in the controller matches the valve and that it is large enough.

Flash gas at the expansion valve

ControllerCode
Danfoss AK-CC 550 / 550B[33]AD flashgas
Danfoss AK-CC 750[36]AD – Flash gas detect

The controller has seen signs for a long time that the liquid reaching the expansion valve contains gas, which cuts capacity and makes the superheat unstable.

Check: Check subcooling and the sight glass before the valve, refrigerant charge, a clogged filter drier or a long or rising liquid line, and the liquid line pressure drop.

Valve motor or valve driver fault

ControllerCode
Carel EVD evolution / EVD evolution twin[16]EEV motor error
Carel EVD evolution / EVD evolution twin[16]Driver B disconnected
Carel EVD ice / EVD mini[17]E5
Carel EVD ice / EVD mini[17]E8
Carel MPXone[21]bLo
Carel MPXone[21]Edc
Carel pRack pR300[22]ALE01
Carel pRack pR300[22]ALE05
Copeland EXD-SH1/2[26]1Π-
Copeland EXD-SH1/2[26]2Π-
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A43
Danfoss EKC 326A[42]A43
Danfoss EKE 1A/1B/1C/1D[43]E126
Danfoss EKE 100[44]A39
Danfoss EKE 100[44]A40
Danfoss EKE 100[44]A41
Carel µC2SE for process chiller[59]EU1
Carel µChiller[60]A38
Daikin RA / SkyAir / VRV (malfunction codes)[75]A9
Daikin RA / SkyAir / VRV (malfunction codes)[75]E9
Mitsubishi Electric City Multi (M-NET error codes)[102]1608
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]20
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A07
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Stepper Fault
RDM Intuitive Superpack / Transcritical Superpack[132]SCPU
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.582
Danfoss AK-PC 781A[37]Stepper module LED red flashingFault on the valve motor or its wiring.
Danfoss AK-PC 782A/782B[38]AK-XM 208C LED red flashFault on the stepper motor or its connection.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D803+D804 yellow (3 s on / 0.5 s off)Current error: PMV leakage error, unit A (20).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D803+D804 yellow (3 s on / 0.5 s off)Current error: PMV leakage error, unit B (20).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D801+D803+D804 yellow (3 s on / 0.5 s off)Current error: PMV leakage error, unit C (20).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D801+D803+D804 yellow (3 s on / 0.5 s off)Current error: PMV leakage error, unit D (20).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D802+D803+D804 yellow (3 s on / 0.5 s off)Current error: PMV leakage error, unit E (20).
Danfoss EKE 1A/1B/1C/1D[43]Valve LEDs red and green flashingValve-related alarm.
Danfoss EKE 100[44]Valve LED red/green alternatingOpen circuit on the valve stepper motor or valve driver overheating; check valve wiring.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]9AOutdoor expansion valve coil error, EEV1 or EEV2 (E.9A.1/E.9A.2).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.9A.1Outdoor expansion valve EEV1 coil open or short (CN116). Check the plug, the wires, the coil (46 ± 4 Ω per phase at 20 °C) and 12 V DC from the main PCB with the coil unplugged.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.9A.2Outdoor expansion valve EEV2 coil open or short (CN117). Same checks as E.9A.1.

The stepper or pulse valve, its coil, cable or the valve driver is faulty, offline or not calibrated.

Check: Measure the coil resistance and the cable, check the driver supply and communication, and let the driver re-home the valve.

Compressor motor protection

ControllerCode
Copeland EazyCool ZX (XCM25D)[5]E28
Carel μC2SE[8]tC1
Carpigiani AES PSP[15]AL01
Carpigiani AES PSP[15]AL02
Carel pRack pR300T (transcritical CO2)[23]ALC91
Copeland Stream condensing units (Next Gen CoreSense)[27]4 flashes
Copeland EazyCool ZX (XCM25D)[5]E23
Copeland EazyCool ZX (XCM25D)[5]L23
Copeland Large ZX 22–30 HP[29]E23
Copeland Large ZX 22–30 HP[29]L23
Copeland Large ZX 22–30 HP[29]E28
Danfoss AK-PC 781A[37]Comp. x over current cut out
Danfoss AK-PC 781A[37]Comp. x motor prot. cut out
Danfoss AK-PC 782A/782B[38]Comp. x motor prot. cut out
Carel µC2SE for process chiller[59]tP
Carel µC2SE for process chiller[59]tC1
Carel µChiller[60]A30
Copeland Digital Compressor Controller[61]3 flashes
Copeland PerformanceAlert diagnostic module[62]LED red
Copeland PerformanceAlert diagnostic module[62]5 flashes
Copeland CoreSense Protection (Discus)[63]LED yellow 2
Copeland CoreSense Diagnostics (scroll AC)[64]LED yellow 5
Copeland CoreSense Diagnostics (scroll AC)[64]LED red (steady)
Copeland CoreSense Diagnostics (scroll AC)[64]LED red 5
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 1
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red solid
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 5
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 5
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green 5
Daikin RA / SkyAir / VRV (malfunction codes)[75]E5
Daikin RA / SkyAir / VRV (malfunction codes)[75]E6
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]MOTOR P ERROR
Pego ECP200 EXPERT PULSE[89]Ec
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]Ec
Kriwan INT69 PYF Diagnose[95]LED red 6 / orange 1
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]COMPRESSOR MOTOR CURRENT HIGH
Temperzone UC8 unit controller[100]OL
Temperzone UC7 unit controller[101]OL
Mitsubishi Electric City Multi (M-NET error codes)[102]4108
Evco EV3 HP / EVD HP (heat pump)[110]AtC1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]APMP
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]At1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AtC1
Evco EV3 MVC / EVD MVC (air handling)[112]AL11
Thermia Atella / Robust[114]MOTOR P ERROR
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]H04
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]H04
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]1C
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A22
RDM Mercury AC and roof top unit controllers[130]Comp. Overload Fault
Taylor 736 soft serve freezer[153]THERMAL
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Motor Temp Trip
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Internal Line Break
Pego 202BASE electronic board[167]Ec
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800 yellow (3 s on / 0.5 s off)Current error: Compressor case thermostat error (check code 1C).
Carel µC2SE for process chiller[59]Icon alarm red flashingGeneral overload (tP): pumps, compressors and fans are stopped.
Carel SmartCella / SmartCella 3PH[24]LED COMPRESSOR yellow off with demand (3PH panel)No power at the compressor terminals; check motor protector QM1 if cooling is demanded.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C1 08The internal thermostat of compressor 1 has opened (factory value 130 °C off, 108 °C on, automatic reset): check the thermostat circuit, suction superheat, charge and supply voltage.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C2 08The internal thermostat of compressor 2 has opened (130 °C off, 108 °C on, automatic reset): check the thermostat circuit, suction superheat, charge and supply voltage.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C1 39Overcurrent on compressor motor 1, measured by current transformer CT1: measure the running current, the voltage and phase balance, and the high pressure.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C2 39Overcurrent on compressor motor 2, measured by current transformer CT2: measure the running current, the voltage and phase balance, and the high pressure.

The built-in thermal protector or the overcurrent protection in the compressor circuit has tripped.

Check: Let the motor cool down, measure voltage and current and find out why the protection tripped.

Beater motor overload or locked beater

ControllerCode
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]BEATER OVERLOAD
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]Beater Over Current
Taylor C392/C393/C394 frozen beverage freezers[150]Beater Overload
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BEATER OVERLOAD
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BEATER OVLD H/C
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BO
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BEATER OVERLOAD
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BEATER LOCKED
Taylor Icetro ISI-161TH/ISI-161TI[154]Er07
Taylor Icetro ISI-161TH/ISI-161TI[154]Er14
Taylor Icetro ISI-161TH/ISI-161TI[154]Er21
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er07
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er14
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er21
Staff BTX/BFX automatic batch freezers (BTX150, BFX150, BFX200, BFX201, BFX400, BFX600, BFX1000, BFX1500)[193]OL2Agitator motor overload: the product is too stiff (density or time set too high for the batch) or the scrapers drag; free the agitator with the vat defrost, then press reset.
Staff BTX/BFX automatic batch freezers (BTX150, BFX150, BFX200, BFX201, BFX400, BFX600, BFX1000, BFX1500)[193]OH2The agitator motor's internal thermal protection has tripped: let the motor cool, check the density setting and the scrapers, then press reset.

The beater (dasher) motor of an ice cream, shake or frozen drink machine has drawn too much current or its overload protection has tripped, often because the product has frozen too hard, the viscosity setting is too high, the scraper blades are worn or the motor or drive is faulty.

Check: Let the product thaw and reset; check the viscosity or consistency setting, mix and refrigeration (product frozen too hard), scraper blades, drive belt and beater motor current.

Oil level or oil pressure

ControllerCode
Carel Heos[18]dLP
Carel pRack pR300[22]ALB06
Carel pRack pR300T (transcritical CO2)[23]ALB06
Carel pRack pR300T (transcritical CO2)[23]ALC94
Copeland Stream condensing units (Next Gen CoreSense)[27]1 flash
Copeland Large ZX 22–30 HP[29]E56
Copeland Large ZX 22–30 HP[29]L56
Danfoss AK-PC 781A[37]Comp. x oil pressure cut out
Danfoss AK-PC 781A[37]Low oil level comp. x
Danfoss AK-PC 782A/782B[38]Comp. x oil pressure cut out
Copeland CoreSense Protection (Discus)[63]LED green 1
Copeland CoreSense Protection (Discus)[63]LED red 1
LG Multi V 5 VRF outdoor units[77]CH116
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]Oil Failure
Hussmann transcritical CO2 rack (rack controller alarms)[87]Oil Failure
Hussmann transcritical CO2 rack (rack controller alarms)[87]Oil Reservoir Low
Hussmann transcritical CO2 rack (rack controller alarms)[87]Oil Separator High
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]⊿OP LOW
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]OIL LEVEL LOW
Mitsubishi Electric City Multi (M-NET error codes)[102]1559
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AOi1
Castel 5650E/5658E electronic oil level regulator (R744)[123]LED red on
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]H07
RDM Intuitive Superpack / Transcritical Superpack[132]Oil1–Oil9
RDM Intuitive Superpack / Transcritical Superpack[132]OilO
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]15
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]133
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]134
Copeland (CPC) E2 RX/BX/CX controller[163]Oil Failure Occurred
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Low Oil Warning
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Oil Pressure Lockout
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]Signal lamp H2 (oil supply fault) onOil supply fault has tripped (lamp wired per wiring diagram). (The manual does not give the colour.)
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Lamp P04Panel lamp in the wiring example: oil supply fault. (The manual does not give the colour.)

The oil level is low or the oil pressure difference is too small.

Check: Check the oil level in the sight glass, oil return and separator, oil management valves and the oil pressure sensor or switch.

Oil temperature out of range

ControllerCode
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]OIL SUPPLY TEMPERATURE HIGH
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]SEPARATOR OIL TEMPERATURE LOW

The oil temperature in the supply line or the oil separator of a screw compressor is too high or too low.

Check: High: check the oil cooler (water/refrigerant flow, fouling, thermostatic valve) and the discharge temperature. Low: check the separator heater and look for liquid refrigerant reaching the compressor, which dilutes the oil.

Oil filter clogged

ControllerCode
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]OIL FILTER
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]FINE FILTER

The pressure drop across the oil filter or fine filter is above the limit, so the compressor may not get enough oil.

Check: Read the pressure before and after the filter, replace the filter element and look at the oil condition (sample or analysis) to find the source of the dirt.

Compressor fault or lock-out

ControllerCode
Carel Heos[18]GEA
Carel pRack pR300[22]ALC01
Carel µRack[25]A01
Copeland EazyCool ZX (XCM25D)[5]E24
Heatcraft Beacon II[30]A3
Heatcraft Beacon II[30]STRUP
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A19
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]a12
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]a13
Danfoss AK-CC55 Water Loop[35]A19
Danfoss AK-PC 781A[37]Common compr. Safety cutout
Danfoss AK-PC 781A[37]Comp. x FCD safety error
Danfoss AK-PC 782A/782B[38]Common compr. Safety cutout
Danfoss Optyma control AK-RC 113[39]Ec
Danfoss Optyma Plus[4]A98
Danfoss Optyma iCO2[46]H28
Dixell XC645D[48]EA1
Dixell XC645D[48]EA2
Dixell XC645D[48]EA3
Dixell XC645D[48]EA4
Dixell XC645D[48]FC01
Dixell XC645D[48]LC01
Carel µChiller[60]A48
Copeland PerformanceAlert diagnostic module[62]2 flashes
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 6
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 7
Danfoss CDS303/CDS803[69]A49
Secop SLV controller 105N46xx[81]A81
Secop SLV controller 105N46xx[81]E80
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E80
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]Compressor Failure
Hussmann transcritical CO2 rack (rack controller alarms)[87]Compressor Failure
Hussmann transcritical CO2 rack (rack controller alarms)[87]Compressor VFD Alarm
RDM DMTouch / miniDM[91]Pack Fail Shutdown
Temperzone UC8 unit controller[100]F39
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]UE
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]11 flashes
Goodman DX20VC inverter condensing unit[105]E17
Hitachi multi-split heat pump[113]39
Hitachi multi-split heat pump[113]43
Hitachi multi-split heat pump[113]EE
Thermia Calibra[115]Class A
Copeland Electronic Unit Controller[116]HPL
Copeland Electronic Unit Controller[116]DLL
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]H01
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]H01
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]1F
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A18
RDM Mercury AC and roof top unit controllers[130]Compressor Lock Alarm
RDM Mercury AC and roof top unit controllers[130]Cloc
RDM Intuitive / Mercury pack and condenser controllers[131]CP
RDM Intuitive / Mercury pack and condenser controllers[131]Stg1–Stg5
RDM Intuitive / Mercury pack and condenser controllers[131]Co 1–Co 5
RDM Intuitive Superpack / Transcritical Superpack[132]St 1–St 16
RDM Intuitive Superpack / Transcritical Superpack[132]StC 1–StC 16
RDM Intuitive Superpack / Transcritical Superpack[132]Inv 1–Inv 3
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Modbus Dev Locked
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]72
Temperzone UC6 unit controller[135]F
ActronAir Advance / VCC / Genesis 13–17 kW[136]E30
ActronAir Advance / VCC / Genesis 13–17 kW[136]E104
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 04
Danfoss ETC (True cabinets)[142]E4
Carel iJF with VCC (Hillphoenix SMD-H)[161]UCF
Copeland (CPC) E2 RX/BX/CX controller[163]Rack Failure Occurred
Copeland (CPC) E2 RX/BX/CX controller[163]Proof Failure Occurred
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Compressor Module Failure
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.280
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.817
Carel µRack[25]Icon compressor + ALARM flashingCompressor alarm, e.g. compressor thermal overload. (The manual does not give the colour.)
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow dark / green litCompressor non-synchronism: speed deviates from the set frequency for 2 s.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 5 + timer flashingInverter compressor drive error (PC 04). (The manual does not give the colour.)
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D801 yellow (3 s on / 0.5 s off)Current error: Compressor system error (1C).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D802 yellow (3 s on / 0.5 s off)Current error: Compressor breakdown (1F).
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Lamp P05Panel lamp in the wiring example: compressor fault. (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Timer blinkingOutdoor compressor-related fault or protective shutdown (H01–H25: breakdown, lock-up, low-pressure drop, oil level …). (Operation and Ready off.) (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink G-onCompressor out of synchronism: running frequency deviates for 2 s (red blink, yellow off, green on).
IVT AirX air-to-water heat pump[175]5350Compressor control fault, usually a power cut during operation so the compressor could not ramp down normally (warning).
IVT AirX air-to-water heat pump[175]5351Compressor control fault, usually a power cut during operation so the compressor could not ramp down normally (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5350Compressor control fault, usually a power cut during operation so the compressor could not ramp down normally (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5351Compressor control fault, usually a power cut during operation so the compressor could not ramp down normally (alarm).
IVT Geo 500/600 series ground source heat pump[177]5350Compressor running out of step (asynchronous), probably after a power cut (warning).
IVT Geo 500/600 series ground source heat pump[177]5351Compressor running out of step (asynchronous) (alarm).
IVT Geo 500/600 series ground source heat pump[177]5903Compressor motor fault, usually temporary.
IVT Geo 312/412 ground source heat pump[178]5350Compressor running out of step (asynchronous), probably after a power cut (warning).
IVT Geo 312/412 ground source heat pump[178]5351Compressor running out of step (asynchronous) (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5350Compressor control fault, usually a power cut during operation so the compressor could not ramp down normally (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5351Compressor control fault, usually a power cut during operation so the compressor could not ramp down normally (alarm).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 13 flashesCompressor control fault (the compressor does not follow the inverter).
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 13Compressor fault.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 5, test button: Red 5 + Green blinkingInverter fault group; after the test button: compressor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 14 flashesCompressor fault.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C1 40The current transformer CT1 for compressor 1 is not connected or gives no signal: check the CT1 plug and wiring on the PCB.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]C2 40The current transformer CT2 for compressor 2 is not connected or gives no signal: check the CT2 plug and wiring on the PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]95Compressor motor loss of synchronisation (E.95.5). Check the inverter PCB and compressor (lock).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.95.5Compressor motor loss of synchronisation 5 times in a row. Check the inverter PCB (IPM) and the compressor for lock.

The controller has stopped or locked out a compressor (several trips, start failure, safety chain or compressor module).

Check: Read which safety stopped it, check the compressor protection module, the safety chain and the reason for repeated trips before resetting.

Compressor runs too long

ControllerCode
Copeland CoreSense Diagnostics (scroll AC)[64]LED yellow 1
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 1
Full Gauge TC-900E POWER / TC-900E 2HP[117]ALrC
Full Gauge TC-900E Log[118]ALrC
Full Gauge MT-514E Faston[122]ALrC
RDM Intuitive / Mercury pack and condenser controllers[131]Increase LED flashing
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]LEA
Danfoss EETa (True cabinets, LED blink codes)[143]3+1 flashes
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]COMP ON TOO LONG
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]COMP ON TOO LONG
Taylor 736 soft serve freezer[153]TIME OUT
HTPG EcoNet enabled unit coolers[162]A108

The compressor has run without a break for far longer than normal at full load, which usually means the system cannot reach its set point.

Check: Check the refrigerant charge and look for leaks, check that the evaporator fan runs and the coil is not iced or blocked, check the expansion valve and the filter drier, and check the thermostat setting and wiring.

Cooling too slow or not cooling

ControllerCode
True Ice TI/TCIM ice machines[147]E22
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]BARREL NOT COOLING
Taylor R200 fry dispenser[157]Error 5
Taylor R280 fry dispenser[158]Err 5

The controller has seen that the product or cylinder temperature did not fall as expected within a set time after cooling started, so the refrigeration does not deliver its capacity.

Check: Check the condenser and its fan, refrigerant charge, expansion device, solenoid or hot gas valve and compressor; in ice cream machines also the scraper blades and mix.

Compressor short cycling

ControllerCode
Copeland PerformanceAlert diagnostic module[62]3 flashes
Copeland CoreSense Diagnostics (scroll AC)[64]LED yellow 3
Copeland CoreSense Diagnostics (scroll AC)[64]LED red 3
Copeland compressor electronics communications (20–40 ton scroll)[65]LED green 3
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 3
Copeland CoreSense Communications (13–15 ton scroll)[67]LED green 3
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red 3
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green 3
Hussmann transcritical CO2 rack (rack controller alarms)[87]Cycles Exceeded
Kriwan INT69 PYF Diagnose[95]LED red 5 / orange 5
Kriwan INT69 YF Diagnose[98]LED red 5 / orange 5
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]74
Kriwan INT69 YF Diagnose[98]LED green 5 / orange 5Warning: the permitted number of starts (switching frequency) has been exceeded.

The compressor starts and stops too often, with very short run times, so the module counts the starts and warns or locks out.

Check: Check the thermostat or controller differential and set point, the pressure switch settings and the refrigerant charge; add an anti-short-cycle timer if the control lacks one.

Compressor contactor or control circuit fault

ControllerCode
Copeland Digital Compressor Controller[61]8 flashes
Copeland PerformanceAlert diagnostic module[62]8 flashes
Copeland CoreSense Diagnostics (scroll AC)[64]LED red 9
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 8
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 10
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green 8
Taylor R200 fry dispenser[157]Error 7
Taylor R280 fry dispenser[158]Err 7
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Welded Contactor
Copeland CoreSense Communications (13–15 ton scroll)[67]LED yellow 8Current in the S and R windings without a demand signal for 15 s (welded contactor).
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED yellow solidRun demand is present but no compressor current is detected (contactor, motor protector or supply).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 4 + Timer 3The outdoor unit still answers more than 2 min after the indoor main relay switched off, so the relay is probably welded (PCB fault).

The module sees motor current without a run demand (welded contactor), or too much current in the contactor coil circuit it switches.

Check: Isolate the power and check the contactor contacts for welding or pitting, measure the coil and its wiring for shorts, and replace the contactor if it does not open.

Compressor outside its operating envelope

ControllerCode
Carel µChiller[60]A42
Carel µChiller[60]A45
LG Multi V 5 VRF outdoor units[77]CH36
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]⊿P LOW
Temperzone UC8 unit controller[100]CRH
Goodman DX20VC inverter condensing unit[105]E44
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]4
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]6
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]8
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]10
Temperzone UC8 unit controller[100]CRL
Temperzone UC8 unit controller[100]diFF-P
ActronAir Advance / VCC / Genesis 13–17 kW[136]E43
ActronAir Advance / VCC / Genesis 13–17 kW[136]E45
ActronAir Aires and Advance 19–25 kW[137]E43
ActronAir Aires and Advance 19–25 kW[137]E45
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 0L
alpha innotec WWB 190 DHW heat pump[169]E8
alpha innotec WWB 190 DHW heat pump[169]E10
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.304
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.306
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.308
IVT AirX air-to-water heat pump[175]5513Condensing temperature too high, outside the working range; check the water flow and lower the heating curve and the hot water setting.
IVT AirX air-to-water heat pump[175]5512Condensing temperature outside the control range, likely low outdoor temperature combined with high load.
IVT AirSplit 200/300 split air-to-water heat pump[176]5512Condensing temperature outside the control range, likely low outdoor temperature combined with high load.
IVT AirSplit 200/300 split air-to-water heat pump[176]5513Condensing temperature too high, probably at low outdoor temperature.
IVT Geo 500/600 series ground source heat pump[177]5512Condensing temperature outside the compressor envelope, usually temporary.
IVT Geo 500/600 series ground source heat pump[177]5513Condensing too high in relation to the evaporating temperature.
IVT Geo 312/412 ground source heat pump[178]5512Condensing temperature outside the compressor envelope, usually temporary.
IVT Geo 312/412 ground source heat pump[178]5513Condensing too high in relation to the evaporating temperature.
IVT Vent 202/302/402 exhaust air heat pump[179]5512Condensing temperature outside the control range, likely low outdoor temperature combined with high load.
IVT Vent 202/302/402 exhaust air heat pump[179]5513Condensing temperature too high, probably at low outdoor temperature.

The evaporating and condensing pressures put the compressor (often a variable speed BLDC or inverter scroll) outside the operating limits set by its manufacturer, for example too high a compression ratio or too small a pressure difference, for longer than the delay, so the controller stops it.

Check: Compare the suction and discharge pressures with the compressor envelope: look for high head pressure (dirty condenser, fan fault, overcharge), very low suction pressure (low charge, low water flow, iced or fouled evaporator) or too small a pressure difference at low load, and check that the pressure transmitters read correctly.

Capacity slide valve fault

ControllerCode
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]CAPACITY NO DOWN
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]LOW SLIDE VALVE POSITION UNDER/OVER RANGE

The capacity slide valve of a screw compressor does not move as commanded, or its position signal is outside the expected range.

Check: Check the load/unload solenoid valves and their coils, the position potentiometer or transmitter and its calibration, and the oil pressure that moves the slide.

Overcurrent at the drive output

ControllerCode
Danfoss VLT FC 103[14]A13
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]3
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]5
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]7
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]10
Danfoss CDS303/CDS803[69]A13
Danfoss VLT HVAC Basic Drive FC 101[70]A13
Daikin RA / SkyAir / VRV (malfunction codes)[75]E8
Daikin RA / SkyAir / VRV (malfunction codes)[75]L5
LG Multi V 5 VRF outdoor units[77]CH21
LG Multi V 5 VRF outdoor units[77]CH29
NIBE F1255 ground source heat pump[78]453
Mitsubishi Electric City Multi (M-NET error codes)[102]4210
Mitsubishi Electric City Multi (M-NET error codes)[102]4250
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]UP
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]2 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]UP
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U6
Goodman DX20VC inverter condensing unit[105]E34
Hitachi multi-split heat pump[113]48
Hitachi multi-split heat pump[113]52
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P26
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P26
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]14
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A15
Temperzone UC8 unit controller[100]F101
ActronAir Advance / VCC / Genesis 13–17 kW[136]E26
ActronAir Advance / VCC / Genesis 13–17 kW[136]E60
ActronAir Aires and Advance 19–25 kW[137]E26
ActronAir Aires and Advance 19–25 kW[137]E60
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 00
ActronAir UltraSlim 2 ducted split system[140]EB
Taylor Icetro ISI-161TH/ISI-161TI[154]Er53
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er53
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]14 flashes
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow lit / green blinkPFC input over-current protection.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow blink / green blinkPFC module (IGBT) peak current protection.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow blink / green blinkCompressor phase over-current protection.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 14xPeak current error: motor drawing too much current.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 7 + timer flashingIPM/IGBT overcurrent (PC 00) or low pressure protection (PC 03); the table uses 7 flashes for both, so read the code. (The manual does not give the colour.)
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D801+D802 yellow (3 s on / 0.5 s off)Current error: Driving element short circuit (14).
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]1 flashOvercurrent cut-out 3 times within 1 min of start (unit stopped), or frequency drop by current protection while running. (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 2 flashesUP compressor overcurrent interruption (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 9 flashesU6 compressor overcurrent or power module fault (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on Y-on G-blinkPFC input overcurrent (red on, yellow on, green blink).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink Y-blink G-blinkCompressor phase overcurrent (red blink, yellow blink, green blink).
IVT AirX air-to-water heat pump[175]5524Overcurrent in the compressor inverter; a single trip after a power cut can be false, a recurring one points to the inverter or compressor.
IVT AirX air-to-water heat pump[175]5354Inverter output current to the compressor too high (warning).
IVT AirX air-to-water heat pump[175]5355Inverter output current to the compressor too high (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5354Inverter output current to the compressor too high (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5355Inverter output current to the compressor too high (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5600Outdoor unit code 21; IVT gives no detail, on LG-built outdoor units this code usually means an inverter peak-current (IPM) trip.
IVT AirSplit 200/300 split air-to-water heat pump[176]5601Outdoor unit code 21; IVT gives no detail, on LG-built outdoor units this code usually means an inverter peak-current (IPM) trip.
IVT AirSplit 200/300 split air-to-water heat pump[176]5602Outdoor unit code 22; IVT gives no detail, on LG-built outdoor units this code usually means input current too high.
IVT AirSplit 200/300 split air-to-water heat pump[176]5603Outdoor unit code 22; IVT gives no detail, on LG-built outdoor units this code usually means input current too high.
IVT AirSplit 200/300 split air-to-water heat pump[176]5612LG outdoor unit code 27 (info); IVT gives no detail, usually a fault or overcurrent in the PFC (input) stage.
IVT AirSplit 200/300 split air-to-water heat pump[176]5613LG outdoor unit code 27 (alarm); IVT gives no detail, usually a fault or overcurrent in the PFC (input) stage.
IVT AirSplit 200/300 split air-to-water heat pump[176]5616Compressor current too high, LG code 29 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5617Compressor current too high, LG code 29 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5354Compressor overcurrent, probably after a power cut (warning).
IVT Geo 500/600 series ground source heat pump[177]5355Inverter output current to the compressor too high (alarm).
IVT Geo 500/600 series ground source heat pump[177]5523Overcurrent in the PFC (input) stage of the inverter; check that every phase is connected (warning).
IVT Geo 500/600 series ground source heat pump[177]5524Overcurrent in the PFC (input) stage of the inverter (alarm).
IVT Geo 500/600 series ground source heat pump[177]5906Short heavy overload of the compressor motor, usually temporary (info).
IVT Geo 500/600 series ground source heat pump[177]5987Short heavy overload of the compressor motor (alarm).
IVT Geo 312/412 ground source heat pump[178]5354Compressor overcurrent, probably after a power cut (warning).
IVT Geo 312/412 ground source heat pump[178]5355Inverter output current to the compressor too high (alarm).
IVT Geo 312/412 ground source heat pump[178]5523Overcurrent in the PFC (input) stage of the inverter; check that every phase is connected (warning).
IVT Geo 312/412 ground source heat pump[178]5524Overcurrent in the PFC (input) stage of the inverter (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5354Inverter output current to the compressor too high (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5355Inverter output current to the compressor too high (alarm).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 5 + Timer 2Inverter power module (IPM) protection from too high current (code 17): check that the outdoor fan runs, that air can reach the coil, and the refrigerant charge.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 5 + Timer 2Outdoor inverter power module (IPM) fault or overcurrent (17).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 12 flashesOvercurrent in the outdoor unit.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 14 flashesInverter power module (IPM) fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]17Inverter power module (IPM) protection.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 10Inverter power module (IPM) fault.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 5, test button: Red 2 + Green blinkingInverter fault group; after the test button: IPM fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 10Current trip (overcurrent).
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 12Inverter power module (IPM) fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 12 flashesInverter power module (IPM) fault.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]94Trip detection: repeated overcurrent after start (E.94.1). Check outdoor air flow, inverter PCB, compressor and SV2 coil.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.94.1Trip detection: overcurrent after start-up 5 times in a row (count resets if no new trip within 40 s of restart). Check outdoor air flow (fan, dirty coil, recirculation, high ambient), the inverter PCB, the compressor and the SV2 coil.

The output current has exceeded the drive's peak limit, for example from a blocked or seized motor, a sudden load step or a motor that is too large for the drive.

Check: Switch off, then check that the compressor or fan turns freely, that the motor size matches the drive and that the motor data and ramp times are set correctly.

Drive overloaded (current or torque limit)

ControllerCode
Danfoss VLT FC 103[14]A9
Danfoss VLT FC 103[14]A12
Carel ir33+ VCC[20]UCF
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]6
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]8
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]9
Danfoss VLT HVAC Basic Drive FC 101[70]A9
Danfoss VLT HVAC Basic Drive FC 101[70]W59
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]I_Limit
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 1
Danfoss VLT FC 103[14]W59
Daikin RA / SkyAir / VRV (malfunction codes)[75]L8
LG Multi V 5 VRF outdoor units[77]CH22
NIBE F1255 ground source heat pump[78]441
NIBE F1255 ground source heat pump[78]455
Danfoss CDS303/CDS803[69]A12
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]4 flashes
Secop SLV controller 105N46xx[81]A82
Mitsubishi Electric City Multi (M-NET error codes)[102]4240
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red steady
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red fast
ActronAir Advance / VCC / Genesis 13–17 kW[136]E47
ActronAir Advance / VCC / Genesis 13–17 kW[136]E99
ActronAir Aires and Advance 19–25 kW[137]E47
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 08
ActronAir Nexus Touch Controller WTC-01[139]PC08
Copeland (CPC) E2 RX/BX/CX controller[163]VS Inverter Fail
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow dark / green blinkCompressor IPM module protection (low drive voltage or IPM over-current).
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 1 + timer flashingCurrent overload protection (PC 08). (The manual does not give the colour.)
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 3Warning: the power limiter is reducing output.
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Symbol overloadOverload: output current is above the nominal motor current. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on Y-blink G-blinkPFC module (IGBT) peak-current protection (red on, yellow blink, green blink).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink G-blinkCompressor IPM module protection (low drive voltage or high IPM current) (red blink, yellow off, green blink).
IVT Geo 500/600 series ground source heat pump[177]5902Compressor motor overload, possibly from low voltage between phase and neutral.
IVT Geo 500/600 series ground source heat pump[177]5990Compressor motor overloaded; check fuses and the supply voltage.

The drive has delivered more than its rated current or the set torque limit for too long, so it limits the speed or trips to protect itself.

Check: Check the load on the compressor or fan (high condensing pressure, dirty condenser, liquid in the compressor, stiff bearings) and that the drive is sized for the motor; check the motor data and the current and torque limits.

Motor overload (calculated, ETR)

ControllerCode
Danfoss VLT FC 103[14]A10
Danfoss VLT HVAC Basic Drive FC 101[70]A10

The drive's electronic thermal model calculates that the motor has run above its rated current for so long that it is too hot.

Check: Check that the motor rated current is set correctly in the drive and that the motor is not overloaded; at low speed check that the motor still gets enough cooling.

Motor thermistor tripped

ControllerCode
Danfoss VLT FC 103[14]A11
Copeland Stream condensing units (Next Gen CoreSense)[27]2 flashes
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 2
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red 1
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red 2
Danfoss VLT HVAC Basic Drive FC 101[70]A11
Kriwan INT69 F Diagnose[94]LED red 1 / orange 1
Kriwan INT69 F Diagnose[94]LED red 1 / orange 4
Kriwan INT69 PYF Diagnose[95]LED red 1 / orange 1
Kriwan INT69 PYF Diagnose[95]LED red 1 / orange 4
Kriwan INT69 UY Diagnose[96]LED red 1 / orange 1
Kriwan INT69 UY Diagnose[96]LED red 1 / orange 4
Kriwan INT69 Y Diagnose[97]LED red 1 / orange 1
Kriwan INT69 Y Diagnose[97]LED red 1 / orange 2
Kriwan INT69 Y Diagnose[97]LED red 1 / orange 3
Kriwan INT69 Y Diagnose[97]LED red 1 / orange 4
Kriwan INT69 Y Diagnose[97]LED red 1 / orange 5
Kriwan INT69 YF Diagnose[98]LED red 1 / orange 1
Kriwan INT69 YF Diagnose[98]LED red 1 / orange 4
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]20
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]62
ActronAir Advance / VCC / Genesis 13–17 kW[136]E80
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]Signal lamp H1 (overtemperature) onMotor or discharge gas overtemperature has tripped (lamp wired per wiring diagram). (The manual does not give the colour.)
Kriwan INT69 F Diagnose[94]LED green 1 / orange 1Warning: motor winding temperature is above the permitted value; the motor still runs.
Kriwan INT69 F Diagnose[94]LED green 1 / orange 4Warning: open or short circuit on the motor temperature sensor input.

The thermistor (PTC) in the motor windings reports too high a temperature, or its circuit to the drive is open.

Check: Measure the thermistor resistance and its wiring to the drive input; if the circuit is intact, look for why the motor runs hot (overload, poor cooling, low suction gas flow, phase fault).

Motor phase missing

ControllerCode
Danfoss VLT FC 103[14]A30
Danfoss VLT FC 103[14]A31
Danfoss VLT FC 103[14]A32
Danfoss Optyma iCO2[46]H27
Danfoss CDS303/CDS803[69]A30
Danfoss CDS303/CDS803[69]A31
Danfoss CDS303/CDS803[69]A32
Danfoss VLT HVAC Basic Drive FC 101[70]A3
Danfoss VLT HVAC Basic Drive FC 101[70]A30
Danfoss VLT HVAC Basic Drive FC 101[70]A31
Danfoss VLT HVAC Basic Drive FC 101[70]A32
NIBE F1255 ground source heat pump[78]435
NIBE F1255 ground source heat pump[78]447
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]12 flashes
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]18
Temperzone UC8 unit controller[100]F117
ActronAir Advance / VCC / Genesis 13–17 kW[136]E61
ActronAir Aires and Advance 19–25 kW[137]E61
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 4xPhase failure on the incoming supply.
Kriwan INT69 UY Diagnose[96]LED red 2 / orange 4Restart delay running after a phase-monitoring error; the unit stays off until it expires.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Outdoor board LED1+LED2 blinkingReverse or open phase on the outdoor power terminal block (L1, L2, L3). (The manual does not give the colour.)
IVT Geo 500/600 series ground source heat pump[177]5900Phase lost to the compressor; check the fuses.
IVT Geo 500/600 series ground source heat pump[177]5981Compressor turning the wrong way, usually temporary (info); if it repeats, check the U-V-W order between inverter and compressor.
IVT Geo 500/600 series ground source heat pump[177]5983Compressor turning the wrong way (alarm); check the U-V-W order between inverter and compressor.
IVT Geo 500/600 series ground source heat pump[177]5989No phase between the inverter control and the compressor motor; check the fuses.

The drive has lost one of the phases between its output and the motor, or no motor is connected.

Check: Switch off and check the motor cable, terminals and any contactor or service switch between the drive and the motor, and measure the motor windings.

Earth fault or short circuit at the motor output

ControllerCode
Danfoss VLT FC 103[14]A14
Danfoss VLT FC 103[14]A16
Danfoss CDS303/CDS803[69]A14
Danfoss CDS303/CDS803[69]A45
Danfoss VLT HVAC Basic Drive FC 101[70]A14
Danfoss VLT HVAC Basic Drive FC 101[70]A16
Danfoss VLT HVAC Basic Drive FC 101[70]A44
Danfoss CDS303/CDS803[69]A16
Mitsubishi Electric City Multi (M-NET error codes)[102]4104
Goodman DX20VC inverter condensing unit[105]E31
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red 1 s
Temperzone UC8 unit controller[100]F125
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 6xPower module failure: short to earth or damaged motor winding.

Current leaks from the output phases to earth, or two phases are short-circuited, in the motor cable or in the motor itself.

Check: Switch off and isolate, then measure the insulation of the motor and the motor cable phase to earth and phase to phase; look for damaged cables, moisture in terminal boxes and burnt windings.

Compressor start failed

ControllerCode
Danfoss VLT FC 103[14]A18
Carel Heos[18]CSF
Danfoss Optyma iCO2[46]H29
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]14
Carel µChiller[60]A44
Copeland Digital Compressor Controller[61]4 flashes
Copeland PerformanceAlert diagnostic module[62]4 flashes
Copeland CoreSense Diagnostics (scroll AC)[64]LED yellow 4
Copeland CoreSense Diagnostics (scroll AC)[64]LED red 4
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 4
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED red 4
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED yellow 4
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED red 4
Danfoss CDS303/CDS803[69]A18
Danfoss VLT HVAC Basic Drive FC 101[70]A18
Danfoss VLT HVAC Basic Drive FC 101[70]A99
Danfoss VLT FC 103[14]A99
Daikin RA / SkyAir / VRV (malfunction codes)[75]L9
LG Multi V 5 VRF outdoor units[77]CH26
NIBE F1255 ground source heat pump[78]449
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]3 flashes
AHT electronic controller (plug-in cases, standard)[82]FU3
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]START
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]8 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]UF
Goodman DX20VC inverter condensing unit[105]E36
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]H02
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]H02
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]1D
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A17
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]16
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]11
ActronAir Advance / VCC / Genesis 13–17 kW[136]E64
ActronAir Aires and Advance 19–25 kW[137]E90
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow blink / green darkCompressor start failure (10 s without synchronous running).
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 11xStart attempted while the fan was turning backwards.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D802 yellow (3 s on / 0.5 s off)Current error: Compressor lock (1D).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 4 flashesUF compressor overcurrent with locked compressor (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on Y-blinkCompressor start failure: not synchronised for 10 s (red on, yellow blink, green off).
IVT AirX air-to-water heat pump[175]5506The compressor did not start; often a temporary disturbance.
IVT AirSplit 200/300 split air-to-water heat pump[176]5506The compressor did not start; often a temporary disturbance.
IVT AirSplit 200/300 split air-to-water heat pump[176]5610Outdoor unit code 26; IVT gives no detail, on LG-built outdoor units this code usually means the compressor rotor position was not found at start.
IVT AirSplit 200/300 split air-to-water heat pump[176]5611Outdoor unit code 26; IVT gives no detail, on LG-built outdoor units this code usually means the compressor rotor position was not found at start.
IVT AirSplit 200/300 split air-to-water heat pump[176]5648Compressor start current too high, LG code 73 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5649Compressor start current too high, LG code 73 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5506The compressor does not start; switch the heat pump supply off and on.
IVT Geo 312/412 ground source heat pump[178]5506The compressor does not start; switch the heat pump supply off and on.
IVT Vent 202/302/402 exhaust air heat pump[179]5506The compressor did not start within 2 min of the start signal; a new attempt is allowed after another 2 min.
IVT Vent 202/302/402 exhaust air heat pump[179]6209The compressor does not start.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 5 + Timer 5The compressor does not follow the inverter (rotor position or start failure, code 1A): check that both service valves are open, winding resistance and compressor leads.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 5 + Timer 5Compressor rotor position or start fault (1A).
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]1ACompressor rotor position or start fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 12Compressor rotor position fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 13Compressor start failure.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 13Compressor rotor position fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 14Compressor start failure.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 13 flashesCompressor rotor position fault.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]93Inverter compressor start-up error (E.93.1). Check the compressor wiring, inverter PCB and compressor.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.93.1Inverter compressor start-up error: overcurrent at start, retried 60 times in each of 2 sets (at least about 100 min before the code shows; retries only with an indoor unit calling). Check the inverter PCB–compressor wiring, the inverter PCB (IPM) and the compressor for lock or shorted windings.

The compressor did not reach the required start speed within the allowed time, which often points to a blocked rotor or too high a pressure difference at start.

Check: Check the pressure difference across the compressor at start (equalisation, start unloading), liquid or oil in the cylinders, and that the compressor turns freely; check the start speed and start time settings.

Voltage or phase fault

ControllerCode
Danfoss ERC 21X[1]AA1
Copeland EazyCool ZX (XCM25D)[5]E26
Copeland EazyCool ZX (XCM25D)[5]E20
Copeland EazyCool ZX (XCM25D)[5]E22
Carel μC2SE[8]ELS
Danfoss VLT FC 103[14]A4
Danfoss VLT FC 103[14]A36
Carpigiani AES PSP[15]AL15
Carel EVD evolution / EVD evolution twin[16]Wrong power supply mode
Carel EVD evolution / EVD evolution twin[16]Battery discharged
Carel EVD ice / EVD mini[17]E7
Carel µRack[25]EHS
Carel µRack[25]ELS
Carel µRack[25]EL1
Copeland EXD-SH1/2[26]PFA
Copeland Stream condensing units (Next Gen CoreSense)[27]5 flashes
Copeland EazyCool ZX (XCM25D)[5]L20
Copeland EazyCool ZX (XCM25D)[5]L21
Copeland EazyCool ZX (XCM25D)[5]E27
Copeland EazyCool ZX (XCM25D)[5]E30
Copeland Large ZX 22–30 HP[29]E20
Copeland Large ZX 22–30 HP[29]L20
Copeland Large ZX 22–30 HP[29]L21
Copeland Large ZX 22–30 HP[29]E22
Copeland Large ZX 22–30 HP[29]E26
Copeland Large ZX 22–30 HP[29]E27
Copeland Large ZX 22–30 HP[29]E30
Danfoss AK-PC 782A/782B[38]External power loss
Danfoss EKE 1A/1B/1C/1D[43]E123
Danfoss EKE 100[44]A05
Danfoss ERC 21X[1]A99
Danfoss Optyma Plus Module B Plus (P02)[45]Y2-R1
Danfoss Optyma Plus Module B Plus (P02)[45]Y2-R2
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]21
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]22
Carel µC2SE for process chiller[59]ELS
Carel µC2SE for process chiller[59]EHS
Copeland Digital Compressor Controller[61]9 flashes
Copeland PerformanceAlert diagnostic module[62]6 flashes
Copeland PerformanceAlert diagnostic module[62]7 flashes
Copeland PerformanceAlert diagnostic module[62]9 flashes
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 6
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 7
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red 9
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED yellow 9
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red 6
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red 7
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red 9
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED yellow 6
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED red 6
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED red 7
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED yellow 9
Danfoss CDS303/CDS803[69]A36
Danfoss VLT HVAC Basic Drive FC 101[70]A4
Danfoss VLT HVAC Basic Drive FC 101[70]A36
Danfoss Gas Sensor DGS[71]Voltage Error
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X Voltage
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]Power Failure
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]PHA
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]UeHigh
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]L_high
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 1
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 2
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 15
Daikin RA / SkyAir / VRV (malfunction codes)[75]P1
Daikin RA / SkyAir / VRV (malfunction codes)[75]U1
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]ERR PHASE SEQ.
LG Multi V 5 VRF outdoor units[77]CH25
LG Multi V 5 VRF outdoor units[77]CH50
NIBE F1255 ground source heat pump[78]431
NIBE F1255 ground source heat pump[78]433
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]1 flashes
Secop SLV controller 105N46xx[81]A93
Secop SLV controller 105N46xx[81]A95
AHT electronic controller (plug-in cases, standard)[82]FU7
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E93
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E95
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]Phase Loss
Hussmann transcritical CO2 rack (rack controller alarms)[87]Phase Loss
RDM DMTouch / miniDM[91]Power Fail
Kriwan INT69 PYF Diagnose[95]LED red 2 / orange 1
Kriwan INT69 PYF Diagnose[95]LED red 2 / orange 2
Kriwan INT69 PYF Diagnose[95]LED red 2 / orange 3
Kriwan INT69 UY Diagnose[96]LED red 2 / orange 1
Kriwan INT69 UY Diagnose[96]LED red 2 / orange 2
Kriwan INT69 UY Diagnose[96]LED red 2 / orange 3
Kriwan INT69 UY Diagnose[96]LED red 2 / orange 5
Kriwan INT69 UY Diagnose[96]LED red 3 / orange 1
Kriwan INT69 Y Diagnose[97]LED red 2 / orange 1
Kriwan INT69 Y Diagnose[97]LED red 2 / orange 2
Kriwan INT69 Y Diagnose[97]LED red 3 / orange 1
Kriwan INT69 YF Diagnose[98]LED red 2 / orange 1
Kriwan INT69 YF Diagnose[98]LED red 2 / orange 2
Kriwan INT69 YF Diagnose[98]LED red 2 / orange 3
Kriwan INT69 YF Diagnose[98]LED red 5 / orange 2
Temperzone UC8 unit controller[100]F30
Temperzone UC7 unit controller[101]F30
Mitsubishi Electric City Multi (M-NET error codes)[102]4102
Mitsubishi Electric City Multi (M-NET error codes)[102]4103
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U9
Goodman DX20VC inverter condensing unit[105]E38
Goodman DX20VC inverter condensing unit[105]E42
Goodman DX20VC inverter condensing unit[105]E43
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED yellow rapid
Evco EVK214[109]PF
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]APH
Hitachi multi-split heat pump[113]05
Hitachi multi-split heat pump[113]06
Thermia Atella / Robust[114]ERR PHASE SEQ.
Full Gauge MT-514E Faston[122]AVoL
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P05
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]L31
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P05
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A21
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]2
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]19
ActronAir Advance / VCC / Genesis 13–17 kW[136]E27
ActronAir Advance / VCC / Genesis 13–17 kW[136]E29
ActronAir Aires and Advance 19–25 kW[137]E27
ActronAir Aires and Advance 19–25 kW[137]E29
ActronAir Aires and Advance 19–25 kW[137]E65
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 01
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 10
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 11
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]uHi
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]uLi
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]uLo
Danfoss ETC (True cabinets)[142]Ulo
Danfoss ETC (True cabinets)[142]UHi
Danfoss EETa (True cabinets, LED blink codes)[143]1+2 flashes
Taylor 736 soft serve freezer[153]PHASES
Taylor 736 soft serve freezer[153]PHASES/N
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er10
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er11
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er16
Taylor R200 fry dispenser[157]DC Power Low
Carel iJF with VCC (Hillphoenix SMD-H)[161]EHI
Carel iJF with VCC (Hillphoenix SMD-H)[161]ELO
Copeland (CPC) E2 RX/BX/CX controller[163]REFR Phase Loss
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Missing Phase Trip
Copeland (CPC) E2 RX/BX/CX controller[163]ISD Supply Voltage Trip
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.281
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.818
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]4 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]12 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]13 flashes
Copeland Digital Compressor Controller[61]All LEDs flashing together24 VAC supply is too low for operation.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow blink / green darkDC bus voltage too low or too high.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED offNo voltage to the fan motor (or power module cooling down); check supply.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 12xLine voltage too low.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 13xLine voltage too high.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 3, timer offZero-crossing signal detection error (EH 02). (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 2 + timer flashingOver- or undervoltage protection (PC 01). (The manual does not give the colour.)
Heatcraft Beacon II[30]Display 888Shown briefly at power-up; if it stays, the board supply is below about 18 V.
Heatcraft Beacon II[30]Display darkDisplay not lit: no 24 V at the control board; check supply, transformer and wiring.
Copeland PerformanceAlert diagnostic module[62]LED red + yellow flashing togetherMiswiring: the module C and L terminals do not get 85-265 V AC, or the contactor coil is on terminal P.
Copeland PerformanceAlert diagnostic module[62]LED green offThe module does not power up: no line voltage on C and L, or they are not connected.
Copeland PerformanceAlert diagnostic module[62]LED green only when compressor runsL and Y are probably swapped: the module needs a constant supply from the line side of the contactor.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller POWER LED offThe condenser controller has no supply power.
Taylor R280 fry dispenser[158]DCV power indicator off, switch litNo DC control voltage although the power switch is on; reset DC breaker CB1. (The manual does not give the colour.)
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Symbol mains interruptedThe incoming mains voltage has been interrupted. (The manual does not give the colour.)
Danfoss Gas Sensor DGS[71]LED offNo power to the sensor; check supply and wiring.
Copeland CoreSense Diagnostics (scroll AC)[64]LED red + yellow flashing together24 V AC control-circuit voltage is too low; the module keeps resetting and stored alerts are cleared.
Temperzone UC8 unit controller[100]Power light offNo mains at the controller: check supply, control circuit breaker, wiring and the board fuse. (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 11 flashesU9/UH over/undervoltage, sync signal or current sensor error (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block all offIndoor unit power is off, or wiring between the receiving unit and the indoor unit is faulty. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink Y-blinkDC bus voltage too low or too high (red blink, yellow blink, green off).
IVT AirX air-to-water heat pump[175]5453No supply to the outdoor unit; check the fuses. It can appear briefly at start-up or after a power cut and then clears itself.
IVT AirX air-to-water heat pump[175]5347Supply voltage to the installer module below 170 V; it resets when above 190 V for 2 min.
IVT AirX air-to-water heat pump[175]5362Mains overvoltage: loose main fuses, an unstable grid or, in some cases, a solar PV system.
IVT AirSplit 200/300 split air-to-water heat pump[176]5273Phase monitoring: check the fuse in the indoor unit feeding the outdoor unit and the main fuses.
IVT AirSplit 200/300 split air-to-water heat pump[176]5347Supply voltage to the installer module below 170 V; it resets when above 190 V for 2 min.
IVT AirSplit 200/300 split air-to-water heat pump[176]5362Mains overvoltage: loose main fuses, an unstable grid or, in some cases, a solar PV system.
IVT AirSplit 200/300 split air-to-water heat pump[176]5453No supply to the outdoor unit; check the fuses.
IVT AirSplit 200/300 split air-to-water heat pump[176]5636Wrong phase sequence or a missing phase, LG code 54 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5637Wrong phase sequence or a missing phase, LG code 54 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5273Phase monitoring: a fuse for the heat pump has tripped.
IVT Geo 500/600 series ground source heat pump[177]5347Supply voltage too low; check the fuses.
IVT Geo 500/600 series ground source heat pump[177]5362Mains voltage too high; check the main fuses for poor contact.
IVT Geo 500/600 series ground source heat pump[177]5370Overvoltage; the compressor stops and the alarm must be reset before it may restart.
IVT Geo 500/600 series ground source heat pump[177]5453No supply to the heat pump; check the main fuses for tripping or poor contact.
IVT Geo 500/600 series ground source heat pump[177]5905Supply voltage to the inverter control below 180 V AC.
IVT Geo 500/600 series ground source heat pump[177]5920Supply voltage to circulation pump PC0 below 150 V.
IVT Geo 500/600 series ground source heat pump[177]5922Supply voltage to circulation pump PC0 too high.
IVT Geo 500/600 series ground source heat pump[177]5939Supply voltage to circulation pump PC0 too low (info).
IVT Geo 312/412 ground source heat pump[178]5347Supply voltage too low; check the fuses.
IVT Geo 312/412 ground source heat pump[178]5362Mains voltage too high; check the main fuses for poor contact.
IVT Geo 312/412 ground source heat pump[178]5453No supply to the heat pump; check the main fuses for tripping or poor contact.
IVT Vent 202/302/402 exhaust air heat pump[179]5273Phase monitoring: check the fuse in the indoor unit feeding the outdoor unit and the main fuses.
IVT Vent 202/302/402 exhaust air heat pump[179]5347Supply voltage to the installer module below 170 V; it resets when above 190 V for 2 min.
IVT Vent 202/302/402 exhaust air heat pump[179]5362Mains overvoltage: loose main fuses, an unstable grid or, in some cases, a solar PV system.
IVT Vent 202/302/402 exhaust air heat pump[179]5453No supply to the outdoor unit; check the fuses.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 4 + Timer 4The indoor unit cannot detect the supply frequency after power-on and stops permanently; usually an indoor PCB fault.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 8 + Timer 2Active filter module (AFM) voltage fault, permanent stop (code 19): check the choke coil and connectors, then the AFM or PCB.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 8 + Timer 3Active filter module (AFM) output voltage fault (code 19), first occurrence: check the wiring and the choke coil.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 4 + Timer 4Indoor unit cannot detect 50/60 Hz supply frequency (08).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 8 + Timer 2Active filter module fault, second time, unit stops (19).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 8 + Timer 3Active filter module fault, first time.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 22 flashesActive filter fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]08Power supply connection or 50/60 Hz detection fault: check supply and wiring.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]19Active filter module (AFM) fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]2ASupply frequency cannot be detected.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E8:00Wrong or faulty power supply connection.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 2Outdoor power connection fault.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 12Active filter module (AFM) fault.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 4 + Green blinking, test button: Red blinking + Green 4Indoor control fault group; after the test button: power source fault.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 1 + LED 2 steadyPower source fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red steady + Green long pulses (D, E, F)Power failure has been detected.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 2 short (F)Three-phase supply connected in the wrong phase order.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]05Reverse phase sequence or a missing phase on the main supply: measure all three phases and check the rotation with a phase-sequence meter; swap two incoming supply wires at the main terminals, never wires inside the unit.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]93The main supply dropped out for less than 2 s: check the supply, loose terminals and contactor contacts.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]94The main supply was off for more than 2 s: check the supply, the main fuses and the main switch.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]31Indoor unit power frequency abnormal: the indoor PCB cannot read the mains frequency. Check about 230 V AC on indoor terminals 1–2 and for voltage dips or noise; if the supply is good, replace the indoor PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]31Indoor unit power frequency abnormal. Check about 230 V AC on indoor terminals 1–2, then the indoor PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]67Inverter PCB short power interruption detected (E.67.2). Check the supply for dips and loose terminals.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.67.2Inverter PCB short power interruption detected (momentary power failure); indoor units show nothing. Check the supply for dips, loose terminals and the filter PCB.
Fujitsu AIRSTAGE J-II VRF – signal amplifier UTY-VSGX (7-segment display)[201]No displayPower supply error: the 7-segment display stays dark. Check the power cable, the terminal–power PCB and power PCB–main PCB connections and reset the supply; with rated voltage present, replace the amplifier.
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]No displayPower supply error: the 7-segment display stays dark. Check the power cable and the PCB connectors and reset the supply; with rated voltage present (220 V on single split use), replace the convertor.
Fujitsu AIRSTAGE J-II VRF – external switch controller UTY-TEKX (LED)[203]LED off, no operationPower supply error: no 12 V (±10 %) between the red and black terminals. Check the indoor unit, the connection cable and its connector on the controller PCB; with 12 V present, replace the controller.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 3 + Timer 1 + Filter flashing fastIndoor unit power frequency abnormal (code 31). Check about 230 V AC on indoor terminals 1–2. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)

The controller has measured too low a voltage, a missing phase or imbalance between the phases. The alarm is a protection function for the compressor.

Check: Measure the supply voltage on all phases during start and operation. Check fuses, terminals and cables.

DC link overvoltage in the drive

ControllerCode
Danfoss VLT FC 103[14]A7
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]1
Danfoss VLT HVAC Basic Drive FC 101[70]A7
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]UzHigh
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 13
Danfoss CDS303/CDS803[69]A7
AHT electronic controller (plug-in cases, standard)[82]FU4
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red/yellow 1 s
Temperzone UC8 unit controller[100]F103
ActronAir Advance / VCC / Genesis 13–17 kW[136]E62
ActronAir Aires and Advance 19–25 kW[137]E62
Taylor Icetro ISI-161TH/ISI-161TI[154]Er54
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er54
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]8 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 8xDC link voltage above limit.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 8 + Timer 4Too high DC voltage in the PFC circuit of the inverter PCB (code 25); usually a PCB fault.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 8 + Timer 4PFC circuit fault in the outdoor inverter.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]25PFC circuit fault (too high DC voltage in the inverter).

The voltage in the drive's DC link has risen above its limit, usually because the motor feeds energy back during fast deceleration or because the mains voltage is too high.

Check: Check the mains voltage, lengthen the deceleration ramp or turn on overvoltage control; on fans that windmill in the wind, check that the drive catches the spinning fan instead of braking it hard.

DC link undervoltage in the drive

ControllerCode
Danfoss VLT FC 103[14]A8
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]2
Danfoss VLT HVAC Basic Drive FC 101[70]A8
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]UzLow
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 13
LG Multi V 5 VRF outdoor units[77]CH23
Danfoss CDS303/CDS803[69]A8
Mitsubishi Electric City Multi (M-NET error codes)[102]4220
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]13 flashes
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red/yellow fast
ActronAir Advance / VCC / Genesis 13–17 kW[136]E63
ActronAir Aires and Advance 19–25 kW[137]E63
Taylor Icetro ISI-161TH/ISI-161TI[154]Er56
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er57
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]7 flashes
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow blink / green litCharging circuit fault: bus voltage below 100 V twice after start-up.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 7xDC link voltage below limit.
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 7Warning: DC link voltage is low.
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink Y-blink G-onCharging circuit fault: bus voltage below 100 V twice after start-up (red blink, yellow blink, green on).
IVT AirSplit 200/300 split air-to-water heat pump[176]5604Outdoor unit code 23; IVT gives no detail, on LG-built outdoor units this code usually means DC link voltage too low or too high.
IVT AirSplit 200/300 split air-to-water heat pump[176]5605Outdoor unit code 23; IVT gives no detail, on LG-built outdoor units this code usually means DC link voltage too low or too high.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.97.4Outdoor fan motor undervoltage: the DC supply has dropped to 180 V or less. Check the mains supply for dips and loose wiring, then the electrolytic capacitor and DC detection on the main PCB.

The voltage in the drive's DC link has fallen below its limit, usually because the supply voltage dips or a phase or fuse is lost.

Check: Measure the mains voltage on all three phases under load, check fuses, contactors and terminals ahead of the drive, and check that the supply matches the drive's rated voltage.

Drive overheated or cooling fan fault

ControllerCode
Danfoss VLT FC 103[14]A29
Danfoss VLT FC 103[14]W24
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]11
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]12
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]29
Danfoss VLT HVAC Basic Drive FC 101[70]W24
Danfoss VLT HVAC Basic Drive FC 101[70]A69
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]TFE
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]TE_high
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]TEI_high
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 3
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 4
Danfoss VLT FC 103[14]W23
Daikin RA / SkyAir / VRV (malfunction codes)[75]L4
LG Multi V 5 VRF outdoor units[77]CH62
NIBE F1255 ground source heat pump[78]439
Danfoss CDS303/CDS803[69]A29
Danfoss CDS303/CDS803[69]A65
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]5 flashes
Secop SLV controller 105N46xx[81]A92
Secop SLV controller 105N46xx[81]A97
Secop SLV controller 105N46xx[81]A98
AHT electronic controller (plug-in cases, standard)[82]FU5
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E75
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E92
Mitsubishi Electric City Multi (M-NET error codes)[102]4230
Mitsubishi Electric City Multi (M-NET error codes)[102]4260
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]4 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U5
Goodman DX20VC inverter condensing unit[105]E32
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red 1 s + fast
Hitachi multi-split heat pump[113]54
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P07
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P07
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A14
ActronAir Advance / VCC / Genesis 13–17 kW[136]E28
ActronAir Aires and Advance 19–25 kW[137]E28
Taylor Icetro ISI-161TH/ISI-161TI[154]Er55
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er55
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.282
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.819
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]9 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]17 flashes
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow blink / green litCompressor IPM overheat (above 96 °C).
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 9xPower module is cooling down.
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 6Warning: temperature inside the electronics is high.
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Symbol reduced switching frequencyThe inverter has lowered its switching frequency because the heat sink is hot. (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 7 flashesU5 heat-sink temperature abnormal (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on Y-blink G-onCompressor IPM overheating (above about 96 °C) (red on, yellow blink, green on).
IVT AirX air-to-water heat pump[175]5302Inverter internal temperature above 80 °C (warning).
IVT AirX air-to-water heat pump[175]5303Inverter too hot (alarm).
IVT AirX air-to-water heat pump[175]5387The PFC (input) stage of the compressor inverter has overheated.
IVT AirSplit 200/300 split air-to-water heat pump[176]5302Inverter internal temperature above 80 °C (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5303Inverter too hot (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5387The PFC (input) stage of the compressor inverter has overheated.
IVT AirSplit 200/300 split air-to-water heat pump[176]5642Inverter temperature above 85 °C, LG code 62 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5643Inverter temperature above 85 °C, LG code 62 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5302Compressor inverter too hot because of poor heat transfer to its cooling loop (warning).
IVT Geo 500/600 series ground source heat pump[177]5303Compressor inverter too hot because of poor heat transfer to its cooling loop (alarm).
IVT Geo 500/600 series ground source heat pump[177]5387The compressor inverter is too hot.
IVT Geo 312/412 ground source heat pump[178]5302Compressor inverter too hot because of poor heat transfer to its cooling loop (warning).
IVT Geo 312/412 ground source heat pump[178]5303Compressor inverter too hot because of poor heat transfer to its cooling loop (alarm).
IVT Geo 312/412 ground source heat pump[178]5387The compressor inverter is too hot.
IVT Vent 202/302/402 exhaust air heat pump[179]5302Inverter internal temperature above 80 °C (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5303Inverter too hot (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5387The PFC (input) stage of the compressor inverter has overheated.

The drive's heatsink or electronics are too hot, or its cooling fan is not running, so the drive warns and then trips.

Check: Check the air temperature around the drive, that the cooling fans run and that the heatsink and air paths are clean and free; also check the load and the motor cable length.

Flow switch has tripped

ControllerCode
Carel μC2SE[8]FL
Danfoss AK-PC 781A[37]Flow switch alarm
Carel µC2SE for process chiller[59]FL
Carel µChiller[60]A10
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]BRINEFLOW LOW
Evco EV3 HP / EVD HP (heat pump)[110]AFLo
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AFLo
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A01
RDM Mercury AC and roof top unit controllers[130]Evap. Press/Pump Fault
RDM Mercury AC and roof top unit controllers[130]Evaporator Lock Alarm
RDM Mercury AC and roof top unit controllers[130]Eloc
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.275
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_FlowSwitch
IVT AirX air-to-water heat pump[175]5451Heating-water flow too low during defrost, so the outdoor coil cannot be defrosted safely.
IVT AirX air-to-water heat pump[175]5252Water flow between outdoor and indoor unit is restricted (detected by the heat pump, not a flow switch); check the filter.
IVT AirX air-to-water heat pump[175]5594Air in the heating system; vent it, open the thermostats and clean the filter.
IVT AirSplit 200/300 split air-to-water heat pump[176]5252Water flow between outdoor and indoor unit is restricted (detected by the heat pump, not a flow switch); check the filter.
IVT AirSplit 200/300 split air-to-water heat pump[176]5451Heating-water flow too low during defrost; heating water may also be too cold.
IVT AirSplit 200/300 split air-to-water heat pump[176]5594Air in the heating system; vent it, open the thermostats and clean the filter.
IVT Geo 500/600 series ground source heat pump[177]5252Heating-medium temperature difference above 13 K in heating or 7 K in cooling, meaning too little flow (closed thermostats, dirty return filter).
IVT Geo 500/600 series ground source heat pump[177]5563Brine temperature difference TB0-TB1 too large, meaning too little brine flow: clogged strainer or air in the collector (warning).
IVT Geo 500/600 series ground source heat pump[177]5565Brine temperature difference TB0-TB1 too large, meaning too little brine flow: clogged strainer or air in the collector (alarm).
IVT Geo 500/600 series ground source heat pump[177]5594Air in the system or a flow problem on the heating side.
IVT Geo 500/600 series ground source heat pump[177]5918Flow through circulation pump PC0 too low; check, vent and fill the heating system.
IVT Geo 312/412 ground source heat pump[178]5252Heating-medium temperature difference above 13 K in heating or 7 K in cooling, meaning too little flow (closed thermostats, dirty return filter).
IVT Geo 312/412 ground source heat pump[178]5563Brine temperature difference TB0-TB1 too large, meaning too little brine flow: clogged strainer or air in the collector (warning).
IVT Geo 312/412 ground source heat pump[178]5565Brine temperature difference TB0-TB1 too large, meaning too little brine flow: clogged strainer or air in the collector (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5252Water flow between outdoor and indoor unit is restricted (detected by the heat pump, not a flow switch); check the filter.
IVT Vent 202/302/402 exhaust air heat pump[179]5451Heating-water flow too low during defrost; heating water may also be too cold.
IVT Vent 202/302/402 exhaust air heat pump[179]5594Air in the heating system; vent it, open the thermostats and clean the filter.

The flow switch on the water or brine side signals too little flow, and the unit stops so that the evaporator does not freeze.

Check: Check pump, strainer, valves and air in the circuit before resetting.

Water or brine pump fault

ControllerCode
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.277
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.788
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.820
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_PumpmFault
BAC TrilliumSeries adiabatic cooler TRF[174]1
BAC TrilliumSeries adiabatic cooler TRF[174]2
BAC TrilliumSeries adiabatic cooler TRF[174]3
BAC TrilliumSeries adiabatic cooler TRF[174]4
IVT AirX air-to-water heat pump[175]5285Frost risk in the heating system because circulation pump PC0 has no supply voltage.
IVT AirSplit 200/300 split air-to-water heat pump[176]5285Frost risk in the heating system because circulation pump PC0 has no supply voltage.
IVT Geo 500/600 series ground source heat pump[177]5567Brine pump PB3 reports an internal fault; a clogged strainer or air in the brine can also cause it (warning).
IVT Geo 500/600 series ground source heat pump[177]5569Brine pump PB3 reports an internal fault; a clogged strainer or air in the brine can also cause it (alarm).
IVT Geo 500/600 series ground source heat pump[177]5917No communication with heating circuit pump PC0.
IVT Geo 500/600 series ground source heat pump[177]5919Circulation pump PC0 is blocked; check the particle filter and the water quality.
IVT Geo 500/600 series ground source heat pump[177]5921Internal fault in circulation pump PC0; switch its supply off and on.
IVT Geo 500/600 series ground source heat pump[177]5938The electronics of pump PC0 are too hot because the plant room is above 35 °C.
IVT Geo 312/412 ground source heat pump[178]5567Brine pump PB3 reports an internal fault; a clogged strainer or air in the brine can also cause it (warning).
IVT Geo 312/412 ground source heat pump[178]5569Brine pump PB3 reports an internal fault; a clogged strainer or air in the brine can also cause it (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5285Frost risk in the heating system because circulation pump PC0 has no supply voltage.

The circulation or spray water pump does not run as commanded: its electronics report a fault, it draws no current, it does not answer the controller, or it has been locked out after repeated failures.

Check: Check supply and fuse to the pump, the signal cable, that the pump turns freely and is not running dry or air-locked, and that the valves on the water side are open.

Water or brine pressure too low

ControllerCode
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]M.32
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.022
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol filling pressure flashingHeating circuit filling pressure is outside the permitted range. (The manual does not give the colour.)
IVT Geo 500/600 series ground source heat pump[177]5276Brine (collector) pressure too low.
IVT Geo 500/600 series ground source heat pump[177]5923Circulation pump PC0 runs dry: fill and vent the heating circuit and check the filter.
IVT Geo 500/600 series ground source heat pump[177]5940Air in circulation pump PC0: fill and vent the heating circuit.
IVT Geo 500/600 series ground source heat pump[177]5994Low brine pressure.
IVT Geo 312/412 ground source heat pump[178]5276Brine (collector) pressure too low.

The pressure in the heating, cooling or brine circuit has fallen below the minimum, usually from a leak, air in the system or a too small expansion vessel, so the unit stops to protect the pump and heat exchanger.

Check: Read the system pressure, top up and bleed the circuit, look for leaks and check the expansion vessel pre-charge and the pressure sensor.

Antifreeze alarm

ControllerCode
Carel ir33[11]AFr
Carel ir33+ VCC[20]AFr
Carel SmartCella / SmartCella 3PH[24]AFr
Danfoss EKE 1A/1B/1C/1D[43]A994
Danfoss EKE 100[44]A30
Carel µC2SE for process chiller[59]A1
Carel µChiller[60]A28
Daikin RA / SkyAir / VRV (malfunction codes)[75]A5
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]BRINE OUT
LG Multi V 5 VRF outdoor units[77]CH187
NIBE F1255 ground source heat pump[78]60
NIBE F1255 ground source heat pump[78]160
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]LEAVING BRINE TEMPERATURE LOW
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]ENTERING BRINE TEMPERATURE LOW
Evco EV3 HP / EVD HP (heat pump)[110]AFr1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AFr
Evco EV3 MVC / EVD MVC (air handling)[112]AL05
Hitachi multi-split heat pump[113]13
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A04
Carel iJF with VCC (Hillphoenix SMD-H)[161]AFr
Copeland (CPC) E2 RX/BX/CX controller[163]A FreezeStat Input Is Too Low
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]E09
IVT AirX air-to-water heat pump[175]5375Freeze protection of the condenser (water side) has stopped the unit, usually because of poor circulation to the heat pump.
IVT AirX air-to-water heat pump[175]5374Frost risk in the condenser from poor water flow; check balancing valves, thermostats, filter, air and system pressure.
IVT AirX air-to-water heat pump[175]5444Frost protection active; check water circulation and that the outdoor fan is not blocked by snow, ice or objects, then run the outdoor unit test.
IVT AirSplit 200/300 split air-to-water heat pump[176]5374Frost risk in the condenser from poor water flow; check balancing valves, thermostats, filter, air and system pressure.
IVT AirSplit 200/300 split air-to-water heat pump[176]5375Frost risk in the condenser (alarm); check balancing valves, thermostats, filter, air and system pressure.
IVT AirSplit 200/300 split air-to-water heat pump[176]5444Frost protection active; check water circulation and that the outdoor fan is not blocked by snow, ice or objects, then run the outdoor unit test.
IVT Geo 500/600 series ground source heat pump[177]5285Freeze protection: T0, TC1 or TC0 has been below 5 °C for 10 min.
IVT Geo 500/600 series ground source heat pump[177]5374Condenser freeze protection warning: poor or no circulation in the heating system.
IVT Geo 500/600 series ground source heat pump[177]5375Condenser freeze protection alarm: poor or no circulation in the heating system.
IVT Geo 312/412 ground source heat pump[178]5285Freeze protection: T0, TC1 or TC0 has been below 5 °C for 10 min.
IVT Geo 312/412 ground source heat pump[178]5374Condenser freeze protection warning: poor or no circulation in the heating system.
IVT Geo 312/412 ground source heat pump[178]5375Condenser freeze protection alarm: poor or no circulation in the heating system.
IVT Vent 202/302/402 exhaust air heat pump[179]5374Frost risk in the condenser from poor water flow; check balancing valves, thermostats, filter, air and system pressure.
IVT Vent 202/302/402 exhaust air heat pump[179]5375Frost risk in the condenser (alarm); check balancing valves, thermostats, filter, air and system pressure.
IVT Vent 202/302/402 exhaust air heat pump[179]5444Frost protection active; check water circulation and that the outdoor fan is not blocked by snow, ice or objects, then run the outdoor unit test.

A probe set up as antifreeze probe has measured a temperature below the antifreeze limit, and the compressor is stopped until the alarm is reset by hand.

Check: Check flow and temperature on the evaporator side (water or brine flow, frosted coil, low load), and the probe and its limit setting, before resetting.

Liquid level

ControllerCode
Carel pRack pR300[22]ALB05
Carel pRack pR300T (transcritical CO2)[23]ALB05
Carel µRack[25]A09
Dixell XC645D[48]A5
NIBE F1255 ground source heat pump[78]53
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]CHILLER LIQUID LEVEL LOW
RDM Intuitive Superpack / Transcritical Superpack[132]Lh 1–Lh 3
RDM Intuitive Superpack / Transcritical Superpack[132]LL 1–LL 3
Taylor 736 soft serve freezer[153]FLU.LEV.
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_WaterLowLvl
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_WaterHighLvl
BAC TrilliumSeries adiabatic cooler TRF[174]6
BAC TrilliumSeries adiabatic cooler TRF[174]7
BAC TrilliumSeries adiabatic cooler TRF[174]15
BAC TrilliumSeries adiabatic cooler TRF[174]16

A liquid level in a separator or vessel is outside its limits.

Check: Check the level sensor against the sight glass, the level control valve and the charge.

Mix low or mix out

ControllerCode
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]MIX LOW FAILURE
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]MIX OUT FAILURE
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]ML
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]MO
Taylor Icetro ISI-161TH/ISI-161TI[154]Er00
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er00
Taylor 736 soft serve freezer[153]MIX LOW iconMix level in the hopper is low; refill soon. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]MIX OUT iconHopper almost empty; Auto is locked out and the freezer goes to Standby until mix is added. (The manual does not give the colour.)
Taylor Icetro ISI-161TH/ISI-161TI[154]MIX-LOW light blinkingThe mix level in the hopper is running low; add mix. (The manual does not give the colour.)
Taylor Icetro ISI-161TH/ISI-161TI[154]MIX-LOW light steadyThe hopper is out of mix. (The manual does not give the colour.)
Taylor R280 fry dispenser[158]Display blinking oLow fry level warning: too little product in the hopper to reach the target weight. (The manual does not give the colour.)
Taylor R280 fry dispenser[158]Empty hopper light flashingThe hopper is empty or the target weight cannot be reached (also scale obstruction, calibration or bridged fries); the unselected basket LEDs flash too and dispensing stops. (The manual does not give the colour.)
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Mix Low light onMix hopper is low; refill soon. (The manual does not give the colour.)
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Mix Out light onHopper nearly empty; Auto is locked out and the freezer goes to Standby. (The manual does not give the colour.)
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]MIX LOW lamp flashingMix is low; portions may be small. Refill. (The manual does not give the colour.)
Carpigiani AES PSP[15]Tank level LED 1/2 onMix in that tank is at minimum; about 10 portions left before the machine goes to storage. (The manual does not give the colour.)
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]Mix Low light onMix hopper is low; refill soon. (The manual does not give the colour.)
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]Mix Out light onMix hopper is almost empty; Auto is locked out and the freezer goes to Standby until mix is added and Auto pressed. (The manual does not give the colour.)

The level sensor in the hopper reports too little mix (or none), so the machine stops freezing or will not run a heat treatment cycle.

Check: Refill the hopper; check the mix level probe, the feed tube and that the hopper is clean and correctly assembled.

Heat treatment cycle failed

ControllerCode
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HEAT MODE FAILURE
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]COOL MODE FAILURE
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]TOTAL TIME FAILURE
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]POWER FAIL IN H/C
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HT
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]CL
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]TT
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]PF
Taylor Icetro ISI-161TH/ISI-161TI[154]Er17
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er17

The heat treatment (pasteurising) cycle of a soft serve or shake freezer did not heat the mix high enough, cool it down again or finish within its time limits, for example after a power cut, a beater or pressure fault or too little mix, so the machine locks the product.

Check: Read the failure code and history in the service menu; check mix level, heaters, thermistors, refrigeration during the cool phase and the power supply, and handle the mix as the food safety rules require.

Water, CO2 or syrup supply low

ControllerCode
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]H2O PRESSURE LOW
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]CO2 PRESSURE LOW
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]SYRUP PRESS LOW
Taylor C392/C393/C394 frozen beverage freezers[150]H2O Low
Taylor C392/C393/C394 frozen beverage freezers[150]CO2 Low
Taylor C392/C393/C394 frozen beverage freezers[150]Syrup Out
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]Product light steadySyrup, water or CO2 is OUT for that barrel; refrigeration stops after the delay. (The manual does not give the colour.)
Taylor R200 fry dispenser[157]Display Hopper Empty flashingHopper empty: target weight not reached, dispensing stopped. (The manual does not give the colour.)

A frozen beverage machine has detected too low pressure in the incoming water, CO2 or syrup supply, so it stops or holds the freezing cylinders to protect the product and the cylinder.

Check: Check the water supply and pump, the CO2 bottle and regulator, syrup containers and lines, and the pressure switches.

Ice machine water system fault

ControllerCode
True Ice TI/TCIM ice machines[147]E24
True Ice TI/TCIM ice machines[147]E25
True Ice TI/TCIM ice machines[147]E27
True Ice TI/TCIM ice machines[147]E28
True Ice TI/TCIM ice machines[147]E29
True Ice TI/TCIM ice machines[147]H₂O

The water side of an ice machine does not behave as expected: the sump fills or drains too slowly, water is lost, or the water pump does not move water, so the freeze and harvest cycle is stopped.

Check: Check water supply pressure and inlet filter, inlet and purge valves, the water level sensor and its tube, the pump and leaks around the sump and distributor.

Refrigerant pump differential pressure out of range

ControllerCode
Hussmann pumped liquid CO2 secondary system (E2 rack controller alarms)[88]LOW PUMP DIFFERENTIAL PRESSURE SHUT DOWN

The pressure rise across the liquid pump of a pumped (secondary) CO2 or ammonia system has stayed too low or too high for longer than the delay, so the controller stops the pump and tries again after a pause; after repeated stops it locks out.

Check: Check the liquid level in the receiver or separator and the subcooling at the pump inlet (too little gives cavitation), that the suction strainer and valves are open, the pump rotation and the two pressure transmitters across the pump. A very high difference points to closed branch valves or a blocked supply line.

Refrigerant leak or gas detector alarm

ControllerCode
Carel Heos[18]LCA
Carel pRack pR300T (transcritical CO2)[23]ALC51
Carel pRack pR300T (transcritical CO2)[23]ALC52
Copeland EazyCool ZX (XCM25D)[5]E48
Copeland Large ZX 22–30 HP[29]E47
Copeland Large ZX 22–30 HP[29]E48
Danfoss AK-CC 550 / 550B[33]AA2
Danfoss AK-CC 550 / 550B[33]AA3
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]AA2
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]AA3
Danfoss AK-CC55 Water Loop[35]AA3
Danfoss EIM 365[40]LOC Alarm
Danfoss Gas Sensor DGS[71]LED red flashing
Danfoss Gas Sensor DGS[71]A!
Danfoss Gas Sensor DGS[71]Overrange
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]A!
Daikin RA / SkyAir / VRV (malfunction codes)[75]U0
LG Multi V 5 VRF outdoor units[77]CH230
Heatcraft A2L Refrigerant Detection System (unit coolers)[79]LED yellow/white flashing
Heatcraft A2L Refrigerant Detection System (unit coolers)[79]LED red/white flashing
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]Refrigerant Loss
Hussmann transcritical CO2 rack (rack controller alarms)[87]Rack Leak Detector
Hussmann pumped liquid CO2 secondary system (E2 rack controller alarms)[88]CO2 LEAKAGE ALARM
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]P8
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]J30
Carel iJF with VCC (Hillphoenix SMD-H)[161]rSF
HTPG EcoNet enabled unit coolers[162]A004
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]LEA
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Ln1
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Ln2
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]LrE
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display CO2 flashingRefrigerant leak alarm (only when the refrigerant is set to CO2). (The manual does not give the colour.)
Danfoss Gas Sensor DGS[71]LED red slow flashingGas level above the warning threshold.
Danfoss Gas Sensor DGS[71]LED red fast flashingGas level above the critical threshold (buzzer on unless acknowledged).
Danfoss Gas Sensor DGS[71]Keypad LED red steadyGas alarm is active.
Danfoss Gas Sensor DGS[71]Display backlight redGas alarm is active (backlight changes from green to red).
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]LED red steadyGas alarm is active; display backlight turns red.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 8 flashesP8 abnormal pipe temperature (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Danfoss sensor LED redRefrigerant at or above the alarm threshold; relay open, liquid solenoid closed, fans on.
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor green blink 2 Hz + alarm 1 redLow refrigerant concentration detected (alarm 1, relay R1 open).
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor green blink 2 Hz + alarm 1 + alarm 2 redHigh concentration: mitigation running, compressors stopped and LLSV/discharge valves closed.
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor green steady + alarm 2 redGas gone but alarm 2 latched; R2 stays open until a manual reset (PM wire to ground for 1 s).

A gas detector or the controller has detected refrigerant in the air or a loss of refrigerant.

Check: Treat it as a real leak until proven otherwise: ventilate, measure with a hand-held detector, find and repair the leak, and check the detector.

Gas detector sensor fault

ControllerCode
Danfoss Gas Sensor DGS[71]LED yellow
Danfoss Gas Sensor DGS[71]Removed
Danfoss Gas Sensor DGS[71]Out of Range
Danfoss Gas Sensor DGS[71]Underrange
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X Sensor Element
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X Overrange
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X Underrange
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X Overtemp.
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]AP 0X Overrange
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]AP Underrange
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]J29
Copeland (CPC) E2 RX/BX/CX controller[163]IRLDS: Line/Filter Flow Fault
Copeland (CPC) E2 RX/BX/CX controller[163]IRLDS: Self-Test Failure
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Li1
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Li2
Danfoss Gas Sensor DGS[71]Keypad LED yellow steadyFault present; read the error list.
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor alarm 2/fault red onlySensor malfunction detected (analogue output about 2.9 V / above 19 mA); manual reset needed.

The gas detector cannot measure reliably: the sensor head is missing, damaged, worn out or of the wrong type, or its signal is outside the range it should give, so a leak may go undetected.

Check: Check the cable and plug between sensor head and detector board, and that the gas type and range match the detector setup. Look for direct sun, heat or moisture at the sensor. Recalibrate or bump test with reference gas; if the fault returns, replace the sensor head. Until then, treat the room as unmonitored.

Refrigerant charge wrong

ControllerCode
Mitsubishi Electric City Multi (M-NET error codes)[102]1500
Mitsubishi Electric City Multi (M-NET error codes)[102]1501
Goodman DX20VC inverter condensing unit[105]E41
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P15
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P15
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A09
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A26
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EL 0C
ActronAir Nexus Touch Controller WTC-01[139]EC
ActronAir UltraSlim 2 ducted split system[140]EF
alpha innotec BWP 190S/260S DHW heat pump[168]Er7
alpha innotec BWP 190S/260S DHW heat pump[168]Er9
alpha innotec WWB 190 DHW heat pump[169]E9
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 8, timer offRefrigerant leak detected (EL 0C). (The manual does not give the colour.)
IVT AirX air-to-water heat pump[175]5448Too little refrigerant in the circuit.
IVT AirX air-to-water heat pump[175]5527Too much refrigerant in the circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5448Too little refrigerant in the circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5527Too much refrigerant in the circuit.
IVT Geo 500/600 series ground source heat pump[177]5448Too little refrigerant in the heat pump.
IVT Geo 500/600 series ground source heat pump[177]5527Too much refrigerant in the heat pump.
IVT Geo 500/600 series ground source heat pump[177]5984No or almost no refrigerant left in the circuit.
IVT Geo 312/412 ground source heat pump[178]5448Too little refrigerant in the heat pump.
IVT Geo 312/412 ground source heat pump[178]5527Too much refrigerant in the heat pump.
IVT Vent 202/302/402 exhaust air heat pump[179]5448Too little refrigerant in the circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5527Too much refrigerant in the circuit.

The unit compares its pressures, temperatures and valve positions and concludes that the system holds clearly too much or too little refrigerant, and limits or stops the compressor.

Check: Check subcooling and superheat against the manufacturer's charging chart, look for oil traces and leak test the joints if the charge is low. If it looks overcharged, check first for blocked condenser air flow, a closed service valve or non-condensables before removing refrigerant; weigh in the charge after any repair.

Leakage input outside its limit

ControllerCode
Kriwan INT69 F Diagnose[94]LED red 4 / orange 1
Kriwan INT69 PYF Diagnose[95]LED red 4 / orange 1
Kriwan INT69 YF Diagnose[98]LED red 4 / orange 1
Kriwan INT69 YF Diagnose[98]LED red 4 / orange 3
Kriwan INT69 F Diagnose[94]LED green 4 / orange 1Warning: the leakage input is outside its permitted limit.
Kriwan INT69 YF Diagnose[98]LED green 4 / orange 1Warning: leakage input 1 is outside its permitted limit.
Kriwan INT69 YF Diagnose[98]LED green 4 / orange 3Warning: leakage input 2 is outside its permitted limit.

The resistance measured between the leakage electrodes (or the leakage switch) of a protection relay is outside the set limits, which usually means liquid or dirt has reached the electrodes, or the electrode wiring is damaged.

Check: Look for liquid (water, oil, condensate) where the electrodes sit, dry and clean them, check the cable for damage or a short, and compare the limits set in the relay with the measured value.

Fan motor protection

ControllerCode
Carel pRack pR300[22]ALB07
Carel pRack pR300[22]ALF01
Carel pRack pR300T (transcritical CO2)[23]ALB07
Carel µRack[25]A22
Carel µRack[25]A26
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A34
Danfoss AK-PC 781A[37]Fan Alarm x
Danfoss AK-PC 782A/782B[38]Fan Alarm x
Danfoss Optyma iCO2[46]A34
Dixell XC645D[48]InF
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]BLK
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]FB
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]TFM
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]TM_high
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]n_Limit
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]n_Low
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]Brake
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 6
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 8
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 9
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 5
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 10
Daikin RA / SkyAir / VRV (malfunction codes)[75]E7
LG Multi V 5 VRF outdoor units[77]CH67
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]2 flashes
AHT electronic controller (plug-in cases, standard)[82]FU2
Hussmann transcritical CO2 rack (rack controller alarms)[87]Gas Cooler Fan Alarm
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]EF
Temperzone UC8 unit controller[100]F10
Temperzone UC8 unit controller[100]F11
Temperzone UC7 unit controller[101]F10
Temperzone UC7 unit controller[101]F11
Mitsubishi Electric City Multi (M-NET error codes)[102]4114
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]10 flashes
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U8
Goodman DX20VC inverter condensing unit[105]E19
Goodman DX20VC inverter condensing unit[105]Eb0
Goodman DX20VC inverter condensing unit[105]Eb9
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]VFD Alarm
Evco EV3 HP / EVD HP (heat pump)[110]AtF1
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AF1
Evco EV3 MVC / EVD MVC (air handling)[112]AL09
Evco EV3 MVC / EVD MVC (air handling)[112]AL10
Hitachi multi-split heat pump[113]09
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P12
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P22
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P12
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P22
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]1A
RDM Mercury AC and roof top unit controllers[130]Fan 1 Fault
RDM Mercury AC and roof top unit controllers[130]Fan 2 Fault
RDM Intuitive / Mercury pack and condenser controllers[131]Cd
ActronAir Advance / VCC / Genesis 13–17 kW[136]E01
ActronAir Aires and Advance 19–25 kW[137]E1
ActronAir Aires and Advance 19–25 kW[137]E102
ActronAir Aires and Advance 19–25 kW[137]E103
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EH 03
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 07
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 71
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 72
ActronAir Nexus Touch Controller WTC-01[139]E3
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.260
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.718
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]E11
BAC Nexus modular hybrid cooler (NXF controls)[172]AL_FanCritical
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_MotBlocked_EBM_n
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_PhaseFault_EBM_n
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_MotSuperHeating_EBM_n
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_IntCircSuperHeat_EBM_n
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]5 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]3 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]6 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]11 flashes
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]2 flashes
Carel µRack[25]Icon fan + ALARM flashingFan alarm, e.g. fan thermal overload. (The manual does not give the colour.)
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow lit / green litBuilt-in DC fan 1 speed below 60 rpm for 5 s.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow lit / green blinkBuilt-in DC fan 2 speed below 60 rpm for 5 s.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Panel ALARM light (red) onOne or more EC fans have a fault; all fans run at emergency speed (about 40 %).
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 2xMotor temperature management is reducing maximum speed.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 3xHall sensor fault: rotor position not detected; reset power.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 5xMotor blocked; check the fan for obstruction.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 17xMotor overheated; fan stays off until temperature is normal.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 4, timer offIndoor fan speed outside the normal range (EH 03). (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 12, timer offOutdoor fan speed outside the normal range (EC 07). (The manual does not give the colour.)
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 8Warning: braking mode, the fan has been driven backwards at high speed for a long time (e.g. by wind or another fan).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D801+D803 yellow (3 s on / 0.5 s off)Current error: Fan system error (1A).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 8 flashesU8 outdoor fan protection stop (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink Y-on G-onBuilt-in DC fan 1 below 60 rpm for 5 s (red blink, yellow on, green on).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink Y-on G-blinkBuilt-in DC fan 2 below 60 rpm for 5 s (red blink, yellow on, green blink).
IVT AirSplit 200/300 split air-to-water heat pump[176]5670Outdoor unit fan blocked, LG code 67 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5671Outdoor unit fan blocked, LG code 67 (alarm).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 5 + Timer 6Outdoor DC fan motor locked or abnormal current (code 1b): turn the fan by hand and check the motor supply from the PCB.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 6 + Timer 2Indoor fan still at 0 rpm about a minute after start (lock error, code 12): check the motor plug and turn the fan by hand.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 6 + Timer 3Indoor fan runs far below its target speed (speed error, code 12): check the motor, its plug and the fan wheel.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 5 + Timer 6Outdoor fan motor fault (1b).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 6 + Timer 2Indoor fan motor locked (12).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 6 + Timer 3Indoor fan motor speed abnormal (12).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 15 flashesOutdoor fan motor fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]12Indoor fan motor locked or running at the wrong speed.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]1bOutdoor fan motor fault.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E:12Indoor fan failure: check fan and motor.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 14Outdoor fan motor fault.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 6 + Timer blinkingIndoor fan failure.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 6 + Green blinking, test button: Red blinking + Green 2Indoor fan fault group; after the test button: fan motor locked.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 6 + Green blinking, test button: Red blinking + Green 3Indoor fan fault group; after the test button: fan speed wrong.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 15Upper outdoor fan motor fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 16Lower outdoor fan motor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 15 flashesUpper outdoor fan motor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 16 flashesLower outdoor fan motor fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 6 short + Green rapid (B, E, F)Indoor fan failure.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]19The overcurrent relay of the indoor (evaporator) fan motor has tripped: measure the motor current against the relay setting, check belt tension, bearings and duct pressure, then reset the relay by hand.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]F1 57The internal thermostat of outdoor (condenser) fan motor 1 has opened (160 °C off, 130 °C on): check the motor current, bearings, rotation direction and the thermostat circuit.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]F2 57The internal thermostat of outdoor (condenser) fan motor 2 has opened (160 °C off, 130 °C on): check the motor current, bearings, rotation direction and the thermostat circuit.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]51Indoor fan motor error: the fan stays at zero speed, or below about a third of the target, for 1 min. Turn the fan by hand, check the motor plug and windings (DC motor: Vm–GND below 300 kΩ means a shorted motor and PCB), then the PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]51Indoor fan motor error (locked or too slow for 1 min). Check the fan, motor and PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]97Outdoor fan motor 1 error: locked at start (E.97.1), DC undervoltage (E.97.4) or overheated (E.97.5).
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]98Outdoor fan motor 2 error: locked at start (E.98.1) or overheated (E.98.5).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.97.1Outdoor fan motor 1 locked at start: 100 rpm or less 20 s after the start command, 15 times (the compressor stops after every third). Check for objects and that the fan turns by hand, the motor plug and windings, then the drive output on the main PCB (13.6–16.5 V DC).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.97.5Outdoor fan motor 1 temperature abnormal: 220 rpm or less 60 s after the start command, 3 times within 3 h. Check for objects, a blocked coil, high ambient or recirculation, the static pressure setting, then the motor.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.98.1Outdoor fan motor 2 locked at start (same logic and checks as E.97.1).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.98.5Outdoor fan motor 2 temperature abnormal (same logic and checks as E.97.5).
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 5 + Timer 1 + Filter flashing fastIndoor fan motor error (code 51): locked or below a third of the target speed for 1 min. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)

A condenser or evaporator fan motor protection or EC fan fault has tripped.

Check: Check the fan motor, its protection and supply, that the fan turns freely, and any fault code on the EC fan.

Electric auxiliary heater overheat protection

ControllerCode
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]AUX. HEATER
NIBE F1255 ground source heat pump[78]52
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]ArEb
Evco EV3 MVC / EVD MVC (air handling)[112]AL06
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.351
IVT AirX air-to-water heat pump[175]5246Either the heating system pressure has dropped below 0.5 bar or the overheat protector of the electric heater has tripped; check the pressure first, then reset the protector.
IVT AirX air-to-water heat pump[175]5269Electric heater EE too hot, usually from poor water circulation or a dirty filter in the return line.
IVT AirX air-to-water heat pump[175]5272External auxiliary heater EM reports not ready, often because low pressure, air or poor circulation has tripped its protection.
IVT AirSplit 200/300 split air-to-water heat pump[176]5246Either the heating system pressure has dropped below 0.5 bar or the overheat protector of the electric heater has tripped; check the pressure first, then reset the protector.
IVT AirSplit 200/300 split air-to-water heat pump[176]5269Electric heater EE too hot, usually from poor water circulation or a dirty filter in the return line.
IVT AirSplit 200/300 split air-to-water heat pump[176]5272External auxiliary heater EM reports not ready, often because low pressure, air or poor circulation has tripped its protection.
IVT Geo 500/600 series ground source heat pump[177]5246Either the heating system pressure has dropped below 0.5 bar or the overheat protector of the electric heater has tripped; check the pressure first, then reset the protector.
IVT Geo 500/600 series ground source heat pump[177]5269Electric heater cassette EE too hot, usually from poor circulation or a dirty filter in the return line.
IVT Geo 500/600 series ground source heat pump[177]5272External auxiliary heater EM not working: system pressure below 0.5 bar or its overheat protector has tripped.
IVT Geo 312/412 ground source heat pump[178]5246Either the heating system pressure has dropped below 0.5 bar or the overheat protector of the electric heater has tripped; check the pressure first, then reset the protector.
IVT Geo 312/412 ground source heat pump[178]5269Electric heater cassette EE too hot, usually from poor circulation or a dirty filter in the return line.
IVT Geo 312/412 ground source heat pump[178]5272External auxiliary heater EM not working: system pressure below 0.5 bar or its overheat protector has tripped.
IVT Vent 202/302/402 exhaust air heat pump[179]5246Either the heating system pressure has dropped below 0.5 bar or the overheat protector of the electric heater has tripped; check the pressure first, then reset the protector.
IVT Vent 202/302/402 exhaust air heat pump[179]5269Electric heater EE too hot, usually from poor water circulation or a dirty filter in the return line.
IVT Vent 202/302/402 exhaust air heat pump[179]5272External auxiliary heater EM reports not ready, often because low pressure, air or poor circulation has tripped its protection.

The overheat protector (temperature limiter) on the electric immersion or flow heater has tripped, so the auxiliary heat is blocked until it is reset by hand.

Check: Check that water flows through the heater (pump running, valves open, system bled, strainer clean) before resetting the limiter. If it trips again or cannot be reset, check the limiter, its contactor and the heater element.

Control stopped

ControllerCode
Danfoss EKC 202A/B/C[2]A45
Danfoss AK-CC 550A[3]A45
Danfoss Optyma Plus[4]A45
Danfoss AK-CC 450[32]A45
Danfoss AK-CC 550 / 550B[33]A45
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A45
Danfoss AK-CC55 Water Loop[35]A45
Danfoss AK-CC 750[36]Control stopped, MainSwitch=OFF
Danfoss AK-PC 781A[37]Control stopped, MainSwitch=OFF
Danfoss AK-PC 782A/782B[38]Control stopped, MainSwitch=OFF
Danfoss EKC 202D1[41]A45
Danfoss EKC 326A[42]A45
Danfoss EKE 1A/1B/1C/1D[43]W002
Danfoss EKE 100[44]A00
Danfoss ERC 21X[1]A45
Danfoss Optyma iCO2[46]A45
RDM Mercury 3 Twin Coil[92]CASE OFF
Copeland Electronic Unit Controller[116]POF
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]CASE OFF
RDM Intuitive / Mercury pack and condenser controllers[131]Stby
Temperzone UC6 unit controller[135]C
Temperzone UC6 unit controller[135]d
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]1 flashes
Temperzone UC7 unit controller[101]Display flashing dashRemote On/Off input is open; unit is held off until the input is closed to G. (The manual does not give the colour.)
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 1xRun enable missing; add enable signal or jumper.
AHT electronic controller (plug-in cases, standard)[82]Display ---Cooling has been switched off with the STANDBY button. (The manual does not give the colour.)
Danfoss Optyma iCO2[46]Display S10Stopped by the main switch (r12 or external input DI2).
Full Gauge MT-512E 2HP[120]LED control functions OFF steadyControl functions are switched off; the unit only indicates temperature (display may go dark with only this LED lit). (The manual does not give the colour.)

The controller is in standby: the main switch in the controller (parameter r12) is off, or a digital input stops it.

Check: Check parameter r12 and the digital inputs before troubleshooting further.

External alarm via digital input

ControllerCode
Danfoss Optyma Plus[4]A16
Danfoss Optyma Plus[4]A97
Carel MPX[6]IA
Carel MasterCella[7]IA
Dixell XW270L/XW271L[9]EAL
Zanotti GM/GS[10]EA
Carel ir33[11]IA
Carel ir33[11]dA
Dixell XR60CX[12]EA
Dixell XR60CX[12]CA
Eliwell ID 974[13]EA
Danfoss VLT FC 103[14]W60
Danfoss VLT FC 103[14]A68
Carel Heos[18]IA
Carel Heos[18]dA
Carel ir33 universale[19]E03
Carel ir33 universale[19]E17
Carel ir33 universale[19]E18
Carel ir33 universale[19]Ed1
Carel ir33 universale[19]Ed2
Carel ir33+ VCC[20]IA
Carel ir33+ VCC[20]dA
Carel MPXone[21]IA
Carel MPXone[21]dA
Carel SmartCella / SmartCella 3PH[24]IA
Carel SmartCella / SmartCella 3PH[24]dA
Danfoss AK-CC 450[32]A15
Danfoss AK-CC 450[32]A16
Danfoss AK-CC 550 / 550B[33]A15
Danfoss AK-CC 550 / 550B[33]A16
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A15
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A16
Danfoss AK-CC55 Water Loop[35]A15
Danfoss AK-CC55 Water Loop[35]A16
Danfoss AK-CC55 Water Loop[35]A93
Danfoss Optyma control AK-RC 113[39]E8
Danfoss EKC 202D1[41]A15
Danfoss EKC 202D1[41]A16
Danfoss EKC 202A/B/C[2]A15
Danfoss ERC 21X[1]A15
Danfoss AK-RC 251[47]AE
Danfoss AK-RC 251[47]AES
Dixell XC645D[48]EA
Dixell XM669K/XM679K[50]EA
Dixell XM669K/XM679K[50]CA
Dixell XR06CX[51]EA
Dixell XR06CX[51]CA
Dixell XR35CX[52]EA
Dixell XR35CX[52]CA
Dixell XR460C[53]EAL
Dixell XR460C[53]bAL
Dixell XR70CX[54]EA
Dixell XR70CX[54]CA
Dixell XW60K/XW60L[55]EA
Dixell XW60K/XW60L[55]CA
Dixell XWi70K[56]EA
Dixell XWi70K[56]CA
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]27
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]STO-F
Carel µC2SE for process chiller[59]Ad1
Carel µChiller[60]A03
Danfoss VLT HVAC Basic Drive FC 101[70]A60
Secop SLV controller 105N46xx[81]A15
Pego ECP200 EXPERT PULSE[89]E8
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]E8
RDM DMTouch / miniDM[91]Plant Fault
RDM Mercury 3 Twin Coil[92]TrAP
RDM Mercury 3 Twin Coil[92]Plt 1
RDM Mercury 3 Twin Coil[92]Plt 2
RDM Mercury 3 Twin Coil[92]Plt 3
RDM Mercury 3 Twin Coil[92]Plt 4
Kriwan INT69 PYF Diagnose[95]LED red 4 / orange 3
Kriwan INT69 PYF Diagnose[95]LED red 5 / orange 3
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]EMERGENCY STOP
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]INTERLOCK
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]PA
Evco EV3203[107]iA
Evco EV3 300 series[108]iA
Evco EVK214[109]iSd
Full Gauge TC-900E POWER / TC-900E 2HP[117]ALrE
Full Gauge TC-900E Log[118]ALrE
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]L30
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]L30
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]TrAP
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Man TrAP
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Plt1
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Plt2
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Plt3
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Plt4
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]PLnt
RDM Mercury / Intuitive Mercury thermostats and monitors[129]PLt1–PLt6
RDM Intuitive / Mercury pack and condenser controllers[131]gn
RDM Intuitive / Mercury pack and condenser controllers[131]gEn 1–gEn 5
RDM Intuitive / Mercury pack and condenser controllers[131]Stage 1 LED flashing
RDM Intuitive / Mercury pack and condenser controllers[131]Stage 2 LED flashing
RDM Intuitive / Mercury pack and condenser controllers[131]Stage 3 LED flashing
RDM Intuitive Superpack / Transcritical Superpack[132]gn 1–gn 16
RDM Intuitive Superpack / Transcritical Superpack[132]PLt 1–PLt 16
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EH 0E
ActronAir Nexus Touch Controller WTC-01[139]EE
ActronAir UltraSlim 2 ducted split system[140]EE
Dixell XR/XW (True cabinets)[145]EAL
Dixell XR/XW (True cabinets)[145]BAL
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]EA
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]CA
Carel MPXzero (Hillphoenix display cases)[160]IA
Carel MPXzero (Hillphoenix display cases)[160]dA
Carel iJF with VCC (Hillphoenix SMD-H)[161]IA
Carel iJF with VCC (Hillphoenix SMD-H)[161]dA
Pego 202BASE electronic board[167]E8
BAC TrilliumSeries adiabatic cooler TRF[174]14
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]ALr
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow lit / green darkSTO (safe torque off) interface disconnected.
Carel ir33[11]Icon alarm steadyDelayed external alarm input is active but its delay (A7) has not yet run out. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Alarm icon steadyDelayed alarm from a digital input is active. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-blink Y-onSTO (safe torque off) interface disconnected after start-up (red blink, yellow on, green off).
Fujitsu AIRSTAGE J-II VRF – external switch controller UTY-TEKX (LED)[203]LED on, SW1/SW2 no effectUTY-TEKX: switch input not detected. Check cable, DIP switches and the external switch (open >50 kΩ, closed <1 kΩ). (The manual does not give the colour.)
Carel MasterCella[7]Alarm icon steadyDelayed external digital-input alarm is pending, before its delay A7 runs out. (The manual does not give the colour.)
Carel ir33+ VCC[20]Alarm icon steadyA delayed alarm from a digital input is active. (The manual does not give the colour.)

A digital input (for example a safety chain, a pressure switch or an alarm from other equipment) has been activated. Some alarms stop the control.

Check: Find out what is connected to the input and fix the cause. Check the input setting in the controller.

Air sensor fault

ControllerCode
Danfoss ERC 21X[1]E29
Danfoss EKC 202A/B/C[2]E29
Carel MPX[6]rE
Carel MPX[6]E0
Carel MasterCella[7]E0
Dixell XW270L/XW271L[9]P1
Zanotti GM/GS[10]E1
Carel ir33[11]rE
Carel ir33[11]E0
Dixell XR60CX[12]P1
Eliwell ID 974[13]E1
Carel Heos[18]rE
Carel ir33 universale[19]E01
Carel ir33+ VCC[20]rE
Carel ir33+ VCC[20]E0
Carel MPXone[21]rE
Carel SmartCella / SmartCella 3PH[24]rE
Carel SmartCella / SmartCella 3PH[24]E0
Heatcraft Beacon II[30]E1
Heatcraft Beacon II[30]BXSEN
Danfoss AK-CC 450[32]E25
Danfoss AK-CC 450[32]E26
Danfoss AK-CC 450[32]E34
Danfoss AK-CC 550 / 550B[33]E25
Danfoss AK-CC 550 / 550B[33]E26
Danfoss AK-CC 550 / 550B[33]E34
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E25
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E26
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E34
Danfoss AK-CC55 Water Loop[35]E25
Danfoss AK-CC55 Water Loop[35]E26
Danfoss AK-CC 750[36]S3A sensor error
Danfoss AK-CC 750[36]S4A sensor error
Danfoss Optyma control AK-RC 113[39]E0
Danfoss EKC 202D1[41]E25
Danfoss EKC 202D1[41]E26
Danfoss AK-RC 251[47]E1
Dixell XM669K/XM679K[50]P1
Dixell XR06CX[51]P1
Dixell XR35CX[52]P1
Dixell XR460C[53]P1
Dixell XR460C[53]P2
Dixell XR70CX[54]P1
Dixell XW60K/XW60L[55]P1
Dixell XWi70K[56]P1
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]OUTDOOR SENSOR
LG Multi V 5 VRF outdoor units[77]CH44
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]6 flashes
Secop SLV controller 105N46xx[81]E25
Secop SLV controller 105N46xx[81]E26
AHT electronic controller (plug-in cases, standard)[82]F1
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]F1
AHT GD-Cooler (GD-XLS, GD-XL)[84]P1
AHT plug-in cases with Danfoss controller (Paris, Ibiza, Malta, Manhattan)[85]E01
AHT plug-in cases with Danfoss controller (Paris, Ibiza, Malta, Manhattan)[85]E02
Pego ECP200 EXPERT PULSE[89]E0
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]E0
RDM Mercury 3 Twin Coil[92]Prb1 Ft
RDM Mercury 3 Twin Coil[92]Prb2 Ft
Störk-Tronic ST121 / ST501 / ST551[93]E1L
Störk-Tronic ST121 / ST501 / ST551[93]E1H
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]P1
Evco EV3203[107]Pr1
Evco EV3 300 series[108]Pr1
Evco EVK214[109]Pr1
Hitachi multi-split heat pump[113]11
Thermia Atella / Robust[114]ROOM SENSOR
Full Gauge TC-900E POWER / TC-900E 2HP[117]Err1
Full Gauge TC-900E Log[118]Err1
Full Gauge TC-940R[119]Er1
Full Gauge MT-512E 2HP[120]Er1
Full Gauge MT-512E Log[121]Err1
Full Gauge MT-514E Faston[122]Err1
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]F10
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb1
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb2
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Prb
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Prb 1–Prb 5
RDM Mercury AC and roof top unit controllers[130]Probe 1
RDM Mercury AC and roof top unit controllers[130]Probe 2
RDM Mercury AC and roof top unit controllers[130]Prb Flt
ActronAir Advance / VCC / Genesis 13–17 kW[136]E03
ActronAir Aires and Advance 19–25 kW[137]E3
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EH 60
ActronAir Nexus Touch Controller WTC-01[139]E4
ActronAir UltraSlim 2 ducted split system[140]E2
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]E01
Danfoss ETC (True cabinets)[142]E1
Danfoss EETa (True cabinets, LED blink codes)[143]2+1 flashes
Carel PQ (True cabinets)[144]E0
Dixell XR/XW (True cabinets)[145]P1
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]E1
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]E1
Taylor R160 frozen food dispenser[156]P1
Taylor R200 fry dispenser[157]Error 8
Taylor R280 fry dispenser[158]Err 8
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]P1
Carel MPXzero (Hillphoenix display cases)[160]rE
Carel MPXzero (Hillphoenix display cases)[160]E1
Carel MPXzero (Hillphoenix display cases)[160]E3
Carel iJF with VCC (Hillphoenix SMD-H)[161]rE
HTPG EcoNet enabled unit coolers[162]A103
LAE AT1-5/AT2-5[166]E1
Pego 202BASE electronic board[167]E0
alpha innotec BWP 190S/260S DHW heat pump[168]Er1
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P04
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]E1
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 6, timer offIndoor sensor T1 (EH 60) or T2 (EH 61) open or short circuit. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display ErrThe temperature cannot be shown because of a sensor fault. (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 1 flashP1 intake (room) sensor error (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
IVT AirX air-to-water heat pump[175]1037Outdoor sensor faulty or its cable broken; the unit heats on a fallback value meanwhile.
IVT AirX air-to-water heat pump[175]3091Thermistor in the room unit for heating circuit 1 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirX air-to-water heat pump[175]3092Thermistor in the room unit for heating circuit 2 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirX air-to-water heat pump[175]3093Thermistor in the room unit for heating circuit 3 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirX air-to-water heat pump[175]3094Thermistor in the room unit for heating circuit 4 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirX air-to-water heat pump[175]5201Outdoor sensor T1: open circuit in sensor or cable.
IVT AirX air-to-water heat pump[175]5202Outdoor sensor T1: short circuit in sensor or cable.
IVT AirX air-to-water heat pump[175]5203Outdoor sensor T1 faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5408Air inlet sensor TL2: open circuit.
IVT AirX air-to-water heat pump[175]5409Air inlet sensor TL2: short circuit.
IVT AirX air-to-water heat pump[175]5410Air inlet sensor TL2 faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]1037Outdoor sensor faulty or its cable broken; the unit heats on a fallback value meanwhile.
IVT AirSplit 200/300 split air-to-water heat pump[176]3091Thermistor in the room unit for heating circuit 1 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirSplit 200/300 split air-to-water heat pump[176]3092Thermistor in the room unit for heating circuit 2 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirSplit 200/300 split air-to-water heat pump[176]3093Thermistor in the room unit for heating circuit 3 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirSplit 200/300 split air-to-water heat pump[176]3094Thermistor in the room unit for heating circuit 4 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT AirSplit 200/300 split air-to-water heat pump[176]5201Outdoor sensor T1: open circuit in sensor or cable.
IVT AirSplit 200/300 split air-to-water heat pump[176]5202Outdoor sensor T1: short circuit in sensor or cable.
IVT AirSplit 200/300 split air-to-water heat pump[176]5203Outdoor sensor T1 faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5395Air inlet sensor TL2: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5408Air inlet sensor TL2: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5409Air inlet sensor TL2: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5410Air inlet sensor TL2 faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5624Outdoor unit air temperature sensor TL2 fault, LG code 44 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5625Outdoor unit air temperature sensor TL2 fault, LG code 44 (alarm).
IVT Geo 500/600 series ground source heat pump[177]3091Thermistor in the room unit (RC100/CR10) for heating circuit 1 is faulty while the bus works.
IVT Geo 500/600 series ground source heat pump[177]3092Thermistor in the room unit (RC100/CR10) for heating circuit 2 is faulty while the bus works.
IVT Geo 500/600 series ground source heat pump[177]3093Thermistor in the room unit (RC100/CR10) for heating circuit 3 is faulty while the bus works.
IVT Geo 500/600 series ground source heat pump[177]3094Thermistor in the room unit (RC100/CR10) for heating circuit 4 is faulty while the bus works.
IVT Geo 500/600 series ground source heat pump[177]3171Low battery in the wireless room sensor for heating circuit 1; replace the battery.
IVT Geo 500/600 series ground source heat pump[177]5201Outdoor sensor T1: open circuit, or no sensor installed.
IVT Geo 500/600 series ground source heat pump[177]5202Outdoor sensor T1: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5203Outdoor sensor T1 faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]3091Thermistor in the room unit (RC100/CR10) for heating circuit 1 is faulty while the bus works.
IVT Geo 312/412 ground source heat pump[178]3092Thermistor in the room unit (RC100/CR10) for heating circuit 2 is faulty while the bus works.
IVT Geo 312/412 ground source heat pump[178]3093Thermistor in the room unit (RC100/CR10) for heating circuit 3 is faulty while the bus works.
IVT Geo 312/412 ground source heat pump[178]3094Thermistor in the room unit (RC100/CR10) for heating circuit 4 is faulty while the bus works.
IVT Geo 312/412 ground source heat pump[178]5201Outdoor sensor T1: open circuit, or no sensor installed.
IVT Geo 312/412 ground source heat pump[178]5202Outdoor sensor T1: short circuit.
IVT Geo 312/412 ground source heat pump[178]5203Outdoor sensor T1 faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]1037Outdoor sensor faulty or its cable broken; the unit heats on a fallback value meanwhile.
IVT Vent 202/302/402 exhaust air heat pump[179]3091Thermistor in the room unit for heating circuit 1 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT Vent 202/302/402 exhaust air heat pump[179]3092Thermistor in the room unit for heating circuit 2 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT Vent 202/302/402 exhaust air heat pump[179]3093Thermistor in the room unit for heating circuit 3 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT Vent 202/302/402 exhaust air heat pump[179]3094Thermistor in the room unit for heating circuit 4 is faulty while the bus works; a wrongly configured external room sensor gives the same code.
IVT Vent 202/302/402 exhaust air heat pump[179]5201Outdoor sensor T1: open circuit in sensor or cable.
IVT Vent 202/302/402 exhaust air heat pump[179]5202Outdoor sensor T1: short circuit in sensor or cable.
IVT Vent 202/302/402 exhaust air heat pump[179]5203Outdoor sensor T1 faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5395Air inlet sensor TL2: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5408Air inlet sensor TL2: open circuit (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5409Air inlet sensor TL2: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5410Air inlet sensor TL2 faulty (alarm stage).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 2 + Timer 2Room (return air) thermistor open or short circuit (code 02/03): measure the thermistor and its plug.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 3 + Timer 4Outdoor air temperature thermistor open or short circuit (code 0A/0b).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 2 + Timer 2Room thermistor open or short circuit (02/03).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Timer 4Outdoor air thermistor fault (0A/0b).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 4 flashesOutdoor air temperature thermistor fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]02Room (return air) thermistor open circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]03Room (return air) thermistor short circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]0AOutdoor air thermistor open circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]0bOutdoor air thermistor short circuit.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E2:00Return air thermistor open circuit or missing.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E3:00Return air thermistor short circuit.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]EA:00Outdoor ambient thermistor open circuit.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]EB:00Outdoor ambient thermistor short circuit (listed only in the unknown-publisher list).
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 4Outdoor air thermistor open circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 4 + Swing blinkingOutdoor air thermistor short circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 2 + Timer blinkingRoom air thermistor open circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 2 + Timer blinking + Swing blinkingRoom air thermistor short circuit.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 2 + Green blinking, test button: Red blinking + Green 2Indoor sensor fault group; after the test button: room air thermistor.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 2, test button: Red 6 + Green blinkingOutdoor thermistor group; after the test button: outdoor air thermistor.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 4Outdoor air thermistor fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 4Outdoor air thermistor fault.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 4 + LED 2 steadyOutdoor air thermistor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 4 flashesOutdoor air thermistor fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 1 short + Green rapid (G)Room sensor fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 2 short + Green rapidRoom sensor open or failed (groups A, B, D, E, F, G).
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 2 short + Green rapid + Yellow rapid (E, F)Room sensor short circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 3 short + Green long (C)Room sensor fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 4 short (F)Outdoor temperature sensor open circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 4 short + Yellow rapid (F)Outdoor temperature sensor short circuit.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]41Room (return air) thermistor open or short at power-on. Measure it off the board (about 33.6 kΩ at 0 °C, 10 kΩ at 25 °C) and check 5 V DC at its PCB input.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]Thermo sensor indicator flashingWired RC UTY-RNK*: the thermistor built into the remote controller is open or short. Replace the remote controller.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]41Indoor room thermistor fault. Measure it (about 10 kΩ at 25 °C) and its 5 V supply.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]74Outdoor air thermistor TH3 open or short (E.74.1).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.74.1Outdoor air thermistor TH3 open or short. Measure it (thermistor C: about 10 kΩ at 25 °C, 33.6 kΩ at 0 °C) and 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 4 + Timer 1 + Filter flashing fastRoom temperature thermistor error (code 41). Measure it (about 10 kΩ at 25 °C). The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)

The air temperature sensor is faulty, or its connection is broken.

Check: Measure the sensor resistance and compare with the table for the sensor type. Check cable and terminal and replace a faulty sensor.

Lost analog signal (live zero)

ControllerCode
Danfoss VLT FC 103[14]A2
Copeland Digital Compressor Controller[61]5 flashes
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED blue 1
Danfoss VLT HVAC Basic Drive FC 101[70]A2
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]Cable break
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 11
Temperzone UC7 unit controller[101]F32
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_CableBreak_EBM_n
BAC TrilliumSeries adiabatic cooler TRF[174]17
IVT Geo 500/600 series ground source heat pump[177]5980A PWM signal (probably the circulation pump control or feedback) is outside its allowed range.

An analog input (4–20 mA, 0–10 V or a PWM set point) has dropped well below its set minimum, which the drive or fan reads as a broken wire or a dead transmitter or controller output.

Check: Measure the signal at the terminal and check the wiring, the transmitter supply and the controller output; check that the input is set to current or voltage to match the signal and that the low limit is right.

Defrost sensor fault (S5)

ControllerCode
Danfoss ERC 21X[1]E27
Danfoss EKC 202A/B/C[2]E27
Danfoss AK-CC 550A[3]E27
Carel MPX[6]E1
Carel MasterCella[7]E1
Dixell XW270L/XW271L[9]P2
Zanotti GM/GS[10]E2
Carel ir33[11]E1
Dixell XR60CX[12]P2
Eliwell ID 974[13]E2
Carel Heos[18]Eb
Carel ir33+ VCC[20]E1
Carel SmartCella / SmartCella 3PH[24]E1
Heatcraft Beacon II[30]E2
Heatcraft Beacon II[30]DFSEN
Danfoss AK-CC 450[32]E27
Danfoss AK-CC 450[32]E37
Danfoss AK-CC 550 / 550B[33]E27
Danfoss AK-CC 550 / 550B[33]E37
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E27
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E37
Danfoss AK-CC55 Water Loop[35]E27
Danfoss AK-CC 750[36]S5-1A sensor error
Danfoss Optyma control AK-RC 113[39]E1
Danfoss EKC 202D1[41]E27
Danfoss EKC 202D1[41]E37
Danfoss AK-RC 251[47]E2
Dixell XM669K/XM679K[50]P2
Dixell XR06CX[51]P2
Dixell XR35CX[52]P2
Dixell XR460C[53]P3
Dixell XR70CX[54]P2
Dixell XW60K/XW60L[55]P2
Dixell XWi70K[56]P2
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]DEFROST SENSOR
Secop SLV controller 105N46xx[81]E27
AHT electronic controller (plug-in cases, standard)[82]F2
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]F2
AHT GD-Cooler (GD-XLS, GD-XL)[84]P2
Pego ECP200 EXPERT PULSE[89]E1
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]E1
Störk-Tronic ST121 / ST501 / ST551[93]E2L
Störk-Tronic ST121 / ST501 / ST551[93]E2H
Temperzone UC8 unit controller[100]F16
Temperzone UC7 unit controller[101]F16
Goodman DX20VC inverter condensing unit[105]E27
Evco EVK214[109]Pr2
Full Gauge TC-900E POWER / TC-900E 2HP[117]Err2
Full Gauge TC-900E Log[118]Err2
Full Gauge TC-940R[119]Er2
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb5
Temperzone UC8 unit controller[100]F18
Temperzone UC7 unit controller[101]F18
ActronAir Advance / VCC / Genesis 13–17 kW[136]E04
ActronAir Aires and Advance 19–25 kW[137]E4
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EH 61
ActronAir Nexus Touch Controller WTC-01[139]E5
ActronAir UltraSlim 2 ducted split system[140]E3
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]E02
Danfoss ETC (True cabinets)[142]E2
Carel PQ (True cabinets)[144]E1
Dixell XR/XW (True cabinets)[145]P2
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]E2
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]E2
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]P2
Carel MPXzero (Hillphoenix display cases)[160]E2
HTPG EcoNet enabled unit coolers[162]A101
HTPG EcoNet enabled unit coolers[162]A102
LAE AT1-5/AT2-5[166]E2
Pego 202BASE electronic board[167]E1
alpha innotec BWP 190S/260S DHW heat pump[168]Er2
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P05

The sensor on the evaporator is faulty or disconnected. The defrost can then not end on temperature.

Check: Measure the sensor and the cable. Check that the defrost works until the sensor has been replaced.

Suction gas or outlet sensor fault

ControllerCode
Danfoss AK-CC 550A[3]E24
Danfoss Optyma Plus[4]E33
Carpigiani AES PSP[15]AL12
Carpigiani AES PSP[15]AL13
Carel EVD evolution / EVD evolution twin[16]Probe S2
Carel EVD ice / EVD mini[17]A2
Carel Heos[18]EA
Carel MPXone[21]dA2
Carel pRack pR300[22]ALA25
Carel pRack pR300T (transcritical CO2)[23]ALA25
Copeland EXD-SH1/2[26]1E1
Copeland EXD-SH1/2[26]2E1
Heatcraft Beacon II[30]E3
Heatcraft Beacon II[30]STSEN
Sanhua SEC60x[31]toP
Sanhua SEC60x[31]tSt
Danfoss AK-CC 550 / 550B[33]E23
Danfoss AK-CC 550 / 550B[33]E24
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E24
Danfoss AK-CC 750[36]S2A sensor error
Danfoss AK-PC 781A[37]SsA sensor error
Danfoss AK-PC 782A/782B[38]SsA sensor error
Danfoss EIM 365[40]S2 Error
Danfoss EKE 1A/1B/1C/1D[43]E024
Danfoss EKE 1A/1B/1C/1D[43]A981
Danfoss EKE 100[44]A18
Danfoss EKE 100[44]A27
Danfoss Optyma iCO2[46]E33
Dixell XEV12D[49]P1
Dixell XM669K/XM679K[50]P6
Carel µC2SE for process chiller[59]ES1
Carel µChiller[60]A24
Daikin RA / SkyAir / VRV (malfunction codes)[75]C5
Daikin RA / SkyAir / VRV (malfunction codes)[75]J5
LG Multi V 5 VRF outdoor units[77]CH46
Pego ECP200 EXPERT PULSE[89]E4
Temperzone UC8 unit controller[100]F14
Temperzone UC8 unit controller[100]F20
Temperzone UC7 unit controller[101]F14
Temperzone UC7 unit controller[101]F20
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]P2
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]P9
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F01
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F12
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]F01
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]F12
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]18
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb3
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb4
RDM Intuitive Superpack / Transcritical Superpack[132]ShFt
ActronAir Advance / VCC / Genesis 13–17 kW[136]E18
ActronAir Aires and Advance 19–25 kW[137]E18
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 56
ActronAir UltraSlim 2 ducted split system[140]E4
True Ice TI/TCIM ice machines[147]E1
Taylor Icetro ISI-161TH/ISI-161TI[154]Er19
Taylor Icetro ISI-161TH/ISI-161TI[154]Er20
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er19
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er20
HTPG EcoNet enabled unit coolers[162]A100
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.514
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P07
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]E2
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 2 flashesP2/P9 indoor pipe sensor error (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Timer alternate blinking, Ready offIndoor temperature sensor error (TCJ, TC1, TC2, TA, TF; F01–F11). (Ready off.) (The manual does not give the colour.)
IVT AirX air-to-water heat pump[175]5426Suction gas sensor TR5: open circuit.
IVT AirX air-to-water heat pump[175]5427Suction gas sensor TR5: short circuit.
IVT AirX air-to-water heat pump[175]5428Suction gas sensor TR5: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5426Suction gas sensor TR5: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5427Suction gas sensor TR5: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5428Suction gas sensor TR5: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5628Suction gas sensor TR5 fault, LG code 46 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5629Suction gas sensor TR5 fault, LG code 46 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5426Suction gas sensor TR5: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5427Suction gas sensor TR5: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5428Suction gas sensor TR5: faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5426Suction gas sensor TR5: open circuit.
IVT Geo 312/412 ground source heat pump[178]5427Suction gas sensor TR5: short circuit.
IVT Geo 312/412 ground source heat pump[178]5428Suction gas sensor TR5: faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5426Suction gas sensor TR5: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5427Suction gas sensor TR5: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5428Suction gas sensor TR5: faulty (alarm stage).
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]42Indoor heat exchanger thermistor (inlet or outlet) open or short. Measure it off the board (about 168.6 kΩ at 0 °C, 49.8 kΩ at 25 °C) and check 5 V DC at its PCB input.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]42Indoor heat exchanger thermistor fault. Measure it (about 49.8 kΩ at 25 °C) and its 5 V supply.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]75Outdoor suction gas thermistor TH4 open or short (E.75.1).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.75.1Suction gas thermistor TH4 open or short. Measure it (thermistor B: about 16.1 kΩ at 0 °C) and 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 4 + Timer 2 + Filter flashing fastIndoor heat exchanger thermistor error (code 42). Measure it (about 49.8 kΩ at 25 °C). The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)

The temperature sensor at the evaporator outlet or on the suction line is faulty or disconnected, so the superheat cannot be calculated correctly.

Check: Measure the sensor and the cable and check the sensor contact with the pipe. Replace a faulty sensor.

Extra or configurable sensor fault

ControllerCode
Carel ir33[11]E2
Carel ir33[11]E3
Carel ir33[11]E4
Dixell XR60CX[12]P3
Dixell XR60CX[12]P4
Eliwell ID 974[13]E3
Carpigiani AES PSP[15]AL05
Carpigiani AES PSP[15]AL07
Carel EVD evolution / EVD evolution twin[16]Probe S4
Carel ir33 universale[19]E02
Carel ir33+ VCC[20]E2
Carel ir33+ VCC[20]E3
Carel ir33+ VCC[20]E4
Carel MPXone[21]E1
Carel MPXone[21]E2
Carel MPXone[21]E3
Carel MPXone[21]E4
Carel MPXone[21]E5
Carel MPXone[21]E6
Carel pRack pR300[22]ALA01
Carel pRack pR300T (transcritical CO2)[23]ALA43
Carel SmartCella / SmartCella 3PH[24]E2
Carel SmartCella / SmartCella 3PH[24]E3
Carel µRack[25]AB2
Carel µRack[25]AB3
Copeland ZSI scroll condensing units[28]LED1 3 flashes
Copeland EazyCool ZX (XCM25D)[5]E03
Copeland Large ZX 22–30 HP[29]E02
Copeland Large ZX 22–30 HP[29]E03
Heatcraft Beacon II[30]A4
Heatcraft Beacon II[30]E5
Heatcraft Beacon II[30]INFLT
Heatcraft Beacon II[30]ODSEN
Danfoss AK-CC 450[32]E28
Danfoss AK-CC 450[32]E38
Danfoss AK-CC 550 / 550B[33]E28
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E28
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E59
Danfoss AK-CC55 Water Loop[35]E50
Danfoss AK-CC55 Water Loop[35]E65
Danfoss AK-CC 750[36]Product temp. A sensor error
Danfoss AK-PC 781A[37]S4A sensor error
Danfoss AK-PC 782A/782B[38]Sgc sensor error
Danfoss EIM 365[40]S4 Error
Danfoss EKC 326A[42]E15
Danfoss EKC 326A[42]E16
Danfoss EKE 1A/1B/1C/1D[43]E025
Danfoss EKE 1A/1B/1C/1D[43]E026
Danfoss EKE 100[44]A19
Danfoss EKE 100[44]A36
Danfoss ERC 21X[1]E30
Danfoss Optyma Plus[4]E30
Danfoss Optyma Plus[4]E31
Danfoss Optyma Plus[4]E32
Danfoss Optyma Plus Module B Plus (P02)[45]Y1-R3
Danfoss Optyma Plus Module B Plus (P02)[45]Y1-R4
Danfoss Optyma iCO2[46]E20
Danfoss Optyma iCO2[46]E31
Danfoss Optyma iCO2[46]E32
Danfoss Optyma iCO2[46]E40
Danfoss AK-RC 251[47]E3
Dixell XC645D[48]P3
Dixell XC645D[48]P4
Dixell XC645D[48]P5
Dixell XM669K/XM679K[50]P3
Dixell XM669K/XM679K[50]P4
Dixell XM669K/XM679K[50]CPF
Dixell XR35CX[52]P3
Dixell XR35CX[52]P4
Dixell XR70CX[54]P3
Dixell XR70CX[54]P4
Dixell XW60K/XW60L[55]P3
Dixell XW60K/XW60L[55]P4
Dixell XWi70K[56]P3
Dixell XWi70K[56]P4
Carel µC2SE for process chiller[59]E1
Carel µC2SE for process chiller[59]E2
Carel µC2SE for process chiller[59]E4
Carel µChiller[60]A05
Carel µChiller[60]A06
Carel µChiller[60]A23
Copeland Digital Compressor Controller[61]6 flashes
Copeland PerformanceAlert diagnostic module[62]11 flashes
Copeland CoreSense Protection (Discus)[63]LED green 3
Copeland CoreSense Protection (Discus)[63]LED green 4
Copeland compressor electronics communications (20–40 ton scroll)[65]LED green 4
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green 11
Daikin RA / SkyAir / VRV (malfunction codes)[75]J3
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]SUPPLY LINE SENSOR
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]RETURN LINE SENSOR
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]HOT WATER SENSOR
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]SENSOR COOLING
LG Multi V 5 VRF outdoor units[77]CH41
NIBE F1255 ground source heat pump[78]2
NIBE F1255 ground source heat pump[78]3
NIBE F1255 ground source heat pump[78]11
NIBE F1255 ground source heat pump[78]12
Secop SLV controller 105N46xx[81]E28
Secop SLV controller 105N46xx[81]E29
AHT electronic controller (plug-in cases, standard)[82]F3
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]F4
RDM DMTouch / miniDM[91]Probe Fault
RDM DMTouch / miniDM[91]Cond N TD Discharge Probe Error
RDM DMTouch / miniDM[91]Cond N TD LiqRtn Probe Error
RDM DMTouch / miniDM[91]Cond N TD Ambient Probe Error
Störk-Tronic ST121 / ST501 / ST551[93]E3L
Störk-Tronic ST121 / ST501 / ST551[93]E3H
Störk-Tronic ST121 / ST501 / ST551[93]E4L
Störk-Tronic ST121 / ST501 / ST551[93]E4H
Kriwan INT69 F Diagnose[94]LED red 3 / orange 4
Kriwan INT69 PYF Diagnose[95]LED red 3 / orange 4
Kriwan INT69 PYF Diagnose[95]LED red 3 / orange 5
Kriwan INT69 PYF Diagnose[95]LED red 5 / orange 4
Kriwan INT69 PYF Diagnose[95]LED red 6 / orange 2
Kriwan INT69 YF Diagnose[98]LED red 3 / orange 4
Kriwan INT69 YF Diagnose[98]LED red 3 / orange 5
Temperzone UC8 unit controller[100]F15
Temperzone UC8 unit controller[100]F17
Temperzone UC8 unit controller[100]F18
Temperzone UC8 unit controller[100]F19
Temperzone UC7 unit controller[101]F15
Temperzone UC7 unit controller[101]F17
Temperzone UC7 unit controller[101]F18
Temperzone UC7 unit controller[101]F19
Mitsubishi Electric City Multi (M-NET error codes)[102]51**
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]U3
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]U4
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U3
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]U4
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]UH
Goodman DX20VC inverter condensing unit[105]E23
Goodman DX20VC inverter condensing unit[105]E28
Goodman DX20VC inverter condensing unit[105]E29
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Outdoor Air Temp Sensor Failure
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Drop Leg Temp Sensor Failure
Evco EV3203[107]Pr2
Evco EVK214[109]Pr3
Evco EV3 HP / EVD HP (heat pump)[110]EA01
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]EA01
Evco EV3 MVC / EVD MVC (air handling)[112]AL03
Hitachi multi-split heat pump[113]20
Thermia Atella / Robust[114]OUTDOOR SENSOR
Thermia Atella / Robust[114]SUPPLY LINE SENSOR
Thermia Atella / Robust[114]RETURN LINE SENSOR
Thermia Atella / Robust[114]HOT WATER SENSOR
Full Gauge TC-900E POWER / TC-900E 2HP[117]Err3
Full Gauge TC-900E Log[118]Err3
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F04
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F06
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]F04
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]F06
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]19
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]1B
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A10
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]F25
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]F26
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb6
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Prb1–Prb6
RDM Mercury / Intuitive Mercury thermostats and monitors[129]rhFt
RDM Mercury AC and roof top unit controllers[130]Evap. In Temp Fault
RDM Mercury AC and roof top unit controllers[130]Evap. Out Temp Fault
RDM Mercury AC and roof top unit controllers[130]Cond. Out Temp Fault
RDM Mercury AC and roof top unit controllers[130]Evap. In Probe Fault
RDM Mercury AC and roof top unit controllers[130]Evap. Out Probe Fault
RDM Mercury AC and roof top unit controllers[130]Cond. Out Probe Fault
RDM Intuitive / Mercury pack and condenser controllers[131]Prb 1–Prb 5
RDM Intuitive Superpack / Transcritical Superpack[132]Prb 1–Prb 8
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]85
RDM ML Controller case controller[134]Prb1–Prb4
Temperzone UC6 unit controller[135]5
ActronAir Advance / VCC / Genesis 13–17 kW[136]E07
ActronAir Aires and Advance 19–25 kW[137]E7
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 52
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 53
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 54
ActronAir Nexus Touch Controller WTC-01[139]F2
ActronAir UltraSlim 2 ducted split system[140]E5
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]E03
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]E04
Carel PQ (True cabinets)[144]E2
Dixell XR/XW (True cabinets)[145]P3
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]E3
True Ice TI/TCIM ice machines[147]E2
True Ice TI/TCIM ice machines[147]E3
True Ice TI/TCIM ice machines[147]E4
True Ice TI/TCIM ice machines[147]E9
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]E3
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]E4
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]THERMISTOR SHORT
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]THERMISTOR OPEN
Taylor C392/C393/C394 frozen beverage freezers[150]Thermistor Open/Shorted
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HOPPER THERMISTOR FAIL
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BARREL THERMISTOR FAIL
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]HOPPER THERM FAIL
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BRL THERM FAIL
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]TH
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]HOPPER THERMISTOR FAIL
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BARREL THERMISTOR FAIL
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]SHRT
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]OPEN
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]OVER
Taylor 736 soft serve freezer[153]TEV INT.
Taylor 736 soft serve freezer[153]TEV S.C.
Taylor 736 soft serve freezer[153]TEC INT.
Taylor 736 soft serve freezer[153]TEC S.C.
Taylor 736 soft serve freezer[153]TEF INT.
Taylor 736 soft serve freezer[153]TEF S.C.
Taylor 736 soft serve freezer[153]CTS INT.
Taylor 736 soft serve freezer[153]CTS S.C.
Taylor Icetro ISI-161TH/ISI-161TI[154]Er01
Taylor Icetro ISI-161TH/ISI-161TI[154]Er02
Taylor Icetro ISI-161TH/ISI-161TI[154]Er03
Taylor Icetro ISI-161TH/ISI-161TI[154]Er04
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er01
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er02
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er03
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er04
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er05
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er06
HTPG EcoNet enabled unit coolers[162]A104
HTPG EcoNet enabled unit coolers[162]A105
Copeland (CPC) E2 RX/BX/CX controller[163]Failed Sensor Or Bad Wiring
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Outdoor Temp Fault
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Drop Leg Temp Fault
alpha innotec BWP 190S/260S DHW heat pump[168]Er3
alpha innotec WWB 190 DHW heat pump[169]E1
alpha innotec WWB 190 DHW heat pump[169]E2
alpha innotec WWB 190 DHW heat pump[169]E3
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.517
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P01
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P02
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]P03
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_LWT_ProbeErr
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_OAT_ProbeErr
BAC TrilliumSeries adiabatic cooler TRF[174]12
BAC TrilliumSeries adiabatic cooler TRF[174]13
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]E3
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 5, timer offOutdoor EEPROM error (EC 51) or outdoor sensor T3, T4, TP or T2B open/short (EC 52-EC 56); read the code. (The manual does not give the colour.)
Kriwan INT69 F Diagnose[94]LED green 3 / orange 4Warning: open or short circuit on temperature input 1.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D802+D803 yellow (3 s on / 0.5 s off)Current error: Discharge temperature sensor TD error (19).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D802+D803 yellow (3 s on / 0.5 s off)Current error: Outdoor air temperature sensor TO error (1B); back-up operation without indoor error display.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D804 yellow (3 s on / 0.5 s off)Current error: Gas pipe sensor TGa (unit A) error (1C); other rooms run normally.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D804 yellow (3 s on / 0.5 s off)Current error: Gas pipe sensor TGb (unit B) error (1C).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D801+D804 yellow (3 s on / 0.5 s off)Current error: Gas pipe sensor TGc (unit C) error (1C).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D801+D804 yellow (3 s on / 0.5 s off)Current error: Gas pipe sensor TGd (unit D) error (1C).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D802+D804 yellow (3 s on / 0.5 s off)Current error: Gas pipe sensor TGe (unit E) error (1C).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 3 flashesU3/U4 outdoor thermistor open or short (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Timer alternate blinking, Ready onOutdoor temperature or pressure sensor error or sensor wiring error (F04–F24). (Ready lit.) (The manual does not give the colour.)
IVT AirX air-to-water heat pump[175]3141The relative humidity sensor in the room unit for heating circuit 1 is broken.
IVT AirX air-to-water heat pump[175]3142The relative humidity sensor in the room unit for heating circuit 2 is broken.
IVT AirX air-to-water heat pump[175]3143The relative humidity sensor in the room unit for heating circuit 3 is broken.
IVT AirX air-to-water heat pump[175]3144The relative humidity sensor in the room unit for heating circuit 4 is broken.
IVT AirX air-to-water heat pump[175]5538Condensate drip tray temperature sensor TA4: open circuit.
IVT AirX air-to-water heat pump[175]5539Condensate drip tray temperature sensor TA4: short circuit.
IVT AirX air-to-water heat pump[175]5540Condensate drip tray temperature sensor TA4: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]3141The relative humidity sensor in the room unit for heating circuit 1 is broken.
IVT AirSplit 200/300 split air-to-water heat pump[176]3142The relative humidity sensor in the room unit for heating circuit 2 is broken.
IVT AirSplit 200/300 split air-to-water heat pump[176]3143The relative humidity sensor in the room unit for heating circuit 3 is broken.
IVT AirSplit 200/300 split air-to-water heat pump[176]3144The relative humidity sensor in the room unit for heating circuit 4 is broken.
IVT AirSplit 200/300 split air-to-water heat pump[176]5538Condensate drip tray temperature sensor TA4: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5539Condensate drip tray temperature sensor TA4: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5540Condensate drip tray temperature sensor TA4: faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]3141The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 500/600 series ground source heat pump[177]3142The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 500/600 series ground source heat pump[177]3143The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 500/600 series ground source heat pump[177]3144The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 500/600 series ground source heat pump[177]5946No signal from flow sensor TM0.
IVT Geo 500/600 series ground source heat pump[177]5947Short circuit in flow sensor TM0.
IVT Geo 500/600 series ground source heat pump[177]5948Signal from flow sensor TM0 outside the allowed range.
IVT Geo 312/412 ground source heat pump[178]3141The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 312/412 ground source heat pump[178]3142The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 312/412 ground source heat pump[178]3143The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Geo 312/412 ground source heat pump[178]3144The relative humidity sensor in the room unit is broken (one code per heating circuit).
IVT Vent 202/302/402 exhaust air heat pump[179]3141The relative humidity sensor in the room unit for heating circuit 1 is broken.
IVT Vent 202/302/402 exhaust air heat pump[179]3142The relative humidity sensor in the room unit for heating circuit 2 is broken.
IVT Vent 202/302/402 exhaust air heat pump[179]3143The relative humidity sensor in the room unit for heating circuit 3 is broken.
IVT Vent 202/302/402 exhaust air heat pump[179]3144The relative humidity sensor in the room unit for heating circuit 4 is broken.
IVT Vent 202/302/402 exhaust air heat pump[179]5538Condensate drip tray temperature sensor TA4: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5539Condensate drip tray temperature sensor TA4: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5540Condensate drip tray temperature sensor TA4: faulty (alarm stage).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 3 + Timer 7Heat sink thermistor on the inverter PCB is faulty (code 0E).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Timer 7Heat sink thermistor in the outdoor inverter is faulty (0E).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 8 flashesHeat sink thermistor fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]0EHeat sink thermistor fault on newer models; the older UK guide lists outdoor high pressure under this code.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 8Heat sink thermistor fault.

A sensor input whose job is set by a parameter (often the condenser, a second evaporator, the product or an antifreeze sensor) reads out of range, or the sensor is disconnected or short-circuited.

Check: Look up which job the input has in the controller set-up, check that the sensor type (NTC/PTC) matches the sensor fitted, measure its resistance against the sensor table and check cables and terminals; an unused input should be set as not present.

Pressure transmitter fault

ControllerCode
Danfoss AK-CC 550A[3]E20
Danfoss Optyma Plus[4]E39
Danfoss Optyma Plus[4]E20
Copeland EazyCool ZX (XCM25D)[5]E01
Carel EVD evolution / EVD evolution twin[16]Probe S1
Carel EVD evolution / EVD evolution twin[16]Probe S3
Carel EVD ice / EVD mini[17]A1
Carel Heos[18]ELP
Carel Heos[18]EHP
Carel MPXone[21]dA1
Carel pRack pR300[22]ALA02
Carel pRack pR300[22]ALA24
Carel pRack pR300T (transcritical CO2)[23]ALA02
Carel pRack pR300T (transcritical CO2)[23]ALA24
Carel pRack pR300T (transcritical CO2)[23]ALA44
Carel µRack[25]A19
Carel µRack[25]A21
Copeland EXD-SH1/2[26]1E0
Copeland EXD-SH1/2[26]2E0
Copeland EazyCool ZX (XCM25D)[5]E02
Copeland Large ZX 22–30 HP[29]E01
Heatcraft Beacon II[30]E4
Heatcraft Beacon II[30]SPSEN
Sanhua SEC60x[31]PoP
Sanhua SEC60x[31]PSt
Danfoss AK-CC 550 / 550B[33]E20
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E20
Danfoss AK-CC 750[36]Po sensor error
Danfoss AK-CC 750[36]Pc sensor error
Danfoss AK-PC 781A[37]P0A sensor error
Danfoss AK-PC 781A[37]PcA sensor error
Danfoss AK-PC 782A/782B[38]P0A sensor error
Danfoss AK-PC 782A/782B[38]Pgc sensor error
Danfoss AK-PC 782A/782B[38]Prec sensor error
Danfoss EIM 365[40]Pe inp.error
Danfoss EKC 326A[42]E20
Danfoss EKC 326A[42]E39
Danfoss EKE 1A/1B/1C/1D[43]E020
Danfoss EKE 1A/1B/1C/1D[43]E121
Danfoss EKE 100[44]A17
Danfoss Optyma iCO2[46]E39
Danfoss Optyma iCO2[46]E41
Danfoss Optyma iCO2[46]E42
Dixell XC645D[48]P1
Dixell XC645D[48]P2
Dixell XEV12D[49]P2
Dixell XM669K/XM679K[50]P5
Dixell XM669K/XM679K[50]PPF
Dixell XM669K/XM679K[50]rPF
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]33
Carel µChiller[60]A19
Carel µChiller[60]A21
Daikin RA / SkyAir / VRV (malfunction codes)[75]JA
Daikin RA / SkyAir / VRV (malfunction codes)[75]JC
LG Multi V 5 VRF outdoor units[77]CH42
LG Multi V 5 VRF outdoor units[77]CH43
Pego ECP200 EXPERT PULSE[89]E5
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]SUCTION PRESSURE OVER RANGE
Mayekawa MYPRO TOUCH (MYCOM screw compressor panel)[99]DISCHARGE PRESSURE UNDER RANGE
Temperzone UC8 unit controller[100]F12
Temperzone UC8 unit controller[100]F13
Temperzone UC8 unit controller[100]F34
Temperzone UC7 unit controller[101]F12
Temperzone UC7 unit controller[101]F13
Temperzone UC7 unit controller[101]F34
Mitsubishi Electric City Multi (M-NET error codes)[102]52**
Goodman DX20VC inverter condensing unit[105]E26
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Discharge Pressure Sensor Failure
Hitachi multi-split heat pump[113]21
Hitachi multi-split heat pump[113]29
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F23
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F24
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A12
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Prb7
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]rFt1
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]rFt2
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Transducer fault
RDM Intuitive / Mercury pack and condenser controllers[131]trAn
RDM Intuitive / Mercury pack and condenser controllers[131]Ft TrAn
RDM Intuitive Superpack / Transcritical Superpack[132]trAn Ft
RDM Intuitive Superpack / Transcritical Superpack[132]gSFt PgAS
RDM Intuitive Superpack / Transcritical Superpack[132]rSFt PrEC
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]87
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]88
Temperzone UC6 unit controller[135]6
ActronAir Advance / VCC / Genesis 13–17 kW[136]E10
ActronAir Advance / VCC / Genesis 13–17 kW[136]E12
ActronAir Aires and Advance 19–25 kW[137]E10
ActronAir Aires and Advance 19–25 kW[137]E12
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 5C
True Ice TI/TCIM ice machines[147]E7
True Ice TI/TCIM ice machines[147]E8
True Ice TI/TCIM ice machines[147]E33
True Ice TI/TCIM ice machines[147]E34
HTPG EcoNet enabled unit coolers[162]A106
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Discharge Pressure Fault
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.546
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]F.703
IVT AirX air-to-water heat pump[175]5432Low pressure transmitter JR0: open circuit, often caused by a brief voltage dip (warning).
IVT AirX air-to-water heat pump[175]5434Low pressure transmitter JR0 faulty (alarm).
IVT AirX air-to-water heat pump[175]5438High pressure transmitter JR1: open circuit, often temporary (warning).
IVT AirX air-to-water heat pump[175]5440High pressure transmitter JR1 faulty (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5432Low pressure transmitter JR0: open circuit, often caused by a brief voltage dip (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5434Low pressure transmitter JR0 faulty (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5438High pressure transmitter JR1: open circuit, often temporary (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5440High pressure transmitter JR1 faulty (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5662Pressure transmitter open or short-circuited, LG code 43 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5663Pressure transmitter faulty, LG code 43 (alarm).
IVT Geo 500/600 series ground source heat pump[177]5432Low pressure transmitter JR0: open circuit (warning).
IVT Geo 500/600 series ground source heat pump[177]5434Low pressure transmitter JR0 faulty (alarm).
IVT Geo 500/600 series ground source heat pump[177]5438High pressure transmitter JR1 faulty.
IVT Geo 500/600 series ground source heat pump[177]5440High pressure transmitter JR1 faulty.
IVT Geo 312/412 ground source heat pump[178]5432Low pressure transmitter JR0: open circuit (warning).
IVT Geo 312/412 ground source heat pump[178]5434Low pressure transmitter JR0 faulty (alarm).
IVT Geo 312/412 ground source heat pump[178]5438High pressure transmitter JR1 faulty.
IVT Geo 312/412 ground source heat pump[178]5440High pressure transmitter JR1 faulty.
IVT Vent 202/302/402 exhaust air heat pump[179]5432Low pressure transmitter JR0: open circuit, often caused by a brief voltage dip (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5434Low pressure transmitter JR0 faulty (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5438High pressure transmitter JR1: open circuit, often temporary (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5440High pressure transmitter JR1 faulty (alarm).
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]86Pressure sensor or high pressure switch error (E.86.1 discharge sensor, E.86.3 suction sensor, E.86.4 HP switch open at power-on).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.86.1Discharge (high) pressure sensor error: below 0.3 V for 30 s, or 5.0 V or more, after power-on. Check the plug and cable, the sensor output (0.5 V at 0 MPa to 4.5 V at 5.0 MPa) and 5 V supply from the main PCB.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.86.3Suction (low) pressure sensor error: below 0.06 V for 30 s, or 5.0 V or more, after power-on. Check the plug and cable, the sensor output (0.5 V at 0 MPa to 3.5 V at 1.7 MPa) and 5 V supply from the main PCB.

A pressure transmitter (suction or condensing pressure) gives no signal or an implausible one.

Check: Check the transmitter supply and signal, cable and connector, and compare with a gauge. Replace a faulty transmitter.

Sensors possibly swapped

ControllerCode
Danfoss EKC 202D1[41]A81
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]F15
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A08
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A11
IVT AirX air-to-water heat pump[175]5446Supply and return pipes between indoor and outdoor unit are connected the wrong way round (seen from the temperatures; the pipes, not the sensors, are swapped).
IVT AirSplit 200/300 split air-to-water heat pump[176]5446Supply and return pipes between indoor and outdoor unit are connected the wrong way round (seen from the temperatures; the pipes, not the sensors, are swapped).
IVT Vent 202/302/402 exhaust air heat pump[179]5446Supply and return pipes between indoor and outdoor unit are connected the wrong way round (seen from the temperatures; the pipes, not the sensors, are swapped).

The readings from two temperature sensors (for example air-on S3 and air-off S4) are the wrong way round, which suggests the sensors have been mounted in each other's places or wired to the wrong terminals.

Check: Check where each sensor is mounted and which terminal it is wired to, and swap them if needed.

Defrost ended on time

ControllerCode
Carel MPX[6]Ed
Carel MasterCella[7]Ed
Zanotti GM/GS[10]Ad2
Carel ir33[11]Ed1
Carel ir33[11]Ed2
Eliwell ID 974[13]Ad2
Carel Heos[18]Ed1
Carel ir33+ VCC[20]Ed1
Carel ir33+ VCC[20]Ed2
Carel MPXone[21]Ed1
Danfoss AK-CC 450[32]Max Def.Time
Danfoss AK-CC 550 / 550B[33]Max Def.Time
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Z01
Danfoss AK-CC55 Water Loop[35]Z01
Danfoss AK-CC 750[36]Max defrost time exceeded
Danfoss AK-RC 251[47]Adt
Secop SLV controller 105N46xx[81]A06
RDM DMTouch / miniDM[91]Warning: Defrost term on time
Evco EV3203[107]dFd
Full Gauge TC-900E POWER / TC-900E 2HP[117]flashing dot
Full Gauge TC-900E Log[118]flashing dot
Full Gauge TC-940R[119]flashing dot
Carel PQ (True cabinets)[144]Ed
Carel iJF with VCC (Hillphoenix SMD-H)[161]Ed1
Carel iJF with VCC (Hillphoenix SMD-H)[161]Ed2
HTPG EcoNet enabled unit coolers[162]T001
Copeland (CPC) E2 RX/BX/CX controller[163]Defrost terminated on Time
Full Gauge TC-900E POWER / TC-900E 2HP[117]Dot lower right flashingLast defrost ended on maximum time (F14), not on temperature. (The manual does not give the colour.)
Full Gauge TC-940R[119]Decimal point (lower right) flashingLast defrost ended on maximum time, not on temperature; stays until the next defrost. (The manual does not give the colour.)

The last defrost was stopped by the maximum time before the sensor reached the end temperature.

Check: Check that the defrost heats and that the sensor is correctly placed, and look for ice on the evaporator.

Evaporator iced up / air flow reduced

ControllerCode
Danfoss AK-CC 550 / 550B[33]A75
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]X02
Danfoss AK-CC 750[36]AD - Case X - Air flow reduced
Temperzone UC8 unit controller[100]FROSt
Temperzone UC7 unit controller[101]FROSt
Mitsubishi Electric City Multi (M-NET error codes)[102]1503
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]P6
Temperzone UC6 unit controller[135]7
ActronAir Nexus Touch Controller WTC-01[139]PH91
alpha innotec BWP 190S/260S DHW heat pump[168]Er8
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 6 flashesP6 freezing/overheating protection of the indoor coil (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
IVT AirX air-to-water heat pump[175]5293Dirty or blocked outdoor air coil or a stopped fan, detected on low pressure transmitter JR0.
IVT AirSplit 200/300 split air-to-water heat pump[176]5293Dirty or blocked outdoor air coil or a stopped fan, detected on low pressure transmitter JR0.
IVT Vent 202/302/402 exhaust air heat pump[179]5293Dirty or blocked outdoor air coil or a stopped fan, detected on low pressure transmitter JR0.

The adaptive defrost function has detected that the air flow through the evaporator has dropped sharply, usually because of heavy ice build-up, a stopped fan or a blocked coil.

Check: Look at the coil and the fans, check that defrosts start and end correctly (heater, drain, termination sensor) and that doors and night covers do not let in moist air.

Defrost fault

ControllerCode
Danfoss AK-CC 450[32]A5
Danfoss AK-CC 550 / 550B[33]A5
Danfoss AK-CC 550 / 550B[33]A74
Danfoss AK-CC 550 / 550B[33]A76
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A05
Danfoss AK-CC55 Water Loop[35]A05
Danfoss AK-CC 750[36]Max defrost hold time
Danfoss AK-CC 750[36]AD - Case X not defrosted
Secop SLV controller 105N46xx[81]A05
AHT electronic controller (plug-in cases, standard)[82]dFr/F3
RDM Mercury 3 Twin Coil[92]Missed defrost
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Missed defrost
Danfoss ETC (True cabinets)[142]E5
True Ice TI/TCIM ice machines[147]E26
True Ice TI/TCIM ice machines[147]E31
Copeland (CPC) E2 RX/BX/CX controller[163]Did Not Exit Defrost
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.283
IVT AirX air-to-water heat pump[175]5378Outdoor unit defrost failed, often because the heating water is too cold or the flow too low.
IVT AirX air-to-water heat pump[175]5463Defrost failed and the outdoor coil is blocked by ice; melt it carefully with warm water and improve the heating-water flow.
IVT AirX air-to-water heat pump[175]5505The heater in the condensate drip tray does not work, so the tray and drain can freeze.
IVT AirSplit 200/300 split air-to-water heat pump[176]5378Outdoor unit defrost failed, often because the heating water is too cold or the flow too low.
IVT AirSplit 200/300 split air-to-water heat pump[176]5463Defrost failed and the outdoor coil is blocked by ice; melt it carefully with warm water and improve the heating-water flow.
IVT AirSplit 200/300 split air-to-water heat pump[176]5505The heater in the condensate drip tray does not work, so the tray and drain can freeze.
IVT Geo 500/600 series ground source heat pump[177]5463Defrost alarm; IVT points to the heating-side flow (thermostats, filter).
IVT Geo 312/412 ground source heat pump[178]5463Defrost alarm; IVT points to the heating-side flow (thermostats, filter).
IVT Vent 202/302/402 exhaust air heat pump[179]5378Outdoor unit defrost failed, often because the heating water is too cold or the flow too low.
IVT Vent 202/302/402 exhaust air heat pump[179]5463Defrost failed and the outdoor coil is blocked by ice; melt it carefully with warm water and improve the heating-water flow.
IVT Vent 202/302/402 exhaust air heat pump[179]5505The heater in the condensate drip tray does not work, so the tray and drain can freeze.

The defrost did not work as expected (heater fault, no termination or too long).

Check: Check the defrost heaters and their current, the defrost sensor and the defrost settings.

Condensate drain overflow

ControllerCode
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]P10
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]P10
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 4 flashesP4 drain float switch connector open (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 5 flashesP5 drain pump error (water level) or PA forced compressor stop (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
IVT AirX air-to-water heat pump[175]5450The condensate drain of the outdoor unit is blocked, so melt water can freeze in the unit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5450The condensate drain of the outdoor unit is blocked, so melt water can freeze in the unit.
IVT Vent 202/302/402 exhaust air heat pump[179]5450The condensate drain of the outdoor unit is blocked, so melt water can freeze in the unit.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 2 + Timer 6Float switch in the indoor unit has operated (code 09): clear the drain, check the condensate pump and that the unit is level.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 2 + Timer 6Float switch tripped or condensate pump problem (09).
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]09Float switch has operated: blocked drain or condensate pump fault.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E9:00Float switch operated: high water level in the drain pan.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 4 + Timer blinkingDrain problem: float switch operated.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 4 short + Green rapid (D, E, F)High water level in the drain pan.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 6 short + Green rapid (G)High water level in the drain pan.
Daikin RA / SkyAir / VRV (malfunction codes)[75]A3Drain level fault on a VRV indoor unit: the float switch stayed up for more than 5 minutes although the drain pump ran, so the unit stops; check the drain pump, a blocked drain pipe or trap and the float switch.
Daikin RA / SkyAir / VRV (malfunction codes)[75]AFThe drain float switch has tripped five times in a row, so the indoor unit reports a drain abnormality but keeps running; clean the drain pan and pipe and check the pump and, where fitted, the humidifier.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]53Drain abnormal: the float switch has been open for more than 3 min. Check the drain pump, the drain pipe and fall, the float switch and its connector; small wall units have no float switch, so the code points to the PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]53Indoor drain abnormal: float switch open for more than 3 min. Check the drain pump, pipe and float switch.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 5 + Timer 3 + Filter flashing fastWater drain abnormal (code 53): float switch open for more than 3 min. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)

The float switch in the indoor unit's drain pan has risen because condensate is not leaving fast enough, so the unit stops cooling to avoid water damage.

Check: Check the drain pump runs and its power and wiring, clear the drain pan, pump inlet and drain pipe of dirt or slime, check the pipe has fall and is not trapped or frozen, and check that the float switch moves freely.

Controller fault

ControllerCode
Danfoss EKC 202A/B/C[2]E1
Danfoss Optyma Plus[4]E1
Carel MPX[6]EA
Dixell XW270L/XW271L[9]EE
Carel ir33[11]Etc
Carel ir33[11]EE
Carel ir33[11]EF
Danfoss VLT FC 103[14]A38
Carel ir33 universale[19]E19
Copeland EXD-SH1/2[26]ACF1
Copeland EXD-SH1/2[26]ACF2
Danfoss AK-CC 450[32]E1
Danfoss AK-CC 550 / 550B[33]E1
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E01
Danfoss AK-CC55 Water Loop[35]E01
Danfoss AK-CC 750[36]System Critical exception
Danfoss EKC 202D1[41]E1
Danfoss EKC 326A[42]E1
Danfoss Optyma Plus[4]A11
Danfoss Optyma iCO2[46]H23
Danfoss Optyma iCO2[46]H24
Danfoss Optyma iCO2[46]H25
Danfoss Optyma iCO2[46]H26
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]4
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]20
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]24
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]30
Copeland CoreSense Protection (Discus)[63]LED red (steady)
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red solid
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green 12
Danfoss CDS303/CDS803[69]A38
Danfoss VLT HVAC Basic Drive FC 101[70]A38
Danfoss VLT HVAC Basic Drive FC 101[70]A47
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X ADC Error
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X CPU Error
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X I/O Error
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]HLL
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]RL_Cal
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 7
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 11
Danfoss VLT FC 103[14]W47
NIBE F1255 ground source heat pump[78]427
Secop SLV controller 105N46xx[81]A96
Secop SLV controller 105N46xx[81]E90
AHT electronic controller (plug-in cases, standard)[82]FU6
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]E70
RDM DMTouch / miniDM[91]Solid State Drive Read Only
RDM DMTouch / miniDM[91]Disk warning
Störk-Tronic ST121 / ST501 / ST551[93]EP0
Kriwan INT69 PYF Diagnose[95]LED red 5 / orange 1
Kriwan INT69 UY Diagnose[96]LED red 3 / orange 3
Kriwan INT69 YF Diagnose[98]LED red 5 / orange 1
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Fb
Full Gauge TC-900E POWER / TC-900E 2HP[117]eCAL
Full Gauge TC-900E Log[118]eCAL
Full Gauge MT-512E Log[121]eCAL
Full Gauge MT-514E Faston[122]eCAL
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]16
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]17
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A16
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A19
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Ft
RDM Mercury / Intuitive Mercury thermostats and monitors[129]Ft
RDM Mercury AC and roof top unit controllers[130]Ft
RDM ML Controller case controller[134]Ft
Temperzone UC7 unit controller[101]F29
Danfoss ETC (True cabinets)[142]E6
Danfoss EETa (True cabinets, LED blink codes)[143]2+2 flashes
Taylor 736 soft serve freezer[153]MICRO TA
Taylor 736 soft serve freezer[153]DEV. KO
Taylor Icetro ISI-161TH/ISI-161TI[154]Er50
Taylor Icetro ISI-161TH/ISI-161TI[154]Er57
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er50
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er51
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er56
Taylor R200 fry dispenser[157]Internal Issue
Taylor R280 fry dispenser[158]Err 10
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.575
Danfoss AK-PC 781A[37]LED Status constantly onController software error. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Status constantly offController software error (no status flashing). (The manual does not give the colour.)
Copeland Digital Compressor Controller[61]All LEDs on solid togetherDigital Compressor Controller has failed.
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red solidModule has an internal fault; cycle T2-T1 power, replace module if it persists.
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Reset LED flashingController is in a fault condition and is resetting. (The manual does not give the colour.)
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow dark / green blinkPFC current sensing circuit fault.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red dark / yellow dark / green blinkCompressor current sensing circuit fault.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red dark / yellow blink / green litCompressor IPM temperature sensor circuit fault.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow dark / green litEEPROM read error.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D501 (red) flashing every 0.5 sNo EEPROM or EEPROM write failed.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D502 (orange) not flashing after power-onIndoor P.C. board not working; check or replace it.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D02 flashing 1 Hz for about 10 s, then rebootEEPROM missing or unreadable; unit loops through auto-address mode (F29/97). (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Status constantly onController software fault. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Status constantly offController software fault (or no supply). (The manual does not give the colour.)
Kriwan INT69 F Diagnose[94]LED red flashing (Temp. and Leak)Both Temp. and Leak LEDs flash red: internal error, the protection relay is defective.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller FAULT LED red steadyController device fault: no application loaded.
Taylor C392/C393/C394 frozen beverage freezers[150]Universal Control LED green steady or offThe control board processor has stopped; the touchscreen shows "Communications with control board failed".
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]OPERATION lamp green flashing 5 HzA protective circuit has operated on a P.C. board (the table lists indoor and outdoor board); read the check code with the remote controller.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D801+D802 yellow (3 s on / 0.5 s off)Current error: Position detection circuit error (16).
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D803 yellow (3 s on / 0.5 s off)Current error: Current detection circuit error (17).
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED D02 flashing 1 sNo EEPROM or EEPROM write fault.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Outdoor 7-segment HELLO over 1 minPossible interface board fault; power off for 30 s and restart. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Main board LED D1 green fast flashingHardware or firmware error.
Copeland (CPC) E2 RX/BX/CX controller[163]Keyboard LED D5 green 4 flashes per secondFlash memory or crystal problem; replace the board.
Copeland (CPC) E2 RX/BX/CX controller[163]Echelon LED red service steadyEchelon board has lost its program; replace the board.
Danfoss AK-CC 750[36]LED Status constantly onSoftware/controller error. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED Status constantly offSoftware/controller error (no status flash). (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 12 flashesFb indoor control board error (memory etc.) (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Timer synchronized blinking, Ready offIndoor EEPROM fault (F29). (both blink together; Ready off.) (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Timer synchronized blinking, Ready onOutdoor EEPROM fault (F31). (both blink together; Ready lit.) (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Reset LED flashingController is in a fault condition and is resetting. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on G-blinkPFC current-sensing circuit fault (red on, yellow off, green blink).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault G-blinkCompressor current-sensing circuit fault (red off, yellow off, green blink).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault Y-blink G-onCompressor IPM temperature-sensor circuit fault (red off, yellow blink, green on).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on G-onEEPROM read error (red on, yellow off, green on).
IVT AirX air-to-water heat pump[175]5395Internal fault in the compressor inverter; often a loose CAN or Modbus connection, otherwise the inverter or the compressor itself.
IVT AirX air-to-water heat pump[175]5394Internal inverter fault (warning), often a loose CAN or Modbus connection.
IVT AirX air-to-water heat pump[175]5452Internal fault in the compressor inverter.
IVT AirX air-to-water heat pump[175]5523Internal fault 3 in the compressor inverter, usually temporary (on Geo models the same number is PFC overcurrent).
IVT AirSplit 200/300 split air-to-water heat pump[176]251System fault in the base controller electronics.
IVT AirSplit 200/300 split air-to-water heat pump[176]5394Internal inverter fault (warning), often a loose CAN or Modbus connection.
IVT AirSplit 200/300 split air-to-water heat pump[176]5452Internal fault in the compressor inverter.
IVT AirSplit 200/300 split air-to-water heat pump[176]5523Internal fault 3 in the compressor inverter, usually temporary (on Geo models the same number is PFC overcurrent).
IVT AirSplit 200/300 split air-to-water heat pump[176]5524Internal fault 3 in the compressor inverter (alarm); on Geo models the same number is PFC overcurrent.
IVT AirSplit 200/300 split air-to-water heat pump[176]5646Fault in the inverter temperature sensor, LG code 65 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5647Fault in the inverter temperature sensor, LG code 65 (alarm).
IVT Geo 500/600 series ground source heat pump[177]258System fault in the base controller electronics; clears after a restart.
IVT Geo 500/600 series ground source heat pump[177]5394Internal inverter fault 1, usually temporary (warning).
IVT Geo 500/600 series ground source heat pump[177]5395Internal inverter fault (alarm).
IVT Geo 500/600 series ground source heat pump[177]5452Internal fault in the compressor inverter.
IVT Geo 500/600 series ground source heat pump[177]5904Fault in the compressor inverter.
IVT Geo 500/600 series ground source heat pump[177]5908The inverter control failed to initialise.
IVT Geo 500/600 series ground source heat pump[177]5988Fault in the inverter control MCE.
IVT Geo 312/412 ground source heat pump[178]5394Internal inverter fault 1, usually temporary (warning).
IVT Geo 312/412 ground source heat pump[178]5395Internal inverter fault (alarm).
IVT Geo 312/412 ground source heat pump[178]5452Internal fault in the compressor inverter.
IVT Vent 202/302/402 exhaust air heat pump[179]5394Internal inverter fault (warning), often a loose CAN or Modbus connection.
IVT Vent 202/302/402 exhaust air heat pump[179]5452Internal fault in the compressor inverter.
IVT Vent 202/302/402 exhaust air heat pump[179]5523Internal fault 3 in the compressor inverter, usually temporary (on Geo models the same number is PFC overcurrent).
IVT Vent 202/302/402 exhaust air heat pump[179]5524Internal fault 3 in the compressor inverter (alarm); on Geo models the same number is PFC overcurrent.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 4 + Timer 2The manual/auto (forced) button has been held in for 30 s or more: check that it is not stuck, otherwise the indoor PCB is faulty.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 4 + Timer 7The electrostatic air cleaner protection has operated several times: check that the front panel is closed and the panel micro switch works.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 4 + Timer 8The air cleaner power circuit reports operation although air cleaning is off: air cleaner unit or indoor PCB faulty.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 5 + Timer 3Current sensor (CT) reads 0 A about one minute after the compressor started (code 18): check the CT wiring, then the PCB.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 4 + Timer 2Manual/auto button on the indoor unit reports a fault (20).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 4 + Timer 7Electrostatic air cleaner filter fault (21).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 4 + Timer 8Air cleaner power circuit fault on the indoor PCB (22).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 5 + Timer 3Current sensor (CT) fault (18).
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]11Model information or indoor memory (EEPROM) fault on newer models; outdoor PCB failure in the older UK guide.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]18Current sensor (CT) fault: no current measured after the compressor started.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]20Manual/auto switch on the indoor unit abnormal.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]21Electrostatic air cleaner fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]22Air cleaner power circuit on the indoor PCB abnormal.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E:14Outdoor PCB failure.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer blinkingIndoor PCB failure.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer blinking + Swing blinkingOutdoor PCB failure.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 11Current sensor (CT) fault.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 4 + Green blinking, test button: Red blinking + Green 2Indoor control fault group; after the test button: manual/auto button fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 11Current sensor (CT) fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 14Timer (PCB) failure.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 blinking + LED 2 blinkingOutdoor PCB failure.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 17 flashesOutdoor PCB fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red + Green short pulsesPCB failure.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]03The PCB has found an internal CPU fault in its self-check; nothing on the unit itself needs checking, so reset the power and replace the PCB if the code returns.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]32Indoor unit main PCB error (model information or EEPROM cannot be read). Switch off and on again; if it returns, replace the indoor controller PCB and set the address again.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]32Indoor unit main PCB error (model information or EEPROM). Reset the power, then replace the indoor controller PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]62Outdoor main PCB error: EEPROM access (E.62.3), inverter communication (E.62.6) or corrupted setting data (E.62.8). See the outdoor display for the detail code.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]63Inverter error reported by the inverter PCB (E.63.1). Check the filter PCB to inverter PCB wiring, then the inverter PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]77Heat sink thermistor inside the IPM faulty (E.77.1). Replace the inverter PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]84Current sensor error on the filter PCB (E.84.1). Check the filter PCB to inverter PCB wiring.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]C4Group remote controller PCB error: its EEPROM cannot be written or a control port does not work; Operation LED flashes. Reset the power; if it returns, replace the group RC.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]CANetwork convertor software error (program, EEPROM or initial setting). Hold SW104 on the convertor for 5 s or switch off and on; if it returns, remove noise sources, then replace the convertor.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.63.1Inverter error reported by the inverter PCB. Check the filter PCB to inverter PCB wiring and connectors, then the inverter and filter PCBs.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.77.1Heat sink temperature sensor built into the IPM open or short. Replace the inverter PCB.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.84.1Current sensor error (sensor on the inverter filter PCB): 0 A read while the inverter runs at 20 rps or more for 1 min (twice), or full-scale while stopped. Check the filter PCB to inverter PCB sensor and supply wiring, then the filter and inverter PCBs.
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]CASoftware error: program, EEPROM or initial setting of the convertor PCB failed. If it does not clear by itself, hold SW104 for 5 s or reset the power; if it returns, remove noise, then replace the convertor.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 3 + Timer 2 + Filter flashing fastIndoor unit main PCB error (code 32): model information or EEPROM cannot be read. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)

The controller has detected an internal fault.

Check: Switch off the supply for a while and restart. If the fault remains, replace the controller and transfer the settings.

Configuration missing or wrong

ControllerCode
Danfoss AK-CC 550 / 550B[33]A11
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]A11
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]a04
Danfoss AK-CC55 Water Loop[35]a04
Danfoss EIM 365[40]No Rfg. Sel.
Danfoss EKE 1A/1B/1C/1D[43]E101
Danfoss EKE 1A/1B/1C/1D[43]E011
Danfoss EKE 1A/1B/1C/1D[43]E103
Danfoss EKE 100[44]A03
Danfoss EKE 100[44]A11
Danfoss EKE 100[44]A12
Copeland CoreSense Communications (13–15 ton scroll)[67]LED green 4
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED blue 2
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED blue 3
Danfoss Gas Sensor DGS[71]Wrong type
Danfoss Gas Sensor DGS[71]?
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]?
LG Multi V 5 VRF outdoor units[77]CH51
Secop SLV controller 105N46xx[81]A76
Secop SLV controller 105N46xx[81]A91
AHT GD-Cooler (GD-XLS, GD-XL)[84]noL
Temperzone UC7 unit controller[101]F26
Mitsubishi Electric City Multi (M-NET error codes)[102]7100
Mitsubishi Electric City Multi (M-NET error codes)[102]7102
Goodman DX20VC inverter condensing unit[105]E11
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]ACnf
Hitachi multi-split heat pump[113]31
Full Gauge TC-900E POWER / TC-900E 2HP[117]PPPP
Full Gauge TC-900E Log[118]PPPP
Full Gauge TC-940R[119]PPP
Full Gauge MT-512E 2HP[120]PPPP
Full Gauge MT-512E Log[121]PPPP
Full Gauge MT-514E Faston[122]PPPP
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]E08
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]L08
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]E08
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]L10
RDM Intuitive / Mercury pack and condenser controllers[131]Conf
RDM Intuitive / Mercury pack and condenser controllers[131]Boot
RDM Intuitive / Mercury pack and condenser controllers[131]Ctrl
RDM Intuitive Superpack / Transcritical Superpack[132]Err
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Modbus Addr Clash
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Modbus Ctrl Source
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]73
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]12
Temperzone UC7 unit controller[101]F27
Temperzone UC7 unit controller[101]F36
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]non
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]SYn
Taylor R200 fry dispenser[157]NV Data Bad
Taylor R280 fry dispenser[158]Err 9
Carel iJF with VCC (Hillphoenix SMD-H)[161]SF
HTPG EcoNet enabled unit coolers[162]A500
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow dark / green darkDIP switch signal level abnormal.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red lit / yellow lit / green litCompressor model code from main controller does not match the drive EEPROM.
Taylor R200 fry dispenser[157]Load size LED does not stay litCalibration lost (or keypad fault): reset parameters to default and recalibrate. (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display FH 0PAP mode activated but no Wi-Fi kit is fitted. (The manual does not give the colour.)
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D802+D803+D804 yellow (3 s on / 0.5 s off)Current error: Miswiring (mispiping) check error.
Carel EVD evolution / EVD evolution twin[16]LED POWER green flashing + red alarm LEDDC supply used while the power-supply-mode parameter is set to AC; correct the parameter.
Danfoss EKE 100[44]Valve LED red+green flashing togetherValve type has not been defined; set the valve type.
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Ready synchronized blinking, Timer offIndoor group/address/capacity setting error (L03, L05–L09). (both blink together; Timer off.) (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Ready synchronized blinking, Timer onOutdoor address/capacity/model setting error, or external interlock (L04, L10–L30). (both blink together; Timer lit.) (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation on, Timer + Ready alternate blinkingSetting incompatibility: auto cool/heat or heating selected on a model that cannot do it. (Operation lit.) (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-onDIP-switch signal level abnormal (red on, yellow off, green off).
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault R-on Y-on G-onCompressor model code from the main controller does not match the drive EEPROM (red on, yellow on, green on).
IVT AirX air-to-water heat pump[175]1081The room unit has the wrong address, so the system sees two master controllers.
IVT AirX air-to-water heat pump[175]1051A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirX air-to-water heat pump[175]1052A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirX air-to-water heat pump[175]1053A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirX air-to-water heat pump[175]1054A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirX air-to-water heat pump[175]1082The room unit for heating circuit 2 is wrongly set up as master controller (CO/SC).
IVT AirX air-to-water heat pump[175]1083The room unit for heating circuit 3 is wrongly set up as master controller (CO/SC).
IVT AirX air-to-water heat pump[175]1084The room unit for heating circuit 4 is wrongly set up as master controller (CO/SC).
IVT AirX air-to-water heat pump[175]3081The room unit refers to a heating circuit that does not exist.
IVT AirX air-to-water heat pump[175]3111A different room unit type (with or without humidity sensor) is connected than the one registered.
IVT AirX air-to-water heat pump[175]5522The indoor and outdoor units are not a valid combination.
IVT AirX air-to-water heat pump[175]6060The solar collector sensor is used as the sensor for a third solar tank.
IVT AirX air-to-water heat pump[175]6070The solar heating system has not been commissioned yet.
IVT AirSplit 200/300 split air-to-water heat pump[176]1051A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirSplit 200/300 split air-to-water heat pump[176]1052A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirSplit 200/300 split air-to-water heat pump[176]1053A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirSplit 200/300 split air-to-water heat pump[176]1054A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT AirSplit 200/300 split air-to-water heat pump[176]1081The room unit for heating circuit 1 is wrongly set up as master controller (CO/SC).
IVT AirSplit 200/300 split air-to-water heat pump[176]1082The room unit for heating circuit 2 is wrongly set up as master controller (CO/SC).
IVT AirSplit 200/300 split air-to-water heat pump[176]1083The room unit for heating circuit 3 is wrongly set up as master controller (CO/SC).
IVT AirSplit 200/300 split air-to-water heat pump[176]1084The room unit for heating circuit 4 is wrongly set up as master controller (CO/SC).
IVT AirSplit 200/300 split air-to-water heat pump[176]3081The room unit refers to a heating circuit that does not exist.
IVT AirSplit 200/300 split air-to-water heat pump[176]3111A different room unit type (with or without humidity sensor) is connected than the one registered.
IVT AirSplit 200/300 split air-to-water heat pump[176]5522The indoor and outdoor units are not a valid combination.
IVT AirSplit 200/300 split air-to-water heat pump[176]6060The solar collector sensor is used as the sensor for a third solar tank.
IVT AirSplit 200/300 split air-to-water heat pump[176]6070The solar heating system has not been commissioned yet.
IVT Geo 500/600 series ground source heat pump[177]1051Heating circuit 1 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 500/600 series ground source heat pump[177]1052Heating circuit 2 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 500/600 series ground source heat pump[177]1053Heating circuit 3 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 500/600 series ground source heat pump[177]1054Heating circuit 4 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 500/600 series ground source heat pump[177]1081The room unit for heating circuit 1 is wrongly set up as master controller.
IVT Geo 500/600 series ground source heat pump[177]1082The room unit for heating circuit 2 is wrongly set up as master controller.
IVT Geo 500/600 series ground source heat pump[177]1083The room unit for heating circuit 3 is wrongly set up as master controller.
IVT Geo 500/600 series ground source heat pump[177]1084The room unit for heating circuit 4 is wrongly set up as master controller.
IVT Geo 500/600 series ground source heat pump[177]3081A room unit is set to control heating circuit 1, which is not defined.
IVT Geo 500/600 series ground source heat pump[177]3082A room unit is set to control heating circuit 2, which is not defined.
IVT Geo 500/600 series ground source heat pump[177]3083A room unit is set to control heating circuit 3, which is not defined.
IVT Geo 500/600 series ground source heat pump[177]3084A room unit is set to control heating circuit 4, which is not defined.
IVT Geo 500/600 series ground source heat pump[177]3111A different room unit type (with or without humidity sensor) is connected than the one registered.
IVT Geo 500/600 series ground source heat pump[177]5522The heat pump and the indoor unit are not a valid combination.
IVT Geo 500/600 series ground source heat pump[177]5909A circulation pump with unknown functions is connected to the Modbus.
IVT Geo 312/412 ground source heat pump[178]1051Heating circuit 1 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 312/412 ground source heat pump[178]1052Heating circuit 2 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 312/412 ground source heat pump[178]1053Heating circuit 3 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 312/412 ground source heat pump[178]1054Heating circuit 4 is set to use the external room sensor module, but the module is not installed (4 min delay).
IVT Geo 312/412 ground source heat pump[178]1081The room unit for heating circuit 1 is wrongly set up as master controller.
IVT Geo 312/412 ground source heat pump[178]1082The room unit for heating circuit 2 is wrongly set up as master controller.
IVT Geo 312/412 ground source heat pump[178]1083The room unit for heating circuit 3 is wrongly set up as master controller.
IVT Geo 312/412 ground source heat pump[178]1084The room unit for heating circuit 4 is wrongly set up as master controller.
IVT Geo 312/412 ground source heat pump[178]3111A different room unit type (with or without humidity sensor) is connected than the one registered.
IVT Geo 312/412 ground source heat pump[178]5522The heat pump and the indoor unit are not a valid combination.
IVT Vent 202/302/402 exhaust air heat pump[179]1051A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT Vent 202/302/402 exhaust air heat pump[179]1052A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT Vent 202/302/402 exhaust air heat pump[179]1053A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT Vent 202/302/402 exhaust air heat pump[179]1054A heating circuit is set to use the external room sensor module, but the module is not installed (one code per circuit, 4 min delay).
IVT Vent 202/302/402 exhaust air heat pump[179]1081The room unit for heating circuit 1 is wrongly set up as master controller (CO/SC).
IVT Vent 202/302/402 exhaust air heat pump[179]1082The room unit for heating circuit 2 is wrongly set up as master controller (CO/SC).
IVT Vent 202/302/402 exhaust air heat pump[179]1083The room unit for heating circuit 3 is wrongly set up as master controller (CO/SC).
IVT Vent 202/302/402 exhaust air heat pump[179]1084The room unit for heating circuit 4 is wrongly set up as master controller (CO/SC).
IVT Vent 202/302/402 exhaust air heat pump[179]3081The room unit refers to a heating circuit that does not exist.
IVT Vent 202/302/402 exhaust air heat pump[179]3111A different room unit type (with or without humidity sensor) is connected than the one registered.
IVT Vent 202/302/402 exhaust air heat pump[179]5522The indoor and outdoor units are not a valid combination.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 5 + Timer 7Model information mismatch or connected indoor unit error read from memory (code 1F); often a PCB fault or a wrong replacement PCB.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 5 + Timer 7The outdoor unit does not accept the connected indoor unit (1F): check models and capacity combination.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 11 flashesTotal capacity of the connected indoor units is not accepted.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 21 flashesModel information on the outdoor PCB is wrong or unreadable.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]1FConnected indoor unit or model information not accepted.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E:11Model abnormal: indoor and outdoor PCB do not match.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 4, test button: Red 2 + Green blinkingIndoor units wrongly connected; after the test button: wrong indoor unit index (piping and wiring do not match).
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 11 flashesIndoor unit indexing problem: piping and wiring of the circuits do not match.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]31No capacity is set for the unit: check that DSW1 on the PCB matches the model (4–10 HP); change DIP switches only with the power off.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]ddThe room thermostat is wired wrongly: check the wiring to PCB terminals A, D, E and F against the wiring label.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]15Scan error / incompatible indoor unit: the RC gets no unit information. Check the master/slave setting (one RC = master; two RCs = one master, one slave; RC plus external switch controller = RC master), the cable and indoor power, then the RC and the indoor PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]--Initial setting error: DIP switch settings on the outdoor main PCB were wrong at power-on (see outdoor display ----). Correct them and switch on again.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]15System error: units were registered within 4 min of power-on, the registration spans 3 or more refrigerant systems, only a slave unit or a non-existing unit is registered, or the outdoor unit is not in the same circuit. Correct the registration and the indoor DIP/rotary switches.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]26Address setting error: no indoor unit is registered in the group RC. Register the indoor units again in function setting mode (hold TIME< and TIME>). Operation LED flashes.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]28Other setting error: auto addressing of indoor units (outdoor E.28.1) or of signal amplifiers (E.28.4) failed. See the outdoor codes.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]----Initial setting error (flashing 0.5 s on/off): a DIP switch on the outdoor main PCB was set wrongly at power-on; indoor units show nothing. Check the master/address switches (for the master unit SET3-1 and SET3-2 off), correct and switch on again.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.28.1Auto address setting error: no indoor unit answered, or an abnormal answer came, during auto addressing. Check indoor power, that no more than 64 indoor units are on one refrigerant circuit, the communication line terminals and noise or power cuts during addressing.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.28.4Signal amplifier auto address error. Check the amplifier power, that no more than 8 amplifiers are in the network, and that auto addressing was not started from more than one master outdoor unit at the same time.
Fujitsu AIRSTAGE J-II VRF – signal amplifier UTY-VSGX (7-segment display)[201]26Address setting error: no address set in the signal amplifier; no operation. Reset with SW7 or power; if it remains, set the address again and reset the power, then replace the amplifier.
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]26Group RC use: indoor units of 3 or more refrigerant circuits are registered on one convertor (reduce to 2 or fewer and wait 2 min). Single split use: communication error with the indoor unit (same checks as 16).

The controller has not been set up completely (for example no refrigerant chosen) or the inputs and outputs are assigned in a way it cannot use, so control does not start.

Check: Go through the start-up settings: refrigerant, connection/application number and the input/output assignment, then start control with the main switch.

Clock, battery or memory fault

ControllerCode
Carel EVD evolution / EVD evolution twin[16]EEPROM damaged
Carel EVD ice / EVD mini[17]EE
Carel Heos[18]tC
Carel ir33 universale[19]E06
Carel ir33 universale[19]E07
Carel ir33 universale[19]E08
Carel ir33+ VCC[20]Etc
Carel ir33+ VCC[20]EE
Carel ir33+ VCC[20]EF
Carel MPXone[21]Etc
Carel pRack pR300[22]ALG01
Carel SmartCella / SmartCella 3PH[24]Etc
Carel SmartCella / SmartCella 3PH[24]EE
Carel SmartCella / SmartCella 3PH[24]EF
Carel µRack[25]EPb
Copeland EazyCool ZX (XCM25D)[5]E86
Copeland Large ZX 22–30 HP[29]L86
Danfoss AK-CC 450[32]E6
Danfoss AK-CC 550 / 550B[33]E6
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]E06
Danfoss AK-CC55 Water Loop[35]E06
Danfoss AK-CC 750[36]Clock has not been set
Danfoss Optyma control AK-RC 113[39]E2
Danfoss EKC 202D1[41]E6
Danfoss EKE 100[44]A07
Danfoss EKC 202A/B/C[2]E6
Dixell XEV12D[49]EE
Dixell XM669K/XM679K[50]rtC
Dixell XM669K/XM679K[50]rtF
Dixell XM669K/XM679K[50]EE
Dixell XR460C[53]EE
Dixell XR460C[53]rtc
Dixell XR460C[53]rtF
Dixell XR70CX[54]rtc
Dixell XR70CX[54]rtF
Dixell XW60K/XW60L[55]EE
Dixell XW60K/XW60L[55]rtc
Dixell XW60K/XW60L[55]rtF
Dixell XWi70K[56]EE
Carel µC2SE for process chiller[59]EPb
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X EE Error
AHT electronic controller (plug-in cases, standard)[82]Clock
AHT electronic controller (plug-in cases, standard)[82]EE
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]A90
Pego ECP200 EXPERT PULSE[89]EE
Pego ECP200 EXPERT PULSE[89]E6
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]E2
Störk-Tronic ST121 / ST501 / ST551[93]EP1
Störk-Tronic ST121 / ST501 / ST551[93]EP2
Störk-Tronic ST121 / ST501 / ST551[93]rtc
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]FC
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED red 2 + pause
Evco EVK214[109]rtc
Full Gauge TC-900E Log[118]adfL
Full Gauge TC-900E Log[118]emem
Full Gauge TC-900E Log[118]eCLO
Full Gauge MT-512E Log[121]adfL
Full Gauge MT-512E Log[121]emem
Full Gauge MT-512E Log[121]eCLO
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]F31
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A13
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EH 00
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EC 51
ActronAir Nexus Touch Controller WTC-01[139]E0
Dixell XR/XW (True cabinets)[145]EE
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]CONFIG CRC ERR
Taylor Icetro ISI-161TH/ISI-161TI[154]Er15
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er15
Taylor R200 fry dispenser[157]NV Data Lost
Carel MPXzero (Hillphoenix display cases)[160]Etc
Carel iJF with VCC (Hillphoenix SMD-H)[161]Etc
Carel iJF with VCC (Hillphoenix SMD-H)[161]CE
HTPG EcoNet enabled unit coolers[162]A502
HTPG EcoNet enabled unit coolers[162]A503
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]TIM
Pego 202BASE electronic board[167]E2
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_retain
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 1, timer offIndoor unit EEPROM parameter error (EH 00 / EH 0A). (The manual does not give the colour.)
Carel ir33[11]Icon clock flashingReal-time clock alarm. (The manual does not give the colour.)
IVT AirX air-to-water heat pump[175]1038Time and date have not been set.
IVT AirSplit 200/300 split air-to-water heat pump[176]1038Time and date have not been set.
IVT AirSplit 200/300 split air-to-water heat pump[176]5638Faulty EEPROM on the outdoor unit circuit board, LG code 60 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5639Faulty EEPROM on the outdoor unit circuit board, LG code 60 (alarm).
IVT Geo 500/600 series ground source heat pump[177]1038Time and date have not been set.
IVT Geo 312/412 ground source heat pump[178]1038Time and date have not been set.
IVT Vent 202/302/402 exhaust air heat pump[179]1038Time and date have not been set.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]All lamps blinkingIndoor unit memory (EEPROM) or model information cannot be read (code 11); the UK guide calls it an indoor PCB failure.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]All four lamps blinkingIndoor unit memory (EEPROM) cannot be read (wired code 11): indoor PCB fault.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.62.3Outdoor unit EEPROM access error on the main PCB. Reset the power; if it returns, replace the main PCB and set the original address.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.62.8EEPROM data corrupted: the checksum of the field (F2) settings does not match. Clear all field settings with F3-35 and set the F2 settings again; if it returns, replace the main PCB.
Carel MasterCella[7]Clock icon flashingClock alarm. (The manual does not give the colour.)
Carel ir33+ VCC[20]Clock icon flashing (Etc)The real-time clock is faulty. (The manual does not give the colour.)

The real-time clock, its battery or the parameter memory (EEPROM) is faulty or has lost its data.

Check: Set the clock, replace the battery if fitted, and check the parameters; replace the controller if the memory fault returns.

Power backup module or battery fault

ControllerCode
Danfoss EKE 1A/1B/1C/1D[43]A997
Danfoss EKE 1A/1B/1C/1D[43]A984
Danfoss EKE 1A/1B/1C/1D[43]A985
Danfoss EKE 100[44]A01
Danfoss EKE 100[44]A02
Carel µC2SE for process chiller[59]Eb1
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]UPS Error
Copeland (CPC) E2 RX/BX/CX controller[163]Battery icon yellowLess than 30 % of battery life left.
Copeland (CPC) E2 RX/BX/CX controller[163]Battery icon redLess than 10 % battery life left, or the battery enable switch is off.
Carel EVD evolution / EVD evolution twin[16]LED alarm red flashingBackup battery discharged, faulty or disconnected.
NIBE F1255 ground source heat pump[78]SMS 40 LED BATT offSMS 40 battery is discharged or not fitted. (The manual does not give the colour.)

The battery or backup module that should close the electronic valve at a power cut is low, faulty or due for replacement, so the valve may stay open if the supply fails.

Check: Measure the backup voltage, check its wiring and replace the backup module or battery; until then there is a risk of liquid flooding at a power failure.

Communication fault

ControllerCode
Carel MPX[6]MA
Zanotti GM/GS[10]E7
Carel ir33[11]n1-n6
Danfoss VLT FC 103[14]A17
Danfoss VLT FC 103[14]A34
Carel EVD evolution / EVD evolution twin[16]LAN error
Carel EVD evolution / EVD evolution twin[16]Display connection error
Carel EVD ice / EVD mini[17]E6
Carel Heos[18]MA
Carel ir33+ VCC[20]COM
Carel MPXone[21]MA
Carel MPXone[21]u1...u9
Carel pRack pR300[22]ALO02
Carel pRack pR300T (transcritical CO2)[23]ALO02
Carel SmartCella / SmartCella 3PH[24]n1-n6
Copeland EXD-SH1/2[26]ACEr
Heatcraft Beacon II[30]E9
Heatcraft Beacon II[30]+COMM+
Danfoss AK-CC 750[36]IO module error
Danfoss AK-CC 750[36]Alarm route failure
Danfoss AK-PC 781A[37]Common IO Alarm
Danfoss AK-PC 782A/782B[38]Common IO Alarm
Danfoss Optyma iCO2[46]E90
Dixell XM669K/XM679K[50]noL
Dixell XWi70K[56]noL
Carel µC2SE for process chiller[59]I/O
Carel µC2SE for process chiller[59]Ed1
Carel µChiller[60]A41
Copeland PerformanceAlert diagnostic module[62]10 flashes
Copeland CoreSense Protection (Discus)[63]LED green 5
Copeland compressor electronics communications (20–40 ton scroll)[65]LED green 1
Copeland CoreSense Communications (13–15 ton scroll)[67]LED green 1
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green 10
Danfoss VLT HVAC Basic Drive FC 101[70]A17
Danfoss Gas Sensor DGS[71]Comm. err.
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]DP 0X Error
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]SB 0X Error
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]EP_06 0X Error
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]Comm. err.
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]SKF
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]No Comms
ebm-papst EC fans via Modbus (ECCN gateway, CN1116 MDC)[73]D/C
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED red 4
Daikin RA / SkyAir / VRV (malfunction codes)[75]U4
LG Multi V 5 VRF outdoor units[77]CH53
AHT electronic controller (plug-in cases, standard)[82]Bus
AHT electronic controller (plug-in cases, standard)[82]Col
AHT electronic controller (plug-in cases, standard)[82]FU1
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Err
RDM DMTouch / miniDM[91]Offline
RDM DMTouch / miniDM[91]Dial out failed
Mitsubishi Electric City Multi (M-NET error codes)[102]6607
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]E8
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]E9
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]E6
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]E7
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]E9
Goodman DX20VC inverter condensing unit[105]E51
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED green/red 1 s
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]ACoM
Evco EV3 MVC / EVD MVC (air handling)[112]AL04
Hitachi multi-split heat pump[113]03
Hitachi multi-split heat pump[113]04
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]E04
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]E06
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]E31
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]E03
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]E04
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]E18
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]A28
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]Brd
RDM Intuitive Superpack / Transcritical Superpack[132]br 1–br 10
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Modbus Dev OffLine
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]1
Temperzone UC8 unit controller[100]F22
Temperzone UC8 unit controller[100]F39
Temperzone UC7 unit controller[101]F21
Temperzone UC7 unit controller[101]F22
ActronAir Advance / VCC / Genesis 13–17 kW[136]E15
ActronAir Advance / VCC / Genesis 13–17 kW[136]E51
ActronAir Aires and Advance 19–25 kW[137]E15
ActronAir Aires and Advance 19–25 kW[137]E51
ActronAir Aires and Advance 19–25 kW[137]E52
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EL 01
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EH 0b
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]EL 11
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]PC 40
ActronAir Nexus Touch Controller WTC-01[139]FA
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]EoC
Danfoss ETC (True cabinets)[142]E13
True Ice TI/TCIM ice machines[147]COM
Taylor 736 soft serve freezer[153]COM. KO
Taylor Icetro ISI-161TH/ISI-161TI[154]Er52
Taylor Icetro ISI-161TH/ISI-161TI[154]Er58
Taylor Icetro ISI-161TH/ISI-161TI[154]Er61
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er52
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er58
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Er61
Carel MPXzero (Hillphoenix display cases)[160]E11
Carel MPXzero (Hillphoenix display cases)[160]E12
Carel MPXzero (Hillphoenix display cases)[160]E13
Carel MPXzero (Hillphoenix display cases)[160]E14
Carel MPXzero (Hillphoenix display cases)[160]MA
Carel MPXzero (Hillphoenix display cases)[160]u1...u9
Carel iJF with VCC (Hillphoenix SMD-H)[161]COM
HTPG EcoNet enabled unit coolers[162]A005
Copeland (CPC) E2 RX/BX/CX controller[163]Device Absent From Network
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]LC1
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]LC2
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]S.581
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]E08
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_Offline_EBM_n
BAC Nexus modular hybrid cooler (NXF controls)[172]Al_CommunicationErr_EBM_n
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]20 flashes
Danfoss AK-PC 781A[37]LED Comm redCommunication error with the bottom PC board/internal modules.
Danfoss AK-PC 781A[37]LED Comm quick flashInternal communication error between modules. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]Extension module LED comm redExtension module has lost communication with the controller.
LG Multi V 5 VRF outdoor units[77]Communication LED (yellow) offNo internal PCB communication; check cables, fuses and PCBs.
LG Multi V 5 VRF outdoor units[77]Heat recovery unit LED (green) on continuouslyHeat recovery unit PCB not communicating; check indoor communication or replace PCB.
LG Multi V 5 VRF outdoor units[77]485 modem LED red onHeat recovery (2A) communication fault; reset outdoor and heat recovery unit power.
LG Multi V 5 VRF outdoor units[77]485 modem LED red flashing485 modem fault; replace the modem (then the heat recovery PCB if it persists).
Goodman DX20VC inverter condensing unit[105]Red communications LED 1 flashCommunications failure or unknown packet received; check wiring, press LEARN.
Goodman DX20VC inverter condensing unit[105]Green receive LED offNo power to the unit, open fuse or communication error.
Goodman DX20VC inverter condensing unit[105]Green receive LED 1 steady flashNo network found: broken communication wire or unit wired as legacy system.
Goodman DX20VC inverter condensing unit[105]Green receive LED on solidTerminal 1/2 miswired, reversed or shorted (to each other or to 24 V C/R).
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED on-line (green) flashingTrying to log on to the network, or the unit has gone off-line/lost its address.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red dark / yellow blink / green blinkNo or invalid data from the main controller to the drive for 30 s.
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED red 20xModbus communication error.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 2, timer offIndoor/outdoor communication error (EL 01). (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 9, timer offCommunication error between indoor PCB and display board (EH 0b). (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 6 + timer flashingCommunication error between outdoor main chip and compressor drive chip (PC 40). (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display Err1The display cannot load data from the controller; unplug and reconnect the display. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display Err2Communication between display and controller is lost. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Comm quick flashInternal communication fault between the controller and its bottom board or modules.
Danfoss AK-PC 782A/782B[38]LED Comm constantly onInternal communication fault between the controller and its bottom board or modules.
Danfoss AK-PC 782A/782B[38]Module LED comm redThe extension module has lost communication with the controller.
BAC TrilliumSeries adiabatic cooler TRF[174]HMI fan dot grayFan status Offline: the fan has not answered within 150 ms.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller bus LED green steadySA bus, FC bus or Modbus LED lit steady: communication lost, waiting to rejoin the bus.
NIBE F1255 ground source heat pump[78]Inverter status LED red flashingOpen circuit on terminal block X4 of the inverter.
Danfoss Optyma iCO2[46]Display F0-F99No communication between the display and the unit controller.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D800+D803 yellow (3 s on / 0.5 s off)Current error: Communication error between MCUs (1C).
Dixell XM669K/XM679K[50]Board LED green blinkingThe LAN connection is wrongly configured.
Dixell XM669K/XM679K[50]Board LED green offThe LAN is not working (also check this when rPF is shown).
Dixell XM669K/XM679K[50]Display nodThe keyboard is trying to work with a board that is missing or not working; select LOC in the SEC menu. (The manual does not give the colour.)
Copeland CoreSense Protection (Discus)[63]LED red steady after RS485 wiringRS485 polarity is wrong (Pos and Neg swapped); correct polarity makes the red and green LEDs flash.
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]6 flashesIndoor-outdoor serial communication failed for 3 min (E8/E9). (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Echelon LED red reset onEchelon port is held in reset (a short flash means it has just reset).
Copeland (CPC) E2 RX/BX/CX controller[163]Echelon LED red service flashingNode has no subnet/node address; reset the E2, then replace the board if it persists.
Carel EVD evolution / EVD evolution twin[16]LED NET green offNo network connection (LAN connection error); control falls back to DI1/DI2.
Carel EVD evolution / EVD evolution twin[16]LED NET green flashingNetwork communication error with the pCO/supervisor.
Danfoss AK-CC 750[36]LED Comm redInternal communication with the lower circuit board has failed.
Danfoss AK-CC 750[36]LED Comm quick flashInternal communication between the modules is faulty. (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 3 flashesE6/E7 indoor–outdoor communication error (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 7 flashesEE indoor–outdoor communication error (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp A 9 flashesE4/E5 remote controller signal receiving error (wireless: count flashes after self-check; pattern A = indoor unit, starts after about 2.5 s off).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 1 flashE9 indoor–outdoor communication (transmitting) error at the outdoor unit (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Outdoor board LED1 2 blinks, LED2 1 blinkWrong indoor–outdoor wiring (S1, S2, S3 polarity) or short in the remote controller wire. (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation blinkingRemote/receiving-unit or indoor-unit communication or address fault (E01–E03, E08–E12, E18). (Timer and Ready off.) (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Ready blinkingIndoor–outdoor or outdoor–outdoor communication/address fault (E04, E06, E07, E15–E31). (Operation and Timer off.) (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD fault Y-blink G-blinkNo or invalid data from the main controller for 30 s (red off, yellow blink, green blink).
IVT AirX air-to-water heat pump[175]1010Communication on the EMS bus has been lost.
IVT AirX air-to-water heat pump[175]3071No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT AirX air-to-water heat pump[175]1001No communication between the controller and the room unit, probably a loose connection.
IVT AirX air-to-water heat pump[175]3061No EMS communication with the mixing module for heating circuit 1 for 4 minutes; clears itself when it returns.
IVT AirX air-to-water heat pump[175]3062No EMS communication with the mixing module for heating circuit 2 for 4 minutes; clears itself when it returns.
IVT AirX air-to-water heat pump[175]3063No EMS communication with the mixing module for heating circuit 3 for 4 minutes; clears itself when it returns.
IVT AirX air-to-water heat pump[175]3064No EMS communication with the mixing module for heating circuit 4 for 4 minutes; clears itself when it returns.
IVT AirX air-to-water heat pump[175]5265The heat pump circuit board does not answer on the CAN bus between heat pump and indoor unit (warning).
IVT AirX air-to-water heat pump[175]5266CAN bus to the heat pump board lost three times within 3 h or for 15 min (alarm).
IVT AirX air-to-water heat pump[175]5330No communication with the compressor inverter: no supply to the outdoor unit or a wrongly routed CAN cable between indoor and outdoor unit (warning).
IVT AirX air-to-water heat pump[175]5331No communication with the compressor inverter (alarm); also check the earth connection between inverter and compressor.
IVT AirX air-to-water heat pump[175]5503Connection to the load (power) monitor lost, usually temporary (warning).
IVT AirX air-to-water heat pump[175]5504Connection to the load monitor lost three times within 3 h or for 30 min (alarm).
IVT AirX air-to-water heat pump[175]5541No communication with the pool module.
IVT AirX air-to-water heat pump[175]5593The pool module has not answered for 90 s or more.
IVT AirSplit 200/300 split air-to-water heat pump[176]1001No communication between the controller and the room unit, probably a loose connection.
IVT AirSplit 200/300 split air-to-water heat pump[176]1010Communication on the EMS bus has been lost.
IVT AirSplit 200/300 split air-to-water heat pump[176]3061No EMS communication with the mixing module for heating circuit 1 for 4 minutes; clears itself when it returns.
IVT AirSplit 200/300 split air-to-water heat pump[176]3062No EMS communication with the mixing module for heating circuit 2 for 4 minutes; clears itself when it returns.
IVT AirSplit 200/300 split air-to-water heat pump[176]3063No EMS communication with the mixing module for heating circuit 3 for 4 minutes; clears itself when it returns.
IVT AirSplit 200/300 split air-to-water heat pump[176]3064No EMS communication with the mixing module for heating circuit 4 for 4 minutes; clears itself when it returns.
IVT AirSplit 200/300 split air-to-water heat pump[176]3071No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT AirSplit 200/300 split air-to-water heat pump[176]3072No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT AirSplit 200/300 split air-to-water heat pump[176]3073No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT AirSplit 200/300 split air-to-water heat pump[176]3074No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT AirSplit 200/300 split air-to-water heat pump[176]5265The heat pump circuit board does not answer on the CAN bus between heat pump and indoor unit (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5266CAN bus to the heat pump board lost three times within 3 h or for 15 min (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5330No communication with the compressor inverter: no supply to the outdoor unit or a wrongly routed CAN cable between indoor and outdoor unit (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5331No communication with the compressor inverter (alarm); also check the earth connection between inverter and compressor.
IVT AirSplit 200/300 split air-to-water heat pump[176]5503Connection to the load (power) monitor lost, usually temporary (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5504Connection to the load monitor lost three times within 3 h or for 30 min (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5541No communication with the pool module.
IVT AirSplit 200/300 split air-to-water heat pump[176]5593The pool module has not answered for 90 s or more.
IVT AirSplit 200/300 split air-to-water heat pump[176]5632Internal communication fault in the inverter, LG code 52.
IVT AirSplit 200/300 split air-to-water heat pump[176]5634Internal CAN communication fault in the outdoor unit, LG code 53 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5635Internal CAN communication fault in the outdoor unit, LG code 53 (alarm).
IVT Geo 500/600 series ground source heat pump[177]1001No communication between the controller and the room unit, probably a loose connection.
IVT Geo 500/600 series ground source heat pump[177]1010Communication on the EMS bus lost, temporarily or by a broken connection.
IVT Geo 500/600 series ground source heat pump[177]3061No EMS communication with the mixing module for heating circuit 1.
IVT Geo 500/600 series ground source heat pump[177]3062No EMS communication with the mixing module for heating circuit 2.
IVT Geo 500/600 series ground source heat pump[177]3063No EMS communication with the mixing module for heating circuit 3.
IVT Geo 500/600 series ground source heat pump[177]3064No EMS communication with the mixing module for heating circuit 4.
IVT Geo 500/600 series ground source heat pump[177]3071No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 500/600 series ground source heat pump[177]3072No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 500/600 series ground source heat pump[177]3073No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 500/600 series ground source heat pump[177]3074No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 500/600 series ground source heat pump[177]3181The wireless room sensor for heating circuit 1 sends no signal, usually too far from its receiver.
IVT Geo 500/600 series ground source heat pump[177]5265The heat pump circuit board does not answer (warning).
IVT Geo 500/600 series ground source heat pump[177]5266The heat pump circuit board is not connected (alarm).
IVT Geo 500/600 series ground source heat pump[177]5330No communication with the compressor inverter, no supply to its I/O (warning).
IVT Geo 500/600 series ground source heat pump[177]5331No communication with the compressor inverter, no supply to its I/O (alarm).
IVT Geo 500/600 series ground source heat pump[177]5503Problem with the connection to the load monitor, usually temporary (warning).
IVT Geo 500/600 series ground source heat pump[177]5504Connection to the load monitor lost (alarm).
IVT Geo 500/600 series ground source heat pump[177]5541Communication with the pool board failed.
IVT Geo 500/600 series ground source heat pump[177]5593No communication with the pool module, usually temporary.
IVT Geo 500/600 series ground source heat pump[177]5993No communication between the inverter control and the main controller.
IVT Geo 312/412 ground source heat pump[178]1001No communication between the controller and the room unit, probably a loose connection.
IVT Geo 312/412 ground source heat pump[178]1010Communication on the EMS bus lost, temporarily or by a broken connection.
IVT Geo 312/412 ground source heat pump[178]3061No EMS communication with the mixing module for heating circuit 1.
IVT Geo 312/412 ground source heat pump[178]3062No EMS communication with the mixing module for heating circuit 2.
IVT Geo 312/412 ground source heat pump[178]3063No EMS communication with the mixing module for heating circuit 3.
IVT Geo 312/412 ground source heat pump[178]3064No EMS communication with the mixing module for heating circuit 4.
IVT Geo 312/412 ground source heat pump[178]3071No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 312/412 ground source heat pump[178]3072No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 312/412 ground source heat pump[178]3073No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 312/412 ground source heat pump[178]3074No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Geo 312/412 ground source heat pump[178]5265The heat pump circuit board does not answer (warning).
IVT Geo 312/412 ground source heat pump[178]5266The heat pump circuit board is not connected (alarm).
IVT Geo 312/412 ground source heat pump[178]5330No communication with the compressor inverter, no supply to its I/O (warning).
IVT Geo 312/412 ground source heat pump[178]5331No communication with the compressor inverter, no supply to its I/O (alarm).
IVT Geo 312/412 ground source heat pump[178]5503Problem with the connection to the load monitor, usually temporary (warning).
IVT Geo 312/412 ground source heat pump[178]5504Connection to the load monitor lost (alarm).
IVT Geo 312/412 ground source heat pump[178]5541Communication with the pool board failed.
IVT Vent 202/302/402 exhaust air heat pump[179]1001No communication between the controller and the room unit, probably a loose connection.
IVT Vent 202/302/402 exhaust air heat pump[179]1010Communication on the EMS bus has been lost.
IVT Vent 202/302/402 exhaust air heat pump[179]3061No EMS communication with the mixing module for heating circuit 1 for 4 minutes; clears itself when it returns.
IVT Vent 202/302/402 exhaust air heat pump[179]3062No EMS communication with the mixing module for heating circuit 2 for 4 minutes; clears itself when it returns.
IVT Vent 202/302/402 exhaust air heat pump[179]3063No EMS communication with the mixing module for heating circuit 3 for 4 minutes; clears itself when it returns.
IVT Vent 202/302/402 exhaust air heat pump[179]3064No EMS communication with the mixing module for heating circuit 4 for 4 minutes; clears itself when it returns.
IVT Vent 202/302/402 exhaust air heat pump[179]3071No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Vent 202/302/402 exhaust air heat pump[179]3072No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Vent 202/302/402 exhaust air heat pump[179]3073No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Vent 202/302/402 exhaust air heat pump[179]3074No EMS communication with the room unit (one code per heating circuit); check the cable and keep it away from mains cables.
IVT Vent 202/302/402 exhaust air heat pump[179]5265The heat pump circuit board does not answer on the CAN bus between heat pump and indoor unit (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5266CAN bus to the heat pump board lost three times within 3 h or for 15 min (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5330No communication with the compressor inverter: no supply to the outdoor unit or a wrongly routed CAN cable between indoor and outdoor unit (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5331No communication with the compressor inverter (alarm); also check the earth connection between inverter and compressor.
IVT Vent 202/302/402 exhaust air heat pump[179]5503Connection to the load (power) monitor lost, usually temporary (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5504Connection to the load monitor lost three times within 3 h or for 30 min (alarm).
IVT Vent 202/302/402 exhaust air heat pump[179]5541No communication with the pool module.
IVT Vent 202/302/402 exhaust air heat pump[179]5593The pool module has not answered for 90 s or more.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation off + Timer 2Indoor and outdoor unit could not talk to each other at start-up (reverse transfer, wired remote code 01): check the interconnecting cable and the voltage at indoor and outdoor unit.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation off + Timer 3Indoor and outdoor unit lost contact for about 10 s during operation (reverse transfer): check the interconnecting cable, splices and supply voltage.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation off + Timer 4No forward signal from the outdoor unit at start-up (wired remote code 13): reset the power, then check the cable and voltages.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation off + Timer 5Forward signal from the outdoor unit lost during operation (wired remote code 13): check the cable, splices and supply.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation off + Timer 8The indoor unit and the wired remote do not communicate (code 00): check the remote cable and the 12 V DC at the indoor connector; with voltage present the remote is faulty.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Timer 2Reverse transfer error at start-up between indoor and outdoor unit (wired code 01).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Timer 3Reverse transfer error during operation between indoor and outdoor unit.
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Timer 4Forward transfer signal from the outdoor unit missing at start-up (wired code 13).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Timer 8Wired remote and indoor unit do not communicate (wired code 00).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 5 + Timer 8Main CPU and sub CPU on the outdoor PCB do not communicate (1C).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 1 flashNo forward signal between the outdoor unit and indoor unit A.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 2 1 flashNo forward signal between the outdoor unit and indoor unit B.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 3 1 flashNo forward signal between the outdoor unit and indoor unit C.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 4 1 flashNo forward signal between the outdoor unit and indoor unit D.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 17 flashesMicrocomputers on the outdoor PCB do not communicate.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]00Indoor unit and wired remote do not communicate: check the remote cable (screened, away from mains cables) and the 12 V DC at the indoor unit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]01Indoor and outdoor unit do not communicate (reverse transfer): check the interconnecting cable, crimped joints and supply voltage.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]13Forward signal from the outdoor unit missing or abnormal.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]1CCommunication fault between the inverter and the main outdoor PCB (main/sub CPU).
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]26Indoor signal error.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]27Indoor signal error.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E0:00Indoor unit and wired remote do not communicate; check the remote cable and interference.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E1:00Indoor and outdoor unit do not communicate; check the interconnecting cable.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E:13Signal from the outdoor unit abnormal.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 5 + Timer blinkingIndoor and outdoor unit do not communicate.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 5 + Timer blinking + Swing blinkingOutdoor PCB or interconnecting wiring fault.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 5 + Green blinking, test button: Red blinking + Green 2Communication fault group; after the test button: reverse transfer (indoor to outdoor) fault.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 5 + Green blinking, test button: Red blinking + Green 3Communication fault group; after the test button: forward transfer (outdoor to indoor) fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 1Communication fault with the indoor unit.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 9Indoor communication error.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 1Communication fault with the indoor unit.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 5 + LED 2 steadyCommunication fault with the indoor unit.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 1 flashesCommunication fault with the indoor unit on this circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 5 short + Green rapid (F)Communication failure between indoor and outdoor unit.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]12Remote controller lost contact with its indoor unit: the indoor unit sent no signal for over 1 min. Check the RC cable and the indoor power, that RC addresses run from 0 without gaps, then measure about 12 V DC at the RC connector on the indoor PCB (12 V: replace the RC; 0 V: replace the indoor PCB).
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]14Network communication error: the indoor unit has heard nothing from the outdoor unit for about 90 s. If only some indoor units show it, check their communication PCB and wiring; if all do, check the outdoor communication PCB and the network line.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]16Indoor unit parallel communication error between the indoor controller PCB and its communication PCB. Check that the communication PCB is fitted and plugged in, then replace it, then the controller PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]12Remote controller communication error (with the indoor unit or the network convertor). On a convertor no valid signal has arrived for 90 s: check the convertor power, the RC line and voltage dips or noise; then the RC. Operation LED flashes.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]14Network or transmission error: the signal from a registered indoor unit (not a slave) has been lost for over 10 min, or the outdoor unit lost an indoor unit. Check the transmission cable and the indoor and convertor power.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]16Indoor unit parallel communication error (indoor controller PCB to communication PCB). Check and replace the indoor communication PCB.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]69Outdoor unit transmission PCB parallel communication error (E.69.1). Check the outdoor communication PCB and its connector.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]C1Network convertor PCB error 1: synchronisation with the network device failed. Hold SW104 for 5 s or reset the power; if it returns, remove noise sources, then replace the convertor.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.14.1Network communication error 1: an indoor unit that has communicated before has been silent for 180 s or more. Check that indoor unit’s power, the network line, the terminal resistor setting, noise and its communication PCB.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.14.2Network communication error 2: all indoor units have been silent for 180 s or more (indoor units show 9/15). Check the network line from the outdoor unit, the terminal resistor, the indoor power and the outdoor communication PCB.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.14.5Indoor unit shortage: fewer indoor units than the stored maximum have answered for 180 s after power-on. The system keeps running. Find the missing unit (power, line, terminal resistor, communication PCB); afterwards clear the stored count with function F3-41.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.62.6Inverter communication error: no signal from the inverter PCB for 10 s or more. Check the main–inverter PCB cable, then the inverter PCB and main PCB.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.69.1Outdoor transmission PCB parallel communication error (failed 5 times). Check that the outdoor communication PCB is seated and connected; then replace it.
Fujitsu AIRSTAGE J-II VRF – signal amplifier UTY-VSGX (7-segment display)[201]C1Parallel communication error between the CPU and the network driver IC. Press RESET (SW7) or switch off and on; if it comes back, remove noise sources, then replace the amplifier.
Fujitsu AIRSTAGE J-II VRF – signal amplifier UTY-VSGX (7-segment display)[201]D9Communication error B (CH_B side network driver IC), display flashing or steady; no operation. Reset with SW7; if it returns, remove noise, then replace the amplifier.
Fujitsu AIRSTAGE J-II VRF – signal amplifier UTY-VSGX (7-segment display)[201]D14Communication error A (CH_A side network driver IC), display flashing or steady; no operation. Reset with SW7; if it returns, remove noise, then replace the amplifier.
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]C1PCB error 1: synchronisation with the network device failed; nothing can be controlled. Hold SW104 for 5 s or switch off and on; if it comes back, remove noise sources, then replace the convertor.
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]12Communication error with the connected (group or standard) remote controller; control from that RC is not possible. Check the RC cable and terminals, DIP-SW103 1–4 on (group RC) or DIP-SW107-2 wired RC enable (single split), the RC’s DIP switch for the number of RCs, then the RC or convertor.
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]16Communication error with the single split indoor unit; nothing operates. Check the RC cable to the indoor unit, indoor power, the indoor main unit address, and DIP-SW103 1–8 (indoor type, RC type, number of units), then the indoor PCB or convertor.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 1 + Timer 2 + Filter flashing fastRemote controller communication error (RC code 12). Check the RC cable, RC addresses and 12 V DC at the RC connector on the indoor PCB. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 1 + Timer 4 + Filter flashing fastNetwork communication error (code 14): no signal from the outdoor unit for about 90 s. Check the network line and the communication PCBs. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 1 + Timer 6 + Filter flashing fastIndoor unit parallel communication error (code 16) between the controller PCB and the communication PCB. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – external switch controller UTY-TEKX (LED)[203]LED flashing 0.5 s on / 0.5 s offUTY-TEKX: remote controller cable abnormal, no communication with the indoor unit for over 1 min. Check the cable, DIP-SW1-4/1-5/1-6 and noise. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – external switch controller UTY-TEKX (LED)[203]LED flashing 0.5 s on / 1.0 s offUTY-TEKX: transmission error, normal communication with the indoor unit suspended for over 1 min. Check DIP-SW1-4/1-5/1-6 and noise. (The manual does not give the colour.)
Secop BD electronic units (BD35F/BD50F/BD35K/BD80CN, 101N0212/0340/0390/0420/0510/0650)[80]7 flashesCommunication error; the manual lists it as error code 7 and says the codes can also be read on the error LED. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]MODBUS 40 LED COM2MODBUS 40: indicates no active communication with the external control system. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED LEV offSMS 40 GSM signal is too weak. (The manual does not give the colour.)

The connection between parts of the controller (display and power board, or master and slave) is broken.

Check: Check cables and connectors between the units and restart them.

Service or maintenance reminder

ControllerCode
Carel pRack pR300[22]ALT01
Carel µRack[25]A05
Dixell XC645D[48]A14
Carel µC2SE for process chiller[59]Hc1
Danfoss Gas Sensor DGS[71]LED green flashing
Danfoss Gas Sensor DGS[71]Calibration due
Danfoss Gas Sensor DGS[71]#
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]Maintenance
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]#
Evco EV3 CHILL / HPRU (chiller, heat pump)[111]AHou
Thermia Calibra[115]Class B
Thermia Calibra[115]Class C
Full Gauge TC-900E Log[118]AMai
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]BRUSH CLEAN TIMEOUT
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]BRUSH CLEAN TIMEOUT
Carel iJF with VCC (Hillphoenix SMD-H)[161]SrC
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]CL
LAE AT1-5/AT2-5[166]CL
alpha innotec BWP 190S/260S DHW heat pump[168]Er10
alpha innotec WWB 190 DHW heat pump[169]E11
Carel µRack[25]Icon MANUFACTURER + ALARM flashingCompressor maintenance hours exceeded. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED service (spanner)The service interval (P-26 run hours) has expired; service the unit and reset the counter. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED service (spanner)The service interval has expired; service the case and reset the interval parameter. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol maintenance (spanner)Maintenance is due or the unit runs in restricted (comfort protection) mode; it keeps running. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Display Lhm.37Comfort protection: a permanent fault was detected and the unit runs with reduced comfort. (The manual does not give the colour.)
True Ice TI/TCIM ice machines[147]UV LED red steadyUV lamp operating time exceeded; replace the lamp.
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Brush-clean countdown shows 1Machine must be disassembled and brush-cleaned within 24 h. (The manual does not give the colour.)
Carel µChiller[60]Service (spanner) icon steadyA device has reached its programmed operating-hour threshold; maintenance is due (see the code). (The manual does not give the colour.)
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]LED green flashingMaintenance (calibration/service) message is due.
RDM Mercury 3 Twin Coil[92]LED service (spanner) steadyService interval set in P-18 has elapsed; service is due. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED service (spanner) steadyRun-hours service interval (P-18) has elapsed; service is due. (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Service icon steadyMaintenance request. (The manual does not give the colour.)
IVT AirX air-to-water heat pump[175]6219Reminder that the 3-year or 5-year warranty service is due.
IVT AirX air-to-water heat pump[175]6220The service reminder was acknowledged three times; only a technician can clear it.
IVT AirSplit 200/300 split air-to-water heat pump[176]6219Warranty service reminder after 3 and 5 years of operation; shown together with 6220.
IVT AirSplit 200/300 split air-to-water heat pump[176]6220Warranty service reminder after 3 and 5 years of operation; shown together with 6219.
IVT Geo 500/600 series ground source heat pump[177]6219Warranty service reminder after 3 and 5 years of operation; shown together with 6220.
IVT Geo 500/600 series ground source heat pump[177]6220Warranty service reminder after 3 and 5 years of operation; shown together with 6219.
IVT Geo 312/412 ground source heat pump[178]6219Reminder that the 3-year or 5-year warranty service is due.
IVT Geo 312/412 ground source heat pump[178]6220The service reminder was acknowledged three times; only a technician can clear it.
IVT Vent 202/302/402 exhaust air heat pump[179]5596Reminder to clean the exhaust air filter, every 2 months; a low pressure warning (5666) also triggers it.
IVT Vent 202/302/402 exhaust air heat pump[179]6219Warranty service reminder after 3 and 5 years of operation; shown together with 6220.
IVT Vent 202/302/402 exhaust air heat pump[179]6220Warranty service reminder after 3 and 5 years of operation; shown together with 6219.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Filter steadyFilter sign: time to clean the air filter; reset the filter sign after cleaning. (The manual does not give the colour.)

A run-hour or service interval has expired, or the controller asks for a check.

Check: Carry out the service and reset the counter according to the manual.

Status: normal operation

ControllerCode
Copeland CoreSense Diagnostics (UltraTech scroll)[66]LED green solidThe module has its 18-28 V supply and works normally; no trip is active.
Copeland CoreSense Diagnostics (scroll AC)[64]LED yellow (steady)The module is powered and the compressor/system runs normally.
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED green solidNormal compressor operation, no alert active.
Copeland CoreSense Communications (13–15 ton scroll)[67]LED green solidThe module is powered and operating normally.
Copeland compressor electronics communications (20–40 ton scroll)[65]LED green solidThe module is powered and operating normally.
Copeland CoreSense Protection (Discus)[63]LED green (steady)Normal state: the compressor is either running or normally off, with no warning, trip or lockout.
Copeland Stream condensing units (Next Gen CoreSense)[27]LED green steadyNormal operation; no faults on the compressor.
Danfoss Optyma Plus Module B Plus (P02)[45]LED2 green steadyStatus LED: Module B Plus is powered and has no error.
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED greenNo warning and no fault; the fan is ready for operation.
Danfoss Gas Sensor DGS[71]LED green steadyPower on, no alarm and no fault.
Heatcraft A2L Refrigerant Detection System (unit coolers)[79]LED green steadyInitialization finished; the detection system is in normal operation.
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]LED steadyThe inverter board LED stays lit during normal operation.
Carel EVD ice / EVD mini[17]Start/stop LED (decimal point) blinkingStart/stop digital input is closed and superheat control is active. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Status slow flashSoftware running normally; controller ready (about one minute after power on). (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Alarm offNo active and no unacknowledged alarms. (The manual does not give the colour.)
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]Extension module LED blue onLow-pressure transmitter input on the extension module is working correctly.
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]Extension module LED red onHigh-pressure transmitter input on the extension module is working correctly (red here is not a fault).
Secop SLV controller 105N46xx[81]External operating LED (DI1 = 18) onController is running (not in Stopped mode). (The manual does not give the colour.)
LG Multi V 5 VRF outdoor units[77]Main PCB 7-segment LED blank after power-onSelf-diagnostics (about 3 min) finished; unit ready for auto addressing. (The manual does not give the colour.)
LG Multi V 5 VRF outdoor units[77]Communication LED (yellow) blinkingCommunication between main PCB, inverter compressor PCBs, fan PCB or MICOMs is normal.
LG Multi V 5 VRF outdoor units[77]External PCB communication LED blinkingSignal between main PCB and external PCB is normal. (The manual does not give the colour.)
LG Multi V 5 VRF outdoor units[77]Heat recovery unit LED (green) blinkingHeat recovery unit PCB is powered and communicating.
Goodman DX20VC inverter condensing unit[105]Red communications LED offNormal condition, no communication fault.
Goodman DX20VC inverter condensing unit[105]Green receive LED rapid flashingNormal network traffic; the control is talking on the network.
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED on-line (green) steadyConnected and on-line on the network.
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Status LED 2 flashesController is working normally (two flashes at one-second intervals). (The manual does not give the colour.)
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Status bar blueNormal operation, no alarm.
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Expansion module status LED flashingExpansion I/O module is powered and healthy. (The manual does not give the colour.)
ActronAir Aires and Advance 19–25 kW[137]Indoor board COM1/COM2 LEDs blinkingCommunication on the wall control/outdoor (or InZone) RS485 lines is occurring. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]Ice cream cone icon steadyProduct is within about 10 % of set consistency and ready to serve. (The manual does not give the colour.)
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Fan LED solid redNormal fan operation (red is normal here).
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D14 (orange) flashingIndoor PCB is receiving the serial signal from the outdoor unit.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D15 (green) flashingIndoor PCB is sending the serial signal to the outdoor unit.
AHT electronic controller (plug-in cases, standard)[82]Lamp 3 greenMechanical controller: the cabinet is in normal operation with no fault.
AHT electronic controller (plug-in cases, standard)[82]Lamp 3a greenMechanical controller: deep-freeze mode (-) selected and running normally.
AHT electronic controller (plug-in cases, standard)[82]Lamp 3b greenMechanical controller: cooling mode (+) selected and running normally.
Danfoss AK-PC 782A/782B[38]LED Status slow flashSoftware running normally; the controller is ready about a minute after power-on. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Alarm offNo active and no unacknowledged alarms. (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]EC fan LED greenEC fan motor: status good, ready for operation.
BAC TrilliumSeries adiabatic cooler TRF[174]HMI fan dot greenFan status Good: no active fan alarms.
Heatcraft Beacon II[30]Display oFFOff cycle: room temperature is satisfied, or the unit is switched off; alternates with the box temperature.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller FAULT LED offNo controller faults.
NIBE F1255 ground source heat pump[78]Board LED Run green flashingThe card processor is working (about one flash per second).
NIBE F1255 ground source heat pump[78]Inverter status LED green steadyCompressor stopped, no fault.
NIBE F1255 ground source heat pump[78]Inverter status LED green flashingCompressor stopped, no fault.
Danfoss Optyma iCO2[46]Display S0Normal control.
Danfoss Optyma iCO2[46]Display S11Thermostat cut-out on DI2 (no cooling demand).
Carel pRack pR300[22]Terminal LED yellowThe pRack controller is switched on.
Taylor C392/C393/C394 frozen beverage freezers[150]Universal Control LED green blinkingHeartbeat: the control board processor is working.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LED D805 green on, D800-D804 offOutdoor P.C. board initial display: normal operation, no error.
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol filling pressure steadyHeating circuit filling pressure is within the permitted range. (The manual does not give the colour.)
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Lamp P02Panel lamp in the wiring example: the compressor is ready to operate. (The manual does not give the colour.)
Carel pRack pR300T (transcritical CO2)[23]Terminal LED yellow steadyThe pRack unit is switched on.
Danfoss Optyma control AK-RC 113[39]Icon stand-by steadyPanel is on and regulating. (The manual does not give the colour.)
Castel 5650E/5658E electronic oil level regulator (R744)[123]LED OIL GOOD green steadyOil level is correct.
RDM Intuitive / Mercury pack and condenser controllers[131]LED network steadyOn-line on the network. (The manual does not give the colour.)
Danfoss EETa (True cabinets, LED blink codes)[143]LED flashing once per secondPower on, no alarm. (The manual does not give the colour.)
True Ice TI/TCIM ice machines[147]UV LED blue steadyUV ballast is on and working correctly.
Copeland (CPC) E2 RX/BX/CX controller[163]Main board LED D1 green flashing 1 s on/1 s offMain board is working normally.
Copeland (CPC) E2 RX/BX/CX controller[163]Keyboard LED D5 green flashing 1 s on/1 s offKeyboard status normal.
Danfoss AK-CC 750[36]LED Status slow flashSoftware running normally; controller ready (about 1 minute after power-up). (The manual does not give the colour.)
Danfoss EKE 100[44]LED alarm red offNo alarm or warning on valve A or B.
Danfoss EKE 100[44]Valve LED red steadyValve (A or B) is fully closed.
Danfoss EKE 100[44]Valve LED offValve is idle at its target position.
Danfoss EKE 100[44]Valve LED green steadyValve is fully open.
Temperzone UC8 unit controller[100]Display dot flashingNormal operation (standby or running). (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Indoor board LED3 blinkingIndoor–outdoor communication is running (should always blink). (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Outdoor board only LED1 lit after start-upNormal: both LEDs light at power-on, then LED2 goes out (about 2 minutes start-up). (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Status bar blue steadyNormal operation, no alarm.
RDM Intuitive Superpack / Transcritical Superpack[132]Status LED double flash every secondController is working normally. (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Expansion module status LED flashing 0.5 sExpansion I/O module is powered and healthy. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Indoor board COM1 + COM2 LEDs blinkingIndoor board is communicating with the wall controller and outdoor unit; no blinking points to a communication fault. (The manual does not give the colour.)
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Danfoss sensor LED green (steady or blinking)Sensor is powered and in normal status.
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor PWR green steady, red offNormal monitoring, no refrigerant detected.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation steadyUnit switched on, no fault. (The manual does not give the colour.)
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red steadyUnit switched on and running normally.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]LED101 POWER/MODE steadyOutdoor main PCB has power; ERROR LED102 is off when there is no fault.
Thermia Atella / Robust[114]Alarm indicator green steadyNormal operation, no alarm.
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED valve steady (Control Thermostat)On the Control Thermostat the valve LED shows the controller's operating state. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Echelon LED red service offNormal operation: the Echelon service LED should be dark.

The lamp shows that the unit has power and works normally; no fault is active.

Check: Nothing to do; if the unit still does not cool, troubleshoot the symptom (the controller sees no fault).

Status: running or demand

ControllerCode
Copeland CoreSense Diagnostics (refrigeration scroll ZB/ZF/ZS)[68]LED blue slow flashingDigital unloader solenoid is energized (scroll unloaded); the on period varies about 2-20 s with the capacity demand.
Copeland Digital Compressor Controller[61]UNLOADER LED yellow onThe digital unloader solenoid is energized, so the compressor is running unloaded at that moment.
Kriwan INT69 F Diagnose[94]LED green flashingNo fault; the machine is running.
Kriwan INT69 PYF Diagnose[95]LED green flashingNo fault; the machine is running.
Kriwan INT69 YF Diagnose[98]LED green flashingNo fault; the machine is running.
Kriwan INT69 UY Diagnose[96]LED green flashingNo fault; the machine is running.
Kriwan INT69 Y Diagnose[97]LED green flashingNo fault; the machine is running.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED green 1 sKB drive ST LED: normal operation, drive in run mode.
Danfoss ERC 21X[1]Icon compressor steadyCompressor output is running. (The manual does not give the colour.)
Danfoss ERC 21X[1]Icon compressor flashingCompressor running in a pull-down cycle. (The manual does not give the colour.)
Danfoss ERC 21X[1]Icon fan steadyEvaporator fan is running. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED compressor onCompressor 1 is enabled. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED condenser fan onCondenser fans are enabled. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED digital unloader onDigital scroll unloader solenoid is energised (compressor unloaded). (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED evaporator fan / liquid solenoid onEvaporator fans or liquid-line solenoid valve output is on. (The manual does not give the colour.)
Carel MPXone[21]Icon solenoid/compressor onSolenoid or compressor output is active (cooling request). (The manual does not give the colour.)
Carel MPXone[21]Icon evaporator fan onEvaporator fan is on. (The manual does not give the colour.)
Carel µRack[25]Icon fan onAt least one condenser fan is running (or fan parameters being set). (The manual does not give the colour.)
Carel µRack[25]Icon compressor onAt least one compressor step is active (or compressor parameters being set). (The manual does not give the colour.)
Carel µRack[25]Icons 1–4 (steps) onShows which compressors/capacity steps (or fans, in fan-only mode) are on. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED 1 onCompressor 1 is running. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED 2 onCompressor 2 is running. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED condenser fan onCondensing fan is running. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED digital compressor onDigital compressor is unloading. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED liquid line solenoid onLiquid-line solenoid valve is energised. (The manual does not give the colour.)
Danfoss AK-CC 550 / 550B[33]LED refrigeration onRefrigeration relay is on (cooling in progress). (The manual does not give the colour.)
Danfoss AK-CC 550 / 550B[33]LED fan onFan relay is on. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED DO1–DO8 onThe corresponding relay output is on. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]Stepper module LED step OPEN greenStepper valve output is driving open.
Danfoss AK-PC 781A[37]Stepper module LED step CLOSE greenStepper valve output is driving closed.
Danfoss EKC 202D1[41]LED refrigeration onRefrigeration (compressor/solenoid) relay is on. (The manual does not give the colour.)
Danfoss EKC 202D1[41]LED fan onEvaporator fan is running. (The manual does not give the colour.)
Dixell XEV12D[49]LED valve onExpansion valve is open.
Dixell XR460C[53]Icon compressor 1 onCompressor 1 output is on. (The manual does not give the colour.)
Dixell XR460C[53]Icon compressor 2 onCompressor 2 output is on. (The manual does not give the colour.)
Dixell XR460C[53]Icon fan onEvaporator fan output is enabled. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon EEV output onElectronic expansion valve output is on. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon cold call (compressor) onCooling is called; compressor output is on. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon fans onEvaporator fans are called on. (The manual does not give the colour.)
Secop SLV controller 105N46xx[81]LED Cooling onCompressor cooling is active. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]LED1 on (default)Compressor/solenoid valve output is on (default assignment U11 = 1; can be reassigned). This default applies to the ST121/ST501; on the ST551 LED1 shows an alarm by default.
Störk-Tronic ST121 / ST501 / ST551[93]LED3 on (default)Evaporator fan is on (default U13 = 3; can be reassigned). This default applies to the ST121/ST501; on the ST551 LED3 shows a low-pressure alarm by default.
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED compressor onCompressor output is on. (The manual does not give the colour.)
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED compressor flashing fastFast freezing mode is running (compressor held on). (The manual does not give the colour.)
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED fan onEvaporator fan output is on. (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED cooling onCooling output is on. (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED heating onHeating output is on. (The manual does not give the colour.)
Temperzone UC7 unit controller[101]Comp light onCompressor contactor output (CMC) is energised. (The manual does not give the colour.)
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Relay LEDs onThe associated relay output is energised. (The manual does not give the colour.)
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink (fast, ~250 ms) / yellow dark / green darkDrive running: red flashes once about every 250 ms.
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Icon compressor onCompressor is running. (The manual does not give the colour.)
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Icon evaporator fan onEvaporator fan is running. (The manual does not give the colour.)
Dixell XR/XW (True cabinets)[145]Icon compressor (snowflake) onCompressor is running. (The manual does not give the colour.)
Dixell XR/XW (True cabinets)[145]Icon fan onEvaporator or condenser fan is running. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]Ice cream cone icon flashingProduct in the barrel is not yet at dispensing consistency (freezing). (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]Beater icon onBeater motor is on. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]Agitator icon onHopper agitator is on. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]AUTO button litAuto mode: refrigeration system is active. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]MIX HOPPER button litHopper agitator is on. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon continuous cycle onContinuous cycle is running. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon compressor onCompressor is running. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon evaporator fan onEvaporator fan is running. (The manual does not give the colour.)
alpha innotec WWB 190 DHW heat pump[169]Symbol electric heater onElectric backup heater is on. (The manual does not give the colour.)
alpha innotec WWB 190 DHW heat pump[169]Symbol heat pump operationHeat pump (compressor) is running. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]LED coolingCooling is on. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]LED fanThe evaporator fans are running. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED DO1-DO8 onThe corresponding relay output is on. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]AK-XM 208C LED step OPEN greenThe stepper valve output is opening.
Danfoss AK-PC 782A/782B[38]AK-XM 208C LED step CLOSE greenThe stepper valve output is closing.
Heatcraft Beacon II[30]Display CooCooling: valve open and compressor running (slave evaporators show only this).
Heatcraft Beacon II[30]Display PdnPumpdown at the end of a cooling cycle: valve closed, compressor pumping the suction side down.
Danfoss ETC (True cabinets)[142]Icon compressorThe compressor is running. (The manual does not give the colour.)
Danfoss ETC (True cabinets)[142]Icon evaporator fanThe evaporator fan is running. (The manual does not give the colour.)
Danfoss EKC 202A/B/C[2]LED refrigeration steadyCooling relay is on. (The manual does not give the colour.)
Danfoss EKC 202A/B/C[2]LED fan steadyFan relay is on. (The manual does not give the colour.)
Copeland EXD-SH1/2[26]LED circuit 1 ONCircuit 1 is switched on (enable input closed) and controlled. (The manual does not give the colour.)
Copeland EXD-SH1/2[26]LED circuit 2 ONCircuit 2 is switched on (EXD-SH2 only). (The manual does not give the colour.)
Copeland EXD-SH1/2[26]LED valve steadyThe valve of the shown circuit is in regulation. (The manual does not give the colour.)
Copeland EXD-SH1/2[26]LED valve opening blinkingThe valve is opening. (The manual does not give the colour.)
Copeland EXD-SH1/2[26]LED valve closing blinkingThe valve is closing. (The manual does not give the colour.)
Danfoss VLT HVAC Basic Drive FC 101[70]LED above Auto OnThe drive is in auto mode, controlled via terminals or serial bus. (The manual does not give the colour.)
Carel Heos[18]Icon compressorMain screen: the compressor output is on. (The manual does not give the colour.)
Carel Heos[18]Icon evaporator fanMain screen: the evaporator fan output is on. (The manual does not give the colour.)
Carel Heos[18]Power+ LED RUN/FAULT greenThe Power+ drive is running the compressor.
HTPG EcoNet enabled unit coolers[162]Relay LED on (controller board)The relay next to the LED is energised (e.g. Aux 1 fans full speed, Aux 1 + Aux 2 fans half speed, defrost relays during defrost). (The manual does not give the colour.)
LAE AT1-5/AT2-5[166]Indicator thermostat outputThe thermostat (compressor or heating) output is on. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Icon compressorThe compressor is running. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Icon evaporator fanThe evaporator fan is running. (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]Group icon greenMJ-310E: the group is running (on).
Mitsubishi Electric City Multi (M-NET error codes)[102]Group icon blueMJ-310E block/building view: only the fan unit is running.
Full Gauge MT-514E Faston[122]LED coolingThe cooling output is on. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]LED heatingThe heating output is on. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display rEFrProcess stage: cooling. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display Hot,Process stage: heating. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]Board LED PWM1/PWM2 orangeThe PWM output is active (PWM1 heating medium pump GP1, PWM2 brine pump GP2 on the base card).
NIBE F1255 ground source heat pump[78]Board LED K1-K4 orangeThe relay is engaged (base card: K1 reversing valve, K2 brine pump, K3 heating medium pump, K4 compressor heater).
NIBE F1255 ground source heat pump[78]Heater card LED K1-K10 orangeImmersion heater card: the relay for that heater step or supply phase is engaged.
NIBE F1255 ground source heat pump[78]Inverter status LED orange steadyThe compressor is running normally.
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED cold onThe compressor (cooling) output is on. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED fans onThe evaporator fans are on. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED hot mode onHeating mode: the heater is being called. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED compressor onThe compressor relay is on. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED evaporator pumpThe evaporator pump relay is on. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED condenser pumpThe condenser pump relay is on. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED coolingCooling (refrigeration output) is on. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED fansThe fans are on. (The manual does not give the colour.)
Taylor C392/C393/C394 frozen beverage freezers[150]Icon refrigeration valveThe barrel refrigeration (liquid line) valve is open. (The manual does not give the colour.)
Taylor C392/C393/C394 frozen beverage freezers[150]PNR LED red slow flashingProduct Not Ready: the barrel is freezing down or has warmed above 0 °C in Auto, or is in Defrost/Rest/Hold; stops when the product is ready.
Full Gauge TC-900E Log[118]LED compressor onThe compressor (cooling) output is on. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]LED fanThe fan output is on. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display rEFrProcess stage: cooling. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol compressor power partly filledThe compressor runs at part load. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol compressor power fullThe compressor runs at full load. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol electric back-up heater flashingThe electric back-up heater is running (for heating or hot water, shown with that mode symbol). (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol heating modeHeating mode active. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol hot waterDomestic hot water generation active. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol cooling modeCooling mode active. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon cooling onCooling output (valve injection) is active. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon fan onThe fan output is active. (The manual does not give the colour.)
Dixell XR70CX[54]LED compressor onThe compressor is enabled. (The manual does not give the colour.)
Dixell XR70CX[54]LED fan onThe fans are enabled. (The manual does not give the colour.)
Danfoss AK-CC 550A[3]Icon compressor steadyRefrigeration/compressor relay is on. (The manual does not give the colour.)
Danfoss AK-CC 550A[3]Icon fan steadyFan relay is on. (The manual does not give the colour.)
Carel ir33[11]Icon compressor steadyCompressor is running. (The manual does not give the colour.)
Carel ir33[11]Icon fan steadyEvaporator fan is running. (The manual does not give the colour.)
Carel ir33[11]Icon continuous cycle steadyContinuous cycle (forced cooling) is running. (The manual does not give the colour.)
Carel ir33 universale[19]Icon output 1-4 steadyThe numbered output is active. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display icon cooling steadyCooling is on. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display icon fan steadyFan is running. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon cold call steadyCooling is being called for. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon fan steadyFans are called for. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon hot mode steadyHeaters are switched on (hot mode). (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon fan steadyEvaporator fans are running. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon solenoid steadyCooling solenoid valve is energised. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon compressor steadyCompressor is running. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon continuous cycle steadyContinuous cycle mode is active. (The manual does not give the colour.)
Dixell XR06CX[51]LED compressor steadyCompressor is enabled. (The manual does not give the colour.)
Dixell XR06CX[51]LED fan steadyFan output is enabled. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED compressor steadyCompressor is running. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED fan steadyFan is running. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED fast freezing steadyFast freezing cycle is running (XW60K). (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED continuous cycle steadyContinuous cycle is running. (The manual does not give the colour.)
Carel µC2SE for process chiller[59]Icon 1/2 amber steadyCompressor 1 and/or 2 is running.
Carel µC2SE for process chiller[59]Icon compressor amber steadyAt least one compressor is running.
Carel µC2SE for process chiller[59]Icon pump amber steadyCondenser pump/fan is on.
Carel µC2SE for process chiller[59]Icon fan amber steadyCondenser fan is running.
Carel µC2SE for process chiller[59]Icon heater amber steadyHeater is on.
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Symbol compressorCompressor/cooling function is active. (The manual does not give the colour.)
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Symbol fanEvaporator fan is running. (The manual does not give the colour.)
Full Gauge TC-940R[119]LED REFR steadyCompressor or liquid solenoid output is on. (The manual does not give the colour.)
Full Gauge TC-940R[119]LED FANS steadyEvaporator fan output is on. (The manual does not give the colour.)
Castel 5650E/5658E electronic oil level regulator (R744)[123]LED OIL FILLING yellow flashingOil injection with the solenoid valve open.
Castel 5650E/5658E electronic oil level regulator (R744)[123]LED OIL FILLING yellow steadyInjection cycle running, solenoid valve closed between pulses.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote operation lamp steadyUnit is running. (The manual does not give the colour.)
True Ice TI/TCIM ice machines[147]Real-time screen component greenThe component is energised.
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Auto key litFreezer is in Auto mode. (The manual does not give the colour.)
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LED compressor steadyCompressor is enabled. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Digital I/O card LED red onRelay output 1 or 2 is on.
Copeland (CPC) E2 RX/BX/CX controller[163]Output board LED onOutput is ON (closed or open path depends on the fail-safe DIP switch). (The manual does not give the colour.)
Danfoss Optyma Plus[4]LED refrigeration steadyLit while the compressor/refrigeration relay is on. (The manual does not give the colour.)
Danfoss Optyma Plus[4]LED fan steadyLit while the condenser fan runs (speed-control output or fan relay). (The manual does not give the colour.)
Carel μC2SE[8]LED compressor 1/2 steadyCompressor 1 and/or 2 is running.
Carel μC2SE[8]LED compressor (any) steadyAt least one compressor is on.
Carel μC2SE[8]LED pump/fan steadyPump/fan output is on.
Carel μC2SE[8]LED condenser fan steadyCondenser fan is active.
Dixell XR60CX[12]LED compressor (❄) steadyCompressor output is enabled. (The manual does not give the colour.)
Dixell XR60CX[12]LED fan steadyEvaporator fans are enabled. (The manual does not give the colour.)
Carel EVD evolution / EVD evolution twin[16]LED OPEN steadyDriver is opening the expansion valve. (The manual does not give the colour.)
Carel EVD evolution / EVD evolution twin[16]LED CLOSE steadyDriver is closing the expansion valve. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Compressor icon steadyCompressor is on. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Fan icon steadyEvaporator fan is on. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]LED COMPRESSOR yellow steady (3PH panel)Power is available at the compressor terminals.
Carel SmartCella / SmartCella 3PH[24]LED EVAPORATOR FAN yellow steady (3PH panel)Power is available at the evaporator fan terminals.
Danfoss AK-CC 450[32]LED refrigeration steadyRefrigeration (compressor/valve relay) is on. (The manual does not give the colour.)
Danfoss AK-CC 450[32]LED fan steadyFan relay is on. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED DO1–DO8 steadyThe corresponding relay output is on. (The manual does not give the colour.)
Danfoss AK-CC 750[36]Display LED 2 (refrigeration) steadyRefrigeration relay on (EKA display front LED). (The manual does not give the colour.)
Danfoss AK-CC 750[36]Display LED 4 (fan) steadyFan relay on (EKA display front LED). (The manual does not give the colour.)
Danfoss EKE 100[44]Valve LED red fast flashingValve is closing.
Danfoss EKE 100[44]Valve LED green fast flashingValve is opening.
Dixell XC645D[48]LED DGS compressor (1) steadyDigital scroll compressor (load 1) is on. (The manual does not give the colour.)
Dixell XC645D[48]LED load 2–4 steadyCompressor/fan step 2, 3 or 4 is on. (The manual does not give the colour.)
Dixell XC645D[48]LED DGS valve steadyThe digital scroll unloading valve is energised. (The manual does not give the colour.)
Dixell XR35CX[52]LED compressor (❄) steadyCompressor output is enabled. (The manual does not give the colour.)
Dixell XWi70K[56]LED compressor steadyCompressor is running. (The manual does not give the colour.)
Dixell XWi70K[56]LED fan steadyFan is running. (The manual does not give the colour.)
Carel µChiller[60]System pump icon steadySystem (user-side) pump is running. (The manual does not give the colour.)
Carel µChiller[60]Source pump/fan icon steadySource-side device (pump or fan) is running. (The manual does not give the colour.)
Carel µChiller[60]Compressor icon steadyCompressor is running. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]LED LLV steadyLiquid-line valve/compressor relay (relay 1 or 2) is on, section is cooling. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]LED fans steadyFan relay (relay 3) is on. (The manual does not give the colour.)
Temperzone UC8 unit controller[100]Comp light onCompressor contactor output (CMC) is switched on. (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]ON/OFF lamp green steady (wired remote)Indoor unit is in operation.
Copeland Electronic Unit Controller[116]LED compressor green steadyCompressor output is on. If lit but the compressor does not run, check the power harness and contactor wiring.
Copeland Electronic Unit Controller[116]LED fan 1 steadyCondenser fan 1 is on. (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED fan 2 steadyCondenser fan 2 is on. (The manual does not give the colour.)
Full Gauge MT-512E 2HP[120]LED cooling steadyCooling (compressor) output is on. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED valve steadyValve/LLV relay (relay 1) is on; the case is cooling. Off during MOP alarm (LLV closed). (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED fans steadyFan relay (relay 2) is on. (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Relay LEDs steadyThe associated relay is energised. (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD runningDrive running: red LED (LED1) gives short flashes of about 250 ms.
Carel PQ (True cabinets)[144]Compressor icon steadyCompressor is running. (The manual does not give the colour.)
Carel PQ (True cabinets)[144]Fan icon steadyEvaporator fan is running. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Compressor LED steadyCompressor is running. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Fan LED steadyEvaporator fan is running. (The manual does not give the colour.)
Taylor R160 frozen food dispenser[156]Compressor enabled LED steadyCompressor output is enabled. Off while the compressor still runs suggests a stuck relay or controller fault. (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Solenoid/compressor icon steadySolenoid valve/compressor output is active. (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Evaporator fan icon steadyEvaporator fan is running. (The manual does not give the colour.)
alpha innotec BWP 190S/260S DHW heat pump[168]Symbol heat pump (compressor) shownHeat pump compressor is running. (The manual does not give the colour.)
alpha innotec BWP 190S/260S DHW heat pump[168]Symbol fan shownFan (ventilation) is running. (The manual does not give the colour.)
Staff BTM5/BTM10/BTMD10/BFM10 batch freezers (with BTMD10 ice cream conservator)[194]Compressor light steadyThe conservator compressor is running. (The manual does not give the colour.)
NTF GM granular ice makers (GM360, GM600, GM1200, GM2000)[192]Rotation sensor LED orange steadyNormal ice production: the start delay is over and the rotation sensor has energised the compressor contactor while it watches the auger speed.
NTF linear (auger) granular ice makers, G series (G160, G280, G510/G500, G1000; GB and TB versions)[196]Rotation sensor LED orange steadyNormal operation: the compressor runs and the sensor sees the auger turning at the right speed.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]CLOutdoor unit running in cooling.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]HtOutdoor unit running in heating.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation steadyIndoor unit is operating. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]7-segment dot flashing (1 s)The inverter compressor is running.
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]Icon thermostat output steadyThe thermostat (compressor/solenoid) output is energised. (The manual does not give the colour.)
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]Icon fan output steadyThe evaporator fan output is energised. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol HP (compressor)The compressor is running; an F beside it means a flow switch is fitted. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol lightning (auxiliary heater)The electric auxiliary heater is running. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol house (heating)The 3-way valve is set for space heating. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol tap (hot water)The 3-way valve is set for hot water production. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol fanThe fan is running. (The manual does not give the colour.)
Carel MasterCella[7]Compressor icon steadyCompressor is running. (The manual does not give the colour.)
Carel MasterCella[7]Fan icon steadyEvaporator fan is running. (The manual does not give the colour.)
Carel MasterCella[7]Continuous cycle icon steadyContinuous cycle is running. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]Extension module LED DO1–DO8 onThe output on the extension module is energised. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol electric back-up heater with heating or hot-water symbolBack-up heater is enabled for the mode whose symbol is shown beside it. (The manual does not give the colour.)
Carel ir33+ VCC[20]Compressor icon steadyThe compressor is running. (The manual does not give the colour.)
Carel ir33+ VCC[20]Fan icon steadyThe evaporator fans are running. (The manual does not give the colour.)
Carel ir33+ VCC[20]Continuous cycle icon steadyThe continuous cycle function is running. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED fans steady (Control Thermostat)The relay set for the fans is on. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED cold (compressor) steadyThe compressor is called. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED fans steadyThe evaporator fans are on. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED hot mode steadyThe heater is called (hot mode). (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED compressor onThe compressor output is running. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED fan onThe evaporator fan is running. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED fast freezing onThe fast freezing (continuous) cycle is active. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED heater on (XW271L)XW271L only: the anti-condensing heater relay is energised. (The manual does not give the colour.)
Eliwell ID 974[13]LED compressor onThe compressor (relay 1) is running. (The manual does not give the colour.)
Eliwell ID 974[13]LED fan onThe evaporator fan is running. (The manual does not give the colour.)
Evco EV3203[107]LED compressor steadyThe compressor is running. (The manual does not give the colour.)
Evco EV3203[107]LED evaporator fan steadyThe evaporator fan is running. (The manual does not give the colour.)
Evco EV3 300 series[108]LED OUT1 steadyThe regulation output is on. (The manual does not give the colour.)
Evco EVK214[109]LED compressor steadyThe compressor is running. (The manual does not give the colour.)
Evco EVK214[109]LED evaporator fan steadyThe evaporator fan is running. (The manual does not give the colour.)
Evco EVK214[109]LED multifunction steady (u1 = 3, compressor 2)Compressor 2 is running. (The manual does not give the colour.)

The lamp shows that the compressor or the unit is running, or that there is a demand for cooling or heating.

Check: Nothing to do; compare with what the unit should be doing right now.

Status: start delay or anti-short-cycle timer

ControllerCode
Copeland Digital Compressor Controller[61]POWER LED green flashingThe two-minute anti-short-cycle timer is running after a compressor stop (only on some module versions).
Copeland PerformanceAlert diagnostic module[62]LED green flashingThe module is keeping the compressor off for the set minimum off time.
Copeland EazyCool ZX (XCM25D)[5]LED compressor flashingAnti-short-cycle delay is running before the compressor may start. (The manual does not give the colour.)
Carel MPXone[21]Icon solenoid/compressor flashingCompressor protection timers are running, or duty-setting OFF time. (The manual does not give the colour.)
Carel µRack[25]Icons 1–4 (steps) flashingA step is called on or off but is waiting for its delay times to expire. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED 1 flashingCompressor 1 is ready to start (waiting for delay). (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED 2 flashingCompressor 2 is ready to start (waiting for delay). (The manual does not give the colour.)
Dixell XR460C[53]Icon compressor 1 flashingAnti-short-cycle delay running for compressor 1. (The manual does not give the colour.)
Dixell XR460C[53]Icon compressor 2 flashingAnti-short-cycle delay running for compressor 2. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon cold call (compressor) flashingCooling is called but the compressor waits for protection time C1. (The manual does not give the colour.)
Kriwan INT69 Y Diagnose[97]LED red 3 / orange 5Reset delay running after a general (supply) error; the motor stays off until it expires.
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon continuous cycle flashingContinuous cycle is requested and waiting. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon compressor flashingCompressor is requested but waiting (protection times). (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]Message Pump X Anti-Recycle Timer ActiveThe adiabatic pre-cooler pump is held off by its anti-short-cycle timer. (The manual does not give the colour.)
Heatcraft Beacon II[30]Display dLYStart delay: the valve is opening before the compressor starts, or the 4-minute hold-off is running.
LAE AT1-5/AT2-5[166]Display RECRecovery after defrost: the room is pulling down before normal display returns. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display dEL,Process stage: start-up delay after power-on. (The manual does not give the colour.)
Danfoss Optyma iCO2[46]Display Sr1Restart delay after a high-pressure stop.
Danfoss Optyma iCO2[46]Display Sr2Restart delay after a fan motor fault.
Danfoss Optyma iCO2[46]Display Sr3Restart delay after high discharge temperature.
Danfoss Optyma iCO2[46]Display Sr4Restart delay after high receiver pressure.
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED cold flashingCooling is called but waiting for the compressor protection delay (C1). (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED compressor flashingCompressor start delay: condenser pump pre-run, or holding off because the starts-per-hour limit is reached. (The manual does not give the colour.)
RDM ML Controller case controller[134]Display recControl state: recovery (pulling down after defrost or an off period). (The manual does not give the colour.)
Taylor R280 fry dispenser[158]Display rF OFF flashingThe compressor cannot restart until the 2-minute short-cycle delay has passed. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display dEL,Process stage: start-up delay after power-on. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display Fan,Process stage: fan delay after defrost. (The manual does not give the colour.)
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Symbol start-to-start intervalThe minimum time between compressor starts has not yet expired. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon cooling blinkingA delay is running before the cooling output changes. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon fan blinkingA fan delay is running. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon defrost blinkingA defrost-related delay is running. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon AUX blinkingA delay is running for the auxiliary relay. (The manual does not give the colour.)
Dixell XR70CX[54]LED compressor flashingAnti-short-cycle delay is running. (The manual does not give the colour.)
Dixell XR70CX[54]LED fan flashingFan delay after defrost is running. (The manual does not give the colour.)
Carel ir33[11]Icon compressor flashingCompressor start is being held back by protection timers. (The manual does not give the colour.)
Carel ir33[11]Icon fan flashingFan start is blocked by an external disable or a running procedure (e.g. post-drip delay). (The manual does not give the colour.)
Carel ir33[11]Icon defrost flashingDefrost is requested but held back by an external disable or a running procedure. (The manual does not give the colour.)
Carel ir33[11]Icon continuous cycle flashingContinuous cycle is requested but blocked, e.g. by the minimum compressor off time. (The manual does not give the colour.)
Carel ir33 universale[19]Icon output 1-4 flashingThe numbered output is requested but delayed by protection times, an external disable or another procedure. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon solenoid flashingSolenoid should open but a delay or protection prevents it. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon compressor flashingCompressor should run but a delay or protection prevents it. (The manual does not give the colour.)
Dixell XR06CX[51]LED compressor flashingAnti-short-cycle delay is running (parameter AC). (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED compressor flashingAnti-short-cycle delay is running (also flashes with the fan LED while programming). (The manual does not give the colour.)
Carel µC2SE for process chiller[59]Icon 1/2 amber flashingCompressor start has been requested and is waiting.
Carel µC2SE for process chiller[59]Icon pump amber flashingPump/fan start has been requested and is waiting.
Carel µC2SE for process chiller[59]Icon chiller mode amber flashingChiller mode has been requested and is waiting.
Kriwan INT69 PYF Diagnose[95]LED red 2 / orange 4Phase monitoring: switch-back delay is running.
Castel 5650E/5658E electronic oil level regulator (R744)[123]LED OIL GOOD green flashingOil level is low but injection has not started yet.
Temperzone UC6 unit controller[135]DS1 digit 1Anti-rapid-cycle timer is blocking a compressor start. (The manual does not give the colour.)
Temperzone UC6 unit controller[135]DS1 digit 2Minimum run timer is keeping the compressor on. (The manual does not give the colour.)
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LED compressor flashingAnti-short-cycle delay is running (parameter AC). (The manual does not give the colour.)
Carel μC2SE[8]LED compressor 1/2 flashingCompressor start is requested but waiting (timings/protection).
Carel μC2SE[8]LED pump/fan flashingPump/fan start is requested but not yet running.
Dixell XR60CX[12]LED compressor (❄) flashingAnti-short-cycle delay is running; compressor waits. (The manual does not give the colour.)
Dixell XR60CX[12]LED fan flashingFan delay after defrost is running. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Compressor icon flashingCompressor start is waiting, delayed or blocked by protection times. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Fan icon flashingFan start is waiting for protection times or another procedure. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Defrost icon flashingDefrost is requested but delayed by protection times or another procedure. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Continuous cycle icon flashingContinuous cycle is requested but delayed by protection times. (The manual does not give the colour.)
Dixell XC645D[48]LED load 1–4 flashing 1 HzThe load is waiting to start (safety timers). (The manual does not give the colour.)
Dixell XR35CX[52]LED compressor (❄) flashingAnti-short-cycle delay is running. (The manual does not give the colour.)
Dixell XWi70K[56]LED compressor flashingAnti-short-cycle delay is running (also flashes, together with the fan LED, in programming mode). (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED compressor green flashingAnti-short-cycle delay is running.
Copeland Electronic Unit Controller[116]LED compressor green off with demandCompressor is off: pressure above cut-in setting or jumper cable not connected.
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Compressor LED flashingCompressor start delayed, in protection time or blocked. (The manual does not give the colour.)
Taylor R160 frozen food dispenser[156]Compressor enabled LED flashingAnti-short-cycle delay is running. (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Solenoid/compressor icon flashingProtection timings are running before the output can switch. (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Defrost icon flashingDefrost is waiting to start. (The manual does not give the colour.)
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor green blink 1 Hz + alarm 1 redGas gone; alarm 1 resets automatically after about 10 s.
NTF GM granular ice makers (GM360, GM600, GM1200, GM2000)[192]Delay timer lamp blinkingAll safety devices are closed and the gear motor runs; the delay timer is counting down (about 8–10 minutes) before it starts the compressor. (The manual does not give the colour.)
Staff BTM5/BTM10/BTMD10/BFM10 batch freezers (with BTMD10 ice cream conservator)[194]Compressor light flashingThe compressor wants to start but waits for the set start delay to run out. (The manual does not give the colour.)
NTF linear (auger) granular ice makers, G series (G160, G280, G510/G500, G1000; GB and TB versions)[196]Rotation sensor LED orange blinkingAll safety devices are closed and the gear motor turns; the 8-minute start delay is running before the compressor is allowed to start. Switching off and on restarts the delay.
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon defrost flashingDefrost is requested and waiting to start. (The manual does not give the colour.)
Carel MasterCella[7]Compressor icon flashingCompressor start is held back by its safety timers. (The manual does not give the colour.)
Carel MasterCella[7]Fan icon flashingFan start is blocked by an external disable or a running procedure. (The manual does not give the colour.)
Carel MasterCella[7]Defrost icon flashingDefrost is requested but blocked by an external disable or a running procedure. (The manual does not give the colour.)
Carel MasterCella[7]Continuous cycle icon flashingContinuous cycle is requested but blocked, e.g. by the minimum compressor off time. (The manual does not give the colour.)
Carel ir33+ VCC[20]Compressor icon flashingCompressor start is requested but held back by protection times. (The manual does not give the colour.)
Carel ir33+ VCC[20]Fan icon flashingFan start is requested but delayed by protection times or another procedure. (The manual does not give the colour.)
Carel ir33+ VCC[20]Defrost icon flashingDefrost is requested but delayed by protection times or another procedure. (The manual does not give the colour.)
Carel ir33+ VCC[20]Continuous cycle icon flashingContinuous cycle is requested but held back by protection times. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED compressor flashingAnti-short-cycle delay is counting down; also flashes in programming mode. (The manual does not give the colour.)
Eliwell ID 974[13]LED compressor flashingCompressor start is held back by a delay, protection or blocked enabling. (The manual does not give the colour.)
Evco EV3203[107]LED compressor blinkingCompressor protection delay is running, or the setpoint is being changed. (The manual does not give the colour.)
Evco EV3203[107]LED evaporator fan blinkingThe evaporator fan is held off (fan stop after defrost). (The manual does not give the colour.)
Evco EV3 300 series[108]LED OUT1 blinkingThe output's protection delay is running. (The manual does not give the colour.)
Evco EVK214[109]LED compressor blinkingCompressor protection is running (C0, C1, C2, i7) or the setpoint is being changed. (The manual does not give the colour.)
Evco EVK214[109]LED evaporator fan blinkingThe evaporator fan is held off (F3). (The manual does not give the colour.)
Evco EVK214[109]LED multifunction blinking (u1 = 3, compressor 2)Compressor 2 start delay is running (C9). (The manual does not give the colour.)

A timer is running (anti-short-cycle or minimum off time) before the compressor may start again.

Check: Wait for the timer; if it never ends, check the controller and its settings.

Status: power on, standby or waiting

ControllerCode
Copeland Digital Compressor Controller[61]POWER LED green steady24 VAC supply is present at the controller's power terminals.
Copeland PerformanceAlert diagnostic module[62]LED green steadySupply voltage is present at the module's power terminals.
Danfoss Optyma Plus Module B Plus (P02)[45]LED1 red steadyPower LED: Module B Plus has supply voltage.
Kriwan INT69 F Diagnose[94]LED green steadyNo fault; the machine is stopped and ready to run.
Kriwan INT69 PYF Diagnose[95]LED green steadyNo fault; the machine is stopped and ready to run.
Kriwan INT69 YF Diagnose[98]LED green steadyNo fault; the machine is stopped and ready to run.
Kriwan INT69 UY Diagnose[96]LED green steadyNo fault; the machine is stopped and ready to run.
Kriwan INT69 Y Diagnose[97]LED green steadyNo fault; the machine is stopped and ready to run.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]LED yellow steadyKB drive ST LED: drive is in stop mode.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]PWR LED green steadyKB drive PWR LED: bus and logic power supply is OK.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller POWER LED green steadyCondenser controller: supply power is connected.
Danfoss Gas Sensor DGS[71]Keypad LED green steadyKeypad status LED: operating voltage is present.
Danfoss AK-PC 781A[37]LED Power onController has supply voltage. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]Extension module LED power onExtension module has supply voltage. (The manual does not give the colour.)
Danfoss Optyma Plus Module B Plus (P02)[45]LED1 offModule B Plus has no supply voltage.
Bitzer VARIPACK FDU+ .. FKU+ (frequency inverter)[57]Signal lamp H6 (ready to operate) onCompressor/inverter is ready to operate. (The manual does not give the colour.)
AHT plug-in cases with Danfoss controller (Paris, Ibiza, Malta, Manhattan)[85]Decimal point (comma) onlyCooling has been switched off with the SC button (standby). (The manual does not give the colour.)
LG Multi V 5 VRF outdoor units[77]Outdoor PCB LED blinkingOutdoor PCB has power and is running; if not blinking check supply and PCB. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]Right decimal point on (standby)Controller is in standby (when L7 = 2).
Störk-Tronic ST121 / ST501 / ST551[93]Right decimal point flashing (standby)Controller is in standby (when L7 = 3).
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED control functions shutdown onControl and alarms are switched off; the unit only shows temperature (OFF alternates on display). (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED control functions OFF onControl functions are switched off; the controller only indicates temperature. (The manual does not give the colour.)
Temperzone UC7 unit controller[101]Power light onController has 230 V supply; if off check mains, breaker, board fuse and phase rotation relay. (The manual does not give the colour.)
Temperzone UC7 unit controller[101]Display flashing dotUnit on but no compressor demand (COMP input/thermostat/BMS signal absent). (The manual does not give the colour.)
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red dark / yellow lit / green darkReset mode: yellow on for about 6 s after power-up.
ActronAir Aires and Advance 19–25 kW[137]VSD LEDs red blink / yellow dark / green darkStandby: red flashes once about every 1 s.
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Blank display with decimal pointControl has been switched off with the power button (shows oFF first). (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]STANDBY button litStandby mode: hopper and barrel kept below 4.4 °C. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]STOP button litMachine is off. (The manual does not give the colour.)
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D501 (red) onIndoor main microcomputer is running (on from power-up).
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D403 (red) onRemote controller power supply is on.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display CPUnit switched off remotely. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Power LED greenThe controller has supply voltage.
Danfoss AK-PC 782A/782B[38]LED Power onThe controller has 24 V supply. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]Module LED supply onThe extension module has supply voltage. (The manual does not give the colour.)
Danfoss VLT HVAC Basic Drive FC 101[70]LED On greenThe drive has supply voltage.
Danfoss VLT FC 103[14]LED On green steadyThe drive has supply voltage (mains, DC bus or external 24 V).
Carel Heos[18]Board power LED green steadyThe Heos board has supply voltage.
Carel Heos[18]Power+ LED POWER green steadyThe Power+ compressor drive is powered.
LAE AT1-5/AT2-5[166]Display OFFThe controller is in stand-by. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Display oFFThe controller is in stand-by (refrigeration off, lights still powered). (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]Group icon redMJ-310E: the group is stopped (off).
Full Gauge MT-514E Faston[122]Display OFF,Control functions are switched off. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display ----Process stage: control functions off. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]Board LED Power green steadyBase, input or accessory card: 12 V supply is OK.
NIBE F1255 ground source heat pump[78]Comm board LED INV greenCommunication board AA123 gets supply from the inverter.
NIBE F1255 ground source heat pump[78]Comm board LED PWR greenCommunication board AA123 gets voltage from the base card.
NIBE F1255 ground source heat pump[78]Inverter power LED orangeThe inverter is powered (16 kW model only).
Danfoss Optyma iCO2[46]Display ----The display is waiting for communication with the unit controller.
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED stand-by flashingThe controller is in stand-by and all outputs are off. (The manual does not give the colour.)
Carel pRack pR300[22]Terminal LED greenThe pRack controller has supply voltage.
Carel pRack pR300[22]Board LED yellowPower is connected to the pRack board.
RDM ML Controller case controller[134]Display OFFThe case is switched off. (The manual does not give the colour.)
Taylor Icetro ISI-161TH/ISI-161TI[154]STAND-BY lightStand-by mode: mix in barrel and hopper is only kept cold. (The manual does not give the colour.)
Taylor R280 fry dispenser[158]Power lightThe dispenser is switched on. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]LED control functions shutdownControl functions are switched off; the display may go dark with only this light on. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display OFF,Control routines are switched off. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display ----Process stage: control functions off. (The manual does not give the colour.)
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]OPERATION lamp green flashing 1 HzPower has been switched on or returned after a power failure; flashing stops when START/STOP is pressed.
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol compressor power emptyThe compressor is not running. (The manual does not give the colour.)
Bitzer VARIPACK FMY+/FMU+ .. FSW+ (frequency inverter)[58]Display INHIBITThe STO (safe torque off) input is de-energised, so the inverter will not start; if STO is energised and this stays, the STO input is faulty. (The manual does not give the colour.)
Carel pRack pR300T (transcritical CO2)[23]Terminal LED green steadyThe pRack is powered.
Carel pRack pR300T (transcritical CO2)[23]Board LED yellow steadyPower is connected to the pRack board.
Sanhua SEC60x[31]LED POWER steadyController is powered. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Controller LED green steadyController is powered.
Danfoss Optyma control AK-RC 113[39]Icon stand-by flashingPanel is in stand-by; outputs are disabled. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Display In5 alternatingStand-by set from the remote digital input. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]All LEDs on at power-upNormal lamp test for a few seconds after switching on, with a short beep. (The manual does not give the colour.)
Danfoss EKE 1A/1B/1C/1D[43]Status LED green steadyController is powered.
Danfoss AK-RC 251[47]Icon stand-by steadyStand-by is on; regulation is paused. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon stand-by flashingControlled shutdown before stand-by is in progress. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED ON/OFF steadyUnit is in stand-by (display shows OFF); all relays are off. (The manual does not give the colour.)
RDM DMTouch / miniDM[91]LED power steadyUnit is powered. (The manual does not give the colour.)
Castel 5650E/5658E electronic oil level regulator (R744)[123]LED POWER green steadyRegulator is correctly powered.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED D02 steadyPower on, microprocessor running; also lit while a DN code is being set.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote SETTING flashing at power-onInitial settings in progress; wait until it disappears. (The manual does not give the colour.)
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Standby keys litFreezer is in Standby (e.g. after a completed heat cycle). (The manual does not give the colour.)
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]All LEDs on at power-upLamp test while the control initialises. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Main board LED D1 green steadyE2 is booting.
Copeland (CPC) E2 RX/BX/CX controller[163]Boot LED D18 green steadyE2 is booting.
Copeland (CPC) E2 RX/BX/CX controller[163]PIB LED green steadyPower is applied to the processor interface board.
Pego 202BASE electronic board[167]Display In5 alternatingStand-by set from the remote digital input. (The manual does not give the colour.)
Carpigiani AES PSP[15]All LEDs on at power-upLamp test for a few seconds after switching on. (The manual does not give the colour.)
Carel EVD evolution / EVD evolution twin[16]LED OPEN + CLOSE flashingDriver disabled: waiting for the initial configuration to be completed. (The manual does not give the colour.)
Carel EVD evolution / EVD evolution twin[16]LED POWER green steadyDriver is powered.
Carel EVD evolution / EVD evolution twin[16]LED POWER green offDriver has no power supply.
Carel SmartCella / SmartCella 3PH[24]LED POWER green steady (3PH panel)Auxiliary circuit is powered (QF2 and QS1 on).
Carel SmartCella / SmartCella 3PH[24]LED POWER green off (3PH panel)Auxiliary circuit has no power; check QF2 and main switch QS1.
Danfoss AK-CC 750[36]LED Power steadyController module has supply voltage. (The manual does not give the colour.)
Danfoss EKE 100[44]LED power green steadyController is powered.
Danfoss EKE 100[44]LED alarm red fast flashing (first 5 s)Initial boot during the first 5 seconds after power-up.
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]LED green steadyOperating voltage is present.
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]LED yellow slow flashingSensor is warming up after power-on.
Temperzone UC8 unit controller[100]Power light onController has 230 V AC mains. (The manual does not give the colour.)
Temperzone UC8 unit controller[100]Display dash slowly flashingUnit is OFF by the remote on/off input (input open circuit). (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Indoor board LED1 steadyControl power is supplied to the indoor microprocessor (should always be lit). (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Indoor board LED2 steadyPower is supplied to the remote controller (only on the unit with refrigerant address 0). (The manual does not give the colour.)
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD reset modeDrive reset: yellow LED (LED2) on for about 6 seconds.
ActronAir Advance / VCC / Genesis 13–17 kW[136]Aires VSD standbyDrive in standby: red LED (LED1) flashes once for about 1 second.
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]All LEDs on at power-upLamp test for a few seconds after switching on. (The manual does not give the colour.)
Taylor R160 frozen food dispenser[156]On/Off switch litMain power to the dispenser is on. (The manual does not give the colour.)
Krack KR-A2L unit cooler (KE2 Evap leak sensor alarms)[164]Copeland sensor PWR green blink 1 Hz + red LEDs on (start-up)Initialisation after power-up; relays open until finished.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]BlankDisplay blank: outdoor unit idle (stopped), no fault.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Timer 3 s on / 1 s offOpposite operation mode: this unit asks for cooling while the system runs heating (or the reverse), so it waits. Set all units on the same outdoor unit to the same mode. (The manual does not give the colour.)
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]Icon stand-by steadyThe controller is in stand-by and does not regulate. (The manual does not give the colour.)
Dixell XWi70K[56]LED ON/OFF steadyController is in stand-by: relays off and control stopped; display shows OFF. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED stand-by flashingThe controller is in stand-by and the outputs are off. (The manual does not give the colour.)
Pego 202BASE electronic board[167]All LEDs on at power-upLamp test for a few seconds after power is switched on. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]ON/OFF button LED onThe controller is switched off with the ON/OFF key; all relays and control are stopped, light and AUX keys still work. (The manual does not give the colour.)
Eliwell ID 974[13]All LEDs and display flashing at power-upLamp test for a few seconds after switching on; normal. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]MODBUS 40 LED VCC steadyMODBUS 40 supply voltage is OK. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED BATT steadySMS 40 backup battery has voltage. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED 4 steadySMS 40 12 V supply is OK. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED VCC steadySMS 40 supply voltage is OK. (The manual does not give the colour.)
Evco EV3 300 series[108]LED on/stand-by steadyThe controller is switched off (stand-by). (The manual does not give the colour.)
Evco EV3 300 series[108]LED on/stand-by blinkingThe controller is being switched off. (The manual does not give the colour.)
Evco EVK214[109]LED on/stand-by steadyThe controller is in stand-by. (The manual does not give the colour.)

The unit has supply voltage but is waiting: standby, no demand or waiting for a signal.

Check: Check the demand signal, the setpoint and any enable or remote on/off input.

Status: information

ControllerCode
Copeland CoreSense Protection (Discus)[63]LED red/green flashing (RS485)The RS485 polarity LEDs on the board flash when the network wiring polarity is correct.
Copeland Stream condensing units (Next Gen CoreSense)[27]LED orange steadyThe compressor is running in emergency mode.
Copeland Stream condensing units (Next Gen CoreSense)[27]LED red steadyThe CoreSense module is in parameter-setting mode.
Copeland ZSI scroll condensing units[28]LED2+LED3 1 flashSwitching between automatic mode and manual EXV test mode succeeded (also shown when entering or leaving manual mode).
Copeland ZSI scroll condensing units[28]LED2 flashingManual EXV test: the valve is opening.
Copeland ZSI scroll condensing units[28]LED2 steadyManual EXV test: the valve is fully open.
Copeland ZSI scroll condensing units[28]LED3 flashingManual EXV test: the valve is closing.
Copeland ZSI scroll condensing units[28]LED3 steadyManual EXV test: the valve is at its minimum opening.
Kriwan INT69 F Diagnose[94]LED orange steadyNo fault and the machine is ready, but the set service interval has run out.
Kriwan INT69 F Diagnose[94]LED orange flashingNo fault and the machine is running, but the set service interval has run out.
Kriwan INT69 F Diagnose[94]LED red steady (Temp.)The protection relay is in parameter-setting mode.
Kriwan INT69 F Diagnose[94]LED red fast flashing (Temp.)The bootloader is active, e.g. while firmware is loaded or when firmware is missing.
Kriwan INT69 PYF Diagnose[95]LED orange steadyNo fault and the machine is ready, but the set service interval has run out.
Kriwan INT69 PYF Diagnose[95]LED orange flashingNo fault and the machine is running, but the set service interval has run out.
Kriwan INT69 YF Diagnose[98]LED orange steadyNo fault and the machine is ready, but the set service interval has run out.
Kriwan INT69 YF Diagnose[98]LED orange flashingNo fault and the machine is running, but the set service interval has run out.
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 9Calibration of the rotor position sensor is in progress.
ebm-papst EC fans with status LED (K3G310, W3G910)[74]LED orange 16The shake-loose function is active.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller FAULT LED red 2 HzCondenser controller: download or start-up in progress, not yet ready for normal operation.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller bus LED green 2 HzCondenser controller SA bus, FC bus or Modbus LED: data is being transmitted on that bus.
Danfoss Gas Sensor DGS[71]LED yellow flashingThe sensor is in special/service mode (e.g. set from the Service Tool); it times out after about 15 minutes.
Danfoss Gas Sensor DGS[71]Keypad LED yellow slow flashingKeypad status LED: the sensor is warming up.
Danfoss Gas Sensor DGS[71]Keypad LED yellow fast flashingKeypad status LED: special mode is active.
Danfoss Gas Sensor DGS[71]All LEDs on (LCD check)LCD function check from the menu: all LEDs light for about two seconds.
Heatcraft A2L Refrigerant Detection System (unit coolers)[79]LED green flashingAfter power-up the A2L controller initializes the leak sensors; this takes about 5 minutes.
Mitsubishi Electric SUZ-KA VA4 outdoor units[103]9 flashesInverter check mode has started because the compressor connector is unplugged (service test).
Danfoss ERC 21X[1]Icon night mode (moon) steadyNight/energy-saving mode is active. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED bar onPressure is displayed in bar. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED bar flashingController is in programming mode. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED PSI onPressure is displayed in psi. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED PSI flashingController is in programming mode. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED service onThe service menu is being browsed. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED service flashingThe fast-access menu is open. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED alarm on (menu)The alarm menu is being browsed. (The manual does not give the colour.)
Carel EVD ice / EVD mini[17]Start/stop LED (decimal point) offStart/stop digital input is open; control is stopped. (The manual does not give the colour.)
Carel MPXone[21]Icon light onCabinet light is on. (The manual does not give the colour.)
Carel MPXone[21]Icon AUX onAuxiliary output is active. (The manual does not give the colour.)
Carel MPXone[21]Icon clock onTime scheduler is active. (The manual does not give the colour.)
Carel MPXone[21]Icon energy saving onSmooth Lines energy-saving function is active. (The manual does not give the colour.)
Carel MPXone[21]Icon service onMaintenance is requested. (The manual does not give the colour.)
Carel MPXone[21]Icon HACCP onHACCP monitoring is active. (The manual does not give the colour.)
Carel MPXone[21]Icon + (generic function) onA configured generic function is active. (The manual does not give the colour.)
Carel MPXone[21]PRG button LED onMain screen or programming mode. (The manual does not give the colour.)
Carel MPXone[21]UP/DOWN button LED flashingA parameter value is being set. (The manual does not give the colour.)
Carel µRack[25]Icon MANUFACTURER onManufacturer parameters are being configured. (The manual does not give the colour.)
Carel µRack[25]Icon MANUFACTURER flashingAt least one device is in manual operation (times and rotation ignored). (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED °C onValues are shown in °C. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED °C flashingController is in programming mode. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED service onThe service menu is being browsed. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED service flashingThe fast-access menu is being browsed. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED ! flashing (upper)The alarm menu is being browsed. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Status quick flashAnswer from the gateway after network installation (up to 10 min). (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Service Tool / LON / I/O extension / Display onCommunication active with Service Tool, LON network, AK-CM 102 extension or display respectively. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Service Pin onThe Service Pin switch has been activated (network installation). (The manual does not give the colour.)
Dixell XEV12D[49]LED valve offExpansion valve is closed.
Dixell XEV12D[49]LED communication blinkingSerial communication is present.
Dixell XEV12D[49]LED communication offNo serial communication.
Dixell XR460C[53]Icon °C onTemperatures shown in °C. (The manual does not give the colour.)
Dixell XR460C[53]Icon °F onTemperatures shown in °F. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon door/cold room light onCold room light is on. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon door/cold room light flashingDoor switch is active (door open) and cold room light is on. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon real-time clock onDefrosts by real-time clock are enabled. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Decimal point flashingNight mode is active. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon AUX onAuxiliary relay is on (when AU1 is set to ±2 or ±3). (The manual does not give the colour.)
Secop SLV controller 105N46xx[81]LED Service onController is in service mode/service level. (The manual does not give the colour.)
LG Multi V 5 VRF outdoor units[77]Main PCB 7-segment LED shows 88Auto addressing or auto pipe detection is running. (The manual does not give the colour.)
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED functions lock onKeypad/functions are locked against changes. (The manual does not give the colour.)
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED temperature unit onShows the selected temperature unit. (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED functions lockdown onFunctions are locked against changes. (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED temperature unit onShows the selected temperature unit. (The manual does not give the colour.)
Goodman DX20VC inverter condensing unit[105]Red communications LED 2 flashesOut-of-box reset after control power-up or LEARN button pressed.
Temperzone UC7 unit controller[101]TZT-100 satellite dish symbolThermostat is communicating with the UC7. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED on-line (green) offNo network attached.
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]ECO indicator onEnergy-saving (ECO) mode is active. (The manual does not give the colour.)
Dixell XR/XW (True cabinets)[145]Icon compressor (snowflake) flashingSet point/programming mode is open. (The manual does not give the colour.)
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]Product light flashingProduct not at serving viscosity (initial freeze-down, defrost or power-saver mode). (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]Draw handle icon in lower positionDraw valve is open or not fully closed. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]Padlock iconKeypad is locked. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]HEAT button litHeat treatment cycle is running; do not draw product or disassemble. (The manual does not give the colour.)
Taylor 736 soft serve freezer[153]WASH button litWash mode: beater motor running. (The manual does not give the colour.)
Taylor R200 fry dispenser[157]Load size LED onShows the basket load size currently selected; drum turns until target weight is reached. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon lights onCase lights are on. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon alarms log onAlarms have been logged; press to open the log. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon AUX onAuxiliary output is active. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon clock onTime scheduler is active. (The manual does not give the colour.)
BAC Vertex evaporative condenser (Ziehl-Abegg ECblue EC fans)[173]Panel OVERRIDE light (amber) onOverride switch is ON: fans follow the control signal despite the alarm.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D501 (red) flashing every 5 sDISP mode is active.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D501 (red) flashing every 1 sFunction select (EEPROM) setting in progress.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D503 (yellow) onMain bus communication with the central controller (about 5 s).
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]D504 (green) flashingSub bus communication with the remote controller or between group master and follower units.
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]Operation lamp (green) off during self-cleanSelf-clean is running after cooling; operation lamp goes off though the fan still runs.
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Running lamp 1 + timer onIndoor units on a multi system ask for conflicting modes (mode conflict). (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display CLFilter cleaning reminder (15 s at power-on) or active clean running. (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display FP8 °C heating (frost protection) mode. (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display FCForced cooling mode. (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display APWi-Fi connection in AP mode. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display --- briefly, then temperatureManual defrost refused: the 24-hour defrost block is active. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display StP / A1-A4The set application (A1-A4) is being shown or changed. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display AdrBus address setting mode. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display tstSECOP controller electronics in test mode. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]LED energy optimizationEnergy optimisation (night setback / eco) is active. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display ALAThe alarm button was pressed; the first alarm code follows. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display LocThe keypad is locked; hold up and down arrows 3 s to unlock. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display UnLThe keypad has been unlocked. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display PSA password is needed to enter the menu. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display FanAppliance cleaning started: only the fans are running. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display OFFCleaning mode active (appliance can be cleaned) or the main switch is set to off. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display SErThe main switch is set to service / manual operation. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Status quick flashAnswer received from the network gateway after network installation (lasts up to 10 min). (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Service ToolCommunication with the AK-ST 500 service tool. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED I/O ExtensionCommunication with the AK-CM 102 module. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED LANCommunication on the IP network. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED DisplayCommunication with the display on the RJ11 plug. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Service PinThe Service Pin switch has been pressed (network address sent). (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Alarm steadyAn active alarm has been acknowledged. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]AK-XM 204B LED override onThe relay is overridden by its manual switch (ON or OFF position). (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]HMI fan dot orangeFan status Manual: the fan is in manual mode.
BAC TrilliumSeries adiabatic cooler TRF[174]Message Cycle of Concentration DrainThe sump is being drained to flush out minerals. (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]Message Water Usage DisabledThe unit is not allowed to enter adiabatic (wet) operation. (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]Message Night Quiet Mode ActiveNight quiet mode is active (fan speed limited). (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]Message Night Dry Mode ActiveNight dry mode is active. (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]Message Schedule Dry Mode ActiveScheduled dry mode is active. (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]Message Emergency Mode ActiveEmergency mode: fan speed is fixed at a preset level instead of PLC control. (The manual does not give the colour.)
Heatcraft Beacon II[30]Display tStTest mode is active.
Heatcraft Beacon II[30]Display SErService mode: the service switch in the condensing unit has shut the system off.
Heatcraft Beacon II[30]Display LocThe board is locked; settings cannot be changed.
Heatcraft Beacon II[30]Display UnLThe board settings have been unlocked.
Copeland PerformanceAlert diagnostic module[62]LED yellow code after power-upFor one minute after power-up the module repeats the last alert code from before the power loss.
Copeland EXD-SH1/2[26]LED instant values modeManual instant-value display mode is active. (The manual does not give the colour.)
Danfoss VLT HVAC Basic Drive FC 101[70]LED Com. yellow flashingFieldbus communication is taking place.
Danfoss VLT HVAC Basic Drive FC 101[70]LED above Hand OnThe drive is in hand (local) mode, controlled from the keypad. (The manual does not give the colour.)
Carel Heos[18]Icon lightMain screen: the cabinet light output is on. (The manual does not give the colour.)
Carel Heos[18]Icon continuous cycleMain screen: continuous cycle (forced cooling) is active. (The manual does not give the colour.)
Carel Heos[18]Icon anti-sweat heatersMain screen: the anti-sweat (rail) heaters are on. (The manual does not give the colour.)
Carel Heos[18]Alarm LED red steadyThe alarm has been seen and the buzzer muted, or an auto-reset alarm is still shown; check the alarm list and reset.
Carel Heos[18]Power+ LED DATA yellowSerial communication with the Power+ drive is active.
Krack microchannel air-cooled condenser (controller and KB fan drive)[106]Controller bus LED offSA bus, FC bus or Modbus LED off: no data is being sent on that bus.
LAE AT1-5/AT2-5[166]Indicator auxiliary outputThe AUX output is on (defrost, light, alarm or on/stand-by, as set by OAU). (The manual does not give the colour.)
LAE AT1-5/AT2-5[166]Display LOCKeypad lock setting in the info menu (YES = buttons locked). (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Icon 2nd parameter setThe second parameter set (e.g. a different setpoint) is active. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Display LocKeypad lock menu; YES means locked. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Display inF flashingBR+/CD25/TM: entering the info menu. (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]× on group icon (status area)MJ-310E: operation from the local remote controller is prohibited. (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]Filter in yellow frameMJ-310E: filter sign, the filter needs cleaning (shown in the filter reset view).
Mitsubishi Electric City Multi (M-NET error codes)[102]Operation mode flashing, red backgroundMJ-310E: the indoor unit is in operation-prohibited state (mode conflict) and stays stopped; change the operation mode to clear it.
Mitsubishi Electric City Multi (M-NET error codes)[102]Schedule mark top leftMJ-310E: a schedule is set for the group. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]LED functions lockFunctions (keypad changes) are locked. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display inibThe alarm buzzer has been silenced. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display OpEnThe door is open. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display LOC, OnFunctions have been locked. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display LOC, OFFFunctions have been unlocked. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]Board LED Com green flashingIrregular flashing: communication is taking place.
NIBE F1255 ground source heat pump[78]Comm board LED COM green flashingCommunication with the inverter is taking place.
Danfoss Optyma iCO2[46]Display S25Manual mode (r12 = -1).
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED light onThe cold room light is on. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED light flashingThe door switch has been activated (door open). (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED auxiliary onThe AUX relay is being called. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]Decimal point flashingNight mode is active. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]All LEDs on at power-upLamp test for a few seconds after switching on, with a beep. (The manual does not give the colour.)
Carel pRack pR300[22]Terminal LED red steadyAlarms are still present but have been acknowledged; check the alarm list.
RDM Mercury AC and roof top unit controllers[130]LED timer onThe 7-day timer has the unit switched on. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED on-line offNo network is attached. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED on-line flashingThe controller is trying to log on to the network. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED on-line steadyThe controller is on-line on the network. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED HACCP onSet remotely by the network (Data Builder HACCP command). (The manual does not give the colour.)
RDM ML Controller case controller[134]LED lightsThe case lights are on. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED network offNo network is attached.
RDM ML Controller case controller[134]LED network flashingThe controller is trying to log on to the network.
RDM ML Controller case controller[134]LED network steadyThe controller is on-line.
RDM ML Controller case controller[134]LED HACCPSet on or flashing remotely by the network (HACCP command). (The manual does not give the colour.)
Taylor R280 fry dispenser[158]Basket size LED litShows which basket load size is selected for that side. (The manual does not give the colour.)
Taylor R280 fry dispenser[158]Display [bYP] flashing bracketsBasket sensor bypass mode is being set. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]LED compressor fast flashingFast freezing mode: the cooling output runs continuously. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]LED functions lockdownFunctions (keypad changes) are locked. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display eCO,Running on the economic setpoint. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display OpEnThe door is open (digital input). (The manual does not give the colour.)
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]TIMER lamp orange flashing 5 Hz (service mode)Remote-controller self-diagnosis (service mode) is running.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]Outdoor PCB LEDs rapid flashing 5/sLatest-error display (selected with SW81): same LED combinations as the current-error table but flashing rapidly; shows the last error that stopped the compressor.
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol noise reductionRunning in reduced-noise mode. (The manual does not give the colour.)
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol eco modeEnergy-saving hot water mode. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon light onThe light relay is on. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon AUX onThe auxiliary relay is on. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon energy savingEnergy saving is active. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon multimasterMultimaster (SEC) is enabled: the keyboard can command other boards over the LAN. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon clockTime or clock value shown. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Units °C/bar blinkingProgramming mode. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Board LED green onThe LAN connection between boards is working.
Dixell XM669K/XM679K[50]Display PonKeyboard unlocked. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Display PoFKeyboard locked. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Display rStAlarm reset: alarm output switched off. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Display noP / nPNot present in the configuration. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Display nAValue not available. (The manual does not give the colour.)
Dixell XR70CX[54]LED continuous cycle onContinuous (fast pull-down) cycle is running. (The manual does not give the colour.)
Dixell XR70CX[54]LED energy saving onEnergy saving is active. (The manual does not give the colour.)
Dixell XR70CX[54]LED light onThe light output is on. (The manual does not give the colour.)
Dixell XR70CX[54]LED aux onThe auxiliary relay is on. (The manual does not give the colour.)
Dixell XR70CX[54]LED °C/°F flashingProgramming mode. (The manual does not give the colour.)
Dixell XR70CX[54]Display PonKeyboard unlocked. (The manual does not give the colour.)
Dixell XR70CX[54]Display PoFKeyboard locked. (The manual does not give the colour.)
Dixell XR70CX[54]Display noPNo parameter in Pr1, or the selected probe is not enabled. (The manual does not give the colour.)
Carel ir33[11]Icon AUX steadyAuxiliary output configured as AUX is on. (The manual does not give the colour.)
Carel ir33[11]Icon AUX flashingAnti-sweat heater function is active. (The manual does not give the colour.)
Carel ir33[11]Icon clock steadyAt least one timed defrost is programmed; at power-up it lights briefly if a real-time clock is fitted. (The manual does not give the colour.)
Carel ir33[11]Icon light steadyAuxiliary output configured as LIGHT is on. (The manual does not give the colour.)
Carel ir33[11]Icon light flashingAnti-sweat heater function is active (not in firmware 3.6). (The manual does not give the colour.)
Carel ir33[11]Icon HACCP steadyHACCP monitoring is enabled. (The manual does not give the colour.)
Carel ir33 universale[19]Icon clock steady (start-up)Shown at power-up when a real-time clock is fitted. (The manual does not give the colour.)
Carel ir33 universale[19]Icon clock flashingAn operating cycle (CL) is running, or a clock alarm is present; check the display for a code. (The manual does not give the colour.)
Carel ir33 universale[19]Icon reverse steadyAt least one relay working in reverse (heating-type) mode is active. (The manual does not give the colour.)
Carel ir33 universale[19]Icon reverse flashingReverse-mode PWM or 0-10 V outputs are in use. (The manual does not give the colour.)
Carel ir33 universale[19]Icon direct steadyAt least one relay working in direct (cooling-type) mode is active. (The manual does not give the colour.)
Carel ir33 universale[19]Icon direct flashingDirect-mode PWM or 0-10 V outputs are in use. (The manual does not give the colour.)
Carel ir33 universale[19]Icon TUNING flashingAuto-Tuning is enabled and running. (The manual does not give the colour.)
Sanhua SEC60x[31]LED manual mode flashingValve is in manual mode. (The manual does not give the colour.)
Sanhua SEC60x[31]LED TX/RX flashingData communication is taking place. (The manual does not give the colour.)
Sanhua SEC60x[31]All left-side LEDs flashingManual valve-opening mode set by DIP switch; valve opening follows the keys. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display icon eco steadyEnergy optimisation is active. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display FanAppliance cleaning started; only the fans run. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display OFFCleaning mode active (appliance can be cleaned) or main switch set to off. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display SErMain switch set to service/manual operation. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Bluetooth light flashingBluetooth pairing active; the display shows the controller address. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon door/light steadyRoom light is on. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon door/light flashingDoor switch is enabled and the room light is on. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon AUX steadyAuxiliary relay is called for. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Decimal point flashingNight (energy-saving) mode is active. (The manual does not give the colour.)
Danfoss EKE 1A/1B/1C/1D[43]Status LED green flashingData transmission or initialisation.
Danfoss EKE 1A/1B/1C/1D[43]Valve LED red flashingValve is closing.
Danfoss EKE 1A/1B/1C/1D[43]Valve LED red steadyValve is fully closed.
Danfoss EKE 1A/1B/1C/1D[43]Valve LED green flashingValve is opening.
Danfoss EKE 1A/1B/1C/1D[43]Valve LED green steadyValve is fully open.
Danfoss AK-RC 251[47]Icon door steadyCold room door is open. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon light steadyCold room light is on. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon alarm muted steadyAn alarm is in progress but the buzzer has been muted. (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon programming steadyProgramming mode is active. (The manual does not give the colour.)
Dixell XR06CX[51]LED °C/°F flashingProgramming mode. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED energy saving steadyEnergy saving is enabled. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED light steadyLight is on. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED AUX steadyAuxiliary relay is on. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED °C/°F flashingProgramming phase (XW60L). (The manual does not give the colour.)
Carel µC2SE for process chiller[59]Icon chiller mode amber steadyUnit is in chiller mode.
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Symbol door heaterDoor heater is on. (The manual does not give the colour.)
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Display ---Cooling function is switched off (manual defrost / cleaning). (The manual does not give the colour.)
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Display Adr alternatingBus-address setting mode; the current address alternates with Adr. (The manual does not give the colour.)
RDM DMTouch / miniDM[91]Dongle network LEDs flashing brieflyIdentify pressed on the RS485 Adapters page. (The manual does not give the colour.)
RDM DMTouch / miniDM[91]LED red/green flashing 10 timesLED test started from the Test page. (The manual does not give the colour.)
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED D02 flashing 10 sNo DISP mode.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED D02 flashing 2 sFunction change (EEPROM) is being set.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED D203 on 5 sGroup header unit is communicating with the remote controller.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED D203 fast flashingCommunication between group header and follower units.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]PCB LED flashing (unit selected)This module is the one selected from the remote controller for a setting change.
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote central control indicator flashingRemote buttons are locked by central control. (The manual does not give the colour.)
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote TEST run indicatorTest run in progress. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED section 1 steadySection 1 pressure is being displayed. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED section 2 steadySection 2 pressure is being displayed. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED network offNo network attached. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED network flashingTrying to log on to the network. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED HACCP flashingSet only by a remote network command (HACCP). (The manual does not give the colour.)
Temperzone UC6 unit controller[135]DS1 digit bDRM2/DRM3 demand response active: reduced capacity. (The manual does not give the colour.)
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Heat Cycle key litHeat treatment cycle is running. (The manual does not give the colour.)
Taylor heat treatment freezers C708/C716, C708 shake, C606[151]Topping heater keys litTopping heaters are on. (The manual does not give the colour.)
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]STAND-BY lamp after heat treatmentHeat treatment finished; mix is kept refrigerated. (The manual does not give the colour.)
Taylor Icetro ISI-271THS/SHS, ISI-300TA, ISI-301TH[155]Supplemental cooling lamp onDuring heating the buttons can still be used while this lamp is on. (The manual does not give the colour.)
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LED °C/°F flashingProgramming mode. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]PIB/RS485 card LED yellow RX onData is being received on the RS485 port.
Copeland (CPC) E2 RX/BX/CX controller[163]PIB/RS485 card LED red TX onData is being sent on the RS485 port.
Copeland (CPC) E2 RX/BX/CX controller[163]Case lights flashing 5 sWash mode is about to end; fans and cooling restart. (The manual does not give the colour.)
Pego 202BASE electronic board[167]Decimal point flashingNight (energy-saving) mode is active. (The manual does not give the colour.)
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]Symbol PV/Smart GridA signal from the PV system or Smart Grid has been received. (The manual does not give the colour.)
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]Display --- flashing with d0nFactory settings have been restored. (The manual does not give the colour.)
Carpigiani AES PSP[15]Function LED onThe function next to the LED is selected. (The manual does not give the colour.)
Carpigiani AES PSP[15]Display Pasto EndPasteurisation cycle completed successfully. (The manual does not give the colour.)
Danfoss Optyma Plus[4]LED crankcase heater steadyLit while the crankcase heater is switched on. (The manual does not give the colour.)
Carel μC2SE[8]LED heater steadyHeater (antifreeze/support heater) is on.
Carel μC2SE[8]LED chiller mode steadyUnit is operating in chiller (cooling) mode.
Carel μC2SE[8]LED chiller mode flashingChiller mode has been requested and is pending.
Dixell XR60CX[12]LED continuous cycle steadyContinuous (fast pull-down) cycle is running. (The manual does not give the colour.)
Dixell XR60CX[12]LED energy saving steadyEnergy saving mode is enabled. (The manual does not give the colour.)
Dixell XR60CX[12]LED °C/°F flashingController is in programming mode. (The manual does not give the colour.)
Carel EVD evolution / EVD evolution twin[16]LED NET green steadyNetwork connection to the controller is available.
Carel SmartCella / SmartCella 3PH[24]AUX icon steadyAuxiliary output 1 or 2 is active. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]AUX/light icon flashingAnti-sweat heater function is active. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Light icon steadyAuxiliary output configured as cold-room light is on. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Continuous cycle icon steadyContinuous cycle function is running. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]HACCP icon steadyHACCP monitoring (HA/HF) is enabled. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Clock icon steadyClock function (RTC) is active. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Clock icon flashingClock function has been requested. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED Status quick flashAnswer from the gateway/system unit after network installation (lasts about 10 minutes). (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED Service Tool steadyCommunication with the Service Tool PC program is active. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED LON flashingData communication on the LON network. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED Service Pin steadyService Pin switch has been activated for network installation. (The manual does not give the colour.)
Dixell XC645D[48]LED maintenance (spanner) steadyThe maintenance menu is open. (The manual does not give the colour.)
Dixell XC645D[48]LED maintenance (spanner) flashingOne or more loads have been put in maintenance status (disabled). (The manual does not give the colour.)
Dixell XC645D[48]LED alarm-log steadyAll stored alarms have been viewed. (The manual does not give the colour.)
Dixell XC645D[48]LED energy saving steadyEnergy saving is active. (The manual does not give the colour.)
Dixell XR35CX[52]LED continuous cycle steadyContinuous (fast pull-down) cycle is running. (The manual does not give the colour.)
Dixell XR35CX[52]LED energy saving steadyEnergy saving is enabled. (The manual does not give the colour.)
Dixell XR35CX[52]LED light steadyLight output is on. (The manual does not give the colour.)
Dixell XR35CX[52]LED auxiliary steadyAuxiliary relay is on. (The manual does not give the colour.)
Dixell XR35CX[52]LED °C/°F flashingController is in programming mode. (The manual does not give the colour.)
Dixell XWi70K[56]LED fan flashingProgramming mode (flashes together with the compressor LED). (The manual does not give the colour.)
Dixell XWi70K[56]LED pull down steadyPull-down (continuous cycle) is running. (The manual does not give the colour.)
Dixell XWi70K[56]LED energy saving steadyEnergy saving is enabled. (The manual does not give the colour.)
Dixell XWi70K[56]LED light steadyLight output is on. (The manual does not give the colour.)
Dixell XWi70K[56]LED auxiliary steadyAuxiliary output is on. (The manual does not give the colour.)
Carel µChiller[60]System pump icon flashingSystem pump is in manual operation. (The manual does not give the colour.)
Carel µChiller[60]Source pump/fan icon flashingSource pump/fan is in manual operation. (The manual does not give the colour.)
Carel µChiller[60]Compressor icon flashingCompressor in manual operation (with electronic expansion valve). (The manual does not give the colour.)
Carel µChiller[60]Frost protection heater icon steadyFrost-protection heater is on. (The manual does not give the colour.)
Carel µChiller[60]Heating mode icon steadyUnit is in heating mode. (The manual does not give the colour.)
Carel µChiller[60]Cooling mode icon steadyUnit is in cooling mode. (The manual does not give the colour.)
Carel µChiller[60]Free cooling icon steadyFree cooling is active. (The manual does not give the colour.)
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]LED yellow fast flashingUnit is in a special mode (e.g. service/test).
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]Relay module LEDsEach relay LED follows its relay coil (off = coil de-energised); meaning depends on energised/de-energised setting. (The manual does not give the colour.)
AHT GD-Cooler (GD-XLS, GD-XL)[84]LED symbol °C/°F flashingSetpoint is being changed. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]LED on-line offNo network attached.
RDM Mercury 3 Twin Coil[92]LED on-line flashingController is trying to log on to the network.
RDM Mercury 3 Twin Coil[92]LED on-line steadyController is on-line on the network.
RDM Mercury 3 Twin Coil[92]LED HACCP steady/flashingHACCP LED is switched on or set flashing by the network command (site-defined meaning). (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED PSI steadyPressures are shown in psig. (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED PSI flashingController is in programming mode. (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED service steadyService menu is being browsed. (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED alarm-menu steadyThe alarm menu is being browsed. (The manual does not give the colour.)
Full Gauge MT-512E 2HP[120]LED heating steadyHeating output is on. (The manual does not give the colour.)
Full Gauge MT-512E 2HP[120]LED functions lockdown steadyParameter lock (tamper-proof) is active. (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block all three synchronized blinkingTest run is in progress (all three lamps blink together). (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED lights steadyLights relay (relay 3) is on. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED on-line offNo network attached.
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED on-line flashingController is trying to log on to the network.
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED on-line steadyController is on-line on the network.
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED HACCP steady/flashingHACCP LED switched on or set flashing by a network command (site-defined meaning). (The manual does not give the colour.)
Carel PQ (True cabinets)[144]2nd parameter set icon steadyThe second parameter set is active. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Alarm LED flashingAlarm acknowledged/buzzer silenced; the alarm is still present until the cause clears. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Economy (reduced set) icon steadyEnergy-saving mode is on. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Economy (reduced set) icon flashingReduced setpoint mode is active. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Economy (reduced set) icon fast flashingLevel-2 parameter menu is open. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]AUX icon steadyAuxiliary output is active. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]AUX icon flashingDeep-cooling (pull-down) cycle is active. (The manual does not give the colour.)
Taylor soft serve and shake freezers C709/C717, C712, C713, C612[152]Standby symbol onStandby mode is active; hopper and cylinder are kept below 4.4 °C (40 °F). (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Lights icon steadyCase lights are on. (The manual does not give the colour.)
alpha innotec BWP 190S/260S DHW heat pump[168]Symbol electric heater shownElectric backup heater is switched on (symbol shows ON/OFF state). (The manual does not give the colour.)
IVT AirX air-to-water heat pump[175]1041Power was lost during the screed drying programme; it resumes by itself unless the outage lasted longer than the battery reserve or the set maximum time.
IVT AirSplit 200/300 split air-to-water heat pump[176]1041Power was lost during the screed drying programme; it resumes by itself unless the outage lasted longer than the battery reserve or the set maximum time.
IVT Geo 500/600 series ground source heat pump[177]5937Flow through PC0 is driven by another pump in the circuit that the heat pump does not control.
IVT Vent 202/302/402 exhaust air heat pump[179]1041Power was lost during the screed drying programme; it resumes by itself unless the outage lasted longer than the battery reserve or the set maximum time.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation steady + Timer and Swing slow blinkTest run is active. (The manual does not give the colour.)
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red slow blinkA protective function is limiting operation; not a stored fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red slow blinkA protective function is limiting operation; not a stored fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red steady + Green steadyTimer mode is set.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red steady + Yellow steadyLouvre swing is on (green may be on or off).
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red + Green pulsingTest run is active.
Hitachi RUA-NP4ATS…NP10ATS self-contained (packaged, ducted) air conditioners, R410A, cooling only, 1 or 2 scroll compressors (PCB display SEG1)[195]ALShown flashing when the PCB is in alarm history mode (SW1 held for more than 3 s): each further press of SW1 shows one of the last five alarm codes; holding SW1 for more than 5 s clears the history.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]orOil recovery operation is running (every 3 h of compressor running in cooling, 8 h in heating; first time after 1 h). Normal; indoor Operation lamps flash slowly.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]PCPeak cut mode active: compressor capacity is held down to cut the power peak. Not a fault; capacity may be lower.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]LnLow noise mode active: the outdoor fan runs at limited speed. Not a fault; capacity may be lower in high ambient.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation steady, dimmedAnti-freeze control is active: the indoor coil is protected against freezing in cooling; the lamp lights at reduced brightness. Not a fault. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Timer steady, dimmedA timer is set (lamp at reduced brightness). (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation + Timer flashing alternately (1 s)Power failure indication: the unit has had a power failure. Check the supply. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation + Timer flashing together (1 s)Test operation is running. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation + Timer + Filter flashing (1 s)Maintenance mode is active. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED fan flashingProgramming phase (the fan LED flashes while parameters are being set, per the XW60K table).
Carel pRack pR300[22]Icon manual operation (main screen)Shown in the main screen status field when one or more outputs are in manual operation. (The manual does not give the colour.)
Carel pRack pR300[22]Icon password level (1-3 lines, menu screens)Lines in the top right corner show the access level: one for user, two for maintenance, three for manufacturer. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED HACCP steadyHACCP LED lit; it is switched on only by a remote network command from the system manager.
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]Icon 2nd setpoint (II Set) steadyThe second parameter group (set II) is active, e.g. eco, night or clock-controlled operation. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol clock (tariff control)Tariff control is active. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol tank (water heater level)Shows the hot water tank temperature level while it is charged. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol tank with lightningPeak heating charge (anti-legionella) is in progress. (The manual does not give the colour.)
Carel MasterCella[7]AUX icon steadyAuxiliary output set as AUX is switched on. (The manual does not give the colour.)
Carel MasterCella[7]AUX icon flashingAnti-sweat heater function is active. (The manual does not give the colour.)
Carel MasterCella[7]Clock icon steadyAt least one timed defrost is programmed; at power-up it lights briefly when a real-time clock is fitted. (The manual does not give the colour.)
Carel MasterCella[7]Light icon steadyAuxiliary output set as LIGHT is switched on. (The manual does not give the colour.)
Carel MasterCella[7]Light icon flashingAnti-sweat heater function is active (not in firmware 3.6). (The manual does not give the colour.)
Carel MasterCella[7]HACCP icon steadyHACCP function is enabled. (The manual does not give the colour.)
Carel ir33 universale[19]Icon TUNING steadyAuto-tuning function is running. (The manual does not give the colour.)
Carel pRack pR300T (transcritical CO2)[23]Main screen manual operation signal (field 4)The main screen shows a signal that one or more outputs are in manual operation. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]Extension module (AK-XM 204B/205B) override LED onA relay on the module is overridden by hand; off means no override. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]LED HACCP steadyHACCP LED switched on by a network command from the data manager. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]Key backlights flashingKey backlights set to flash by a network command from the data manager. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED HACCP steadyHACCP LED switched on by a network command from the data manager. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon lights flashingLights are off but can be switched on from the keypad. (The manual does not give the colour.)
Carel μC2SE[8]LED heat pump mode steadyThe unit is running in heat pump mode (P6=0).
Carel μC2SE[8]LED heat pump mode flashingHeat pump mode has been requested but is not yet active (P6=0).
Dixell XR60CX[12]LED °C/°F steadyShows the unit of the displayed temperature. (The manual does not give the colour.)
Carel ir33+ VCC[20]AUX icon steadyAuxiliary output 1 or 2 is active. (The manual does not give the colour.)
Carel ir33+ VCC[20]AUX icon flashingThe anti-sweat heater function is active. (The manual does not give the colour.)
Carel ir33+ VCC[20]Clock icon steadyA timed defrost is set; with a real-time clock fitted it also shows briefly at start-up. (The manual does not give the colour.)
Carel ir33+ VCC[20]Light icon steadyAn auxiliary output set as light is on. (The manual does not give the colour.)
Carel ir33+ VCC[20]Light icon flashingThe anti-sweat heater function is active. (The manual does not give the colour.)
Carel ir33+ VCC[20]HACCP icon steadyThe HACCP function is enabled. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Light icon flashingThe anti-sweat heater function is active. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]ST501 LED5 on (default)With factory settings LED5 shows that parameter set 1 is active. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]ST501 LED6 on (default)With factory settings LED6 shows that parameter set 2 is active. (The manual does not give the colour.)
Full Gauge MT-512E 2HP[120]LED defrost flashingFlashes while the manual defrost item is selected in the quick menu, before it is confirmed. (The manual does not give the colour.)
Full Gauge MT-512E 2HP[120]LED temperature unit steadyShows the unit of the displayed temperature. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED service steady (Control Thermostat)The controller is in the additional parameter setting mode. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED HACCP steady (remote command)Switched on by a remote command from a Data Builder program. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED HACCP flashing (remote command)Set to flash by a remote command from a Data Builder program. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED lights steady (5 Channel Thermostat)The timer is in its on period. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]°C / °F icon steadyShows which temperature unit is set. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED room light steadyThe cold room light is on. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED room light flashingThe door switch is activated. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED AUX steadyThe auxiliary relay is called (AU1/AU2 = +/-2 or +/-3). (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED fan flashingFlashes together with the compressor LED while in programming mode. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]SET button LED flashingThe set point is shown and can be changed. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]SET button LED fast flashingEnergy saving mode is active. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]ENERGY SAVING button LED onEnergy saving mode is active. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LIGHT button LED onThe cabinet/room light output is on. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]AUX button LED on (XW270L)XW270L only: the auxiliary output is on. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]HEATER button LED on (XW271L)XW271L only: the anti-condensing heater is on. (The manual does not give the colour.)
Eliwell ID 974[13]LED alarm flashingThe alarm has been acknowledged and the buzzer silenced; the alarm is still present. (The manual does not give the colour.)
Eliwell ID 974[13]LED economy (reduced set) flashing (IDPlus)IDPlus: the reduced (economy) set point is active. (The manual does not give the colour.)
Eliwell ID 974[13]LED AUX on (IDPlus)IDPlus: auxiliary output indication; its meaning depends on the model. (The manual does not give the colour.)
Eliwell ID 974[13]LED °C on (IDPlus)IDPlus: temperatures are shown in °C (dro = 0). (The manual does not give the colour.)
Eliwell ID 974[13]LED °F on (IDPlus)IDPlus: temperatures are shown in °F (dro = 1). (The manual does not give the colour.)
Carel MPXone[21]UP/DOWN button LED onScrolling menus, parameters or direct access functions; a key is usable only when lit. (The manual does not give the colour.)
Carel µRack[25]Icon BAR onValues are shown in bar. (The manual does not give the colour.)
Carel µRack[25]Icon °C onValues are shown in °C. (The manual does not give the colour.)
Carel µRack[25]Icon suction probe onThe display shows the suction probe value. (The manual does not give the colour.)
Carel µRack[25]Icon discharge probe onThe display shows the discharge probe value. (The manual does not give the colour.)
Sanhua SEC60x[31]LED SH onThe display shows superheat. (The manual does not give the colour.)
Sanhua SEC60x[31]LED PRESS onThe display shows pressure. (The manual does not give the colour.)
Sanhua SEC60x[31]LED OPEN onThe display shows the valve opening in %. (The manual does not give the colour.)
Sanhua SEC60x[31]LED TEMP onThe display shows a temperature. (The manual does not give the colour.)
Sanhua SEC60x[31]LED °C/bar onShows the unit of the displayed temperature or pressure. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Units °C/bar/time onShows the unit of the displayed value. (The manual does not give the colour.)
Dixell XR70CX[54]LED °C/°F onShows the selected temperature unit. (The manual does not give the colour.)
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LED °C/°F onShows the selected temperature unit. (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED defrost flashing (quick access menu)The defrost command is selected in the quick access menu; press to switch defrost on or off. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]MODBUS 40 LED COM1 flashingMODBUS 40 accessory is communicating with the heat pump. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED COM1 flashingSMS 40 is communicating with the heat pump (also at start-up). (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED LEV steadySMS 40 GSM signal is OK. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED COM2 flashingSMS 40 is communicating with its GSM modem. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]SMS 40 LED SYNC flashingSMS 40 is sending or receiving a text message. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED HACCP flashingHACCP LED set to flash by a remote command from the system manager. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]Function key backlights flashingKey backlights set to flash by a remote command; keys normally light when pressed and go dark after 20 s. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED HACCP flashingHACCP LED set to flash by a remote command from the system manager. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon single userOne user is logged in to the E2. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon multiple usersSeveral users are logged in to the E2. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon terminal modeTerminal mode is in use. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon EthernetThe E2 is connected to Ethernet. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon wait/busyThe system is busy; wait. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon disk activityThe E2 is reading or saving to its memory. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Header icon caps lockCaps lock is on. (The manual does not give the colour.)
Evco EV3203[107]LED energy saving steadyEnergy saving mode is on. (The manual does not give the colour.)
Evco EV3 300 series[108]LED °C/°F steadyThe display shows a temperature in the unit of the lit LED. (The manual does not give the colour.)
Evco EVK214[109]LED HACCP steadyNot all stored HACCP alarms have been viewed yet. (The manual does not give the colour.)
Evco EVK214[109]LED maintenance steadyCompressor maintenance is due (C10). (The manual does not give the colour.)
Evco EVK214[109]LED °C or °F blinkingEnergy saving is active (r4, i5, HE1, HE2). (The manual does not give the colour.)
Evco EVK214[109]LED multifunction steady (u1 = 0, light)The cabinet light was switched on manually. (The manual does not give the colour.)
Evco EVK214[109]LED multifunction blinking (u1 = 0, light)The cabinet light was switched on remotely (i0). (The manual does not give the colour.)

The lamp gives information that is not a fault, for example communication, start-up, self-test, service or emergency mode.

Check: See the manual for the product; check communication wiring and settings when the lamp points to them.

Status: defrost or drip time

ControllerCode
Danfoss ERC 21X[1]Icon defrost steadyA defrost cycle is in progress. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED defrost onUnit is in defrost. (The manual does not give the colour.)
Carel MPXone[21]Icon defrost onDefrost is in progress. (The manual does not give the colour.)
Carel MPXone[21]Icon defrost flashingA defrost is requested and waiting to start. (The manual does not give the colour.)
Danfoss AK-CC 550 / 550B[33]LED defrost onDefrost relay is on. (The manual does not give the colour.)
Danfoss EKC 202D1[41]LED defrost onDefrost is in progress. (The manual does not give the colour.)
Dixell XR460C[53]Icon defrost 1 onDefrost of section 1 in progress. (The manual does not give the colour.)
Dixell XR460C[53]Icon defrost 1 flashingDrip time running for section 1. (The manual does not give the colour.)
Dixell XR460C[53]Icon defrost 2 onDefrost of section 2 in progress. (The manual does not give the colour.)
Dixell XR460C[53]Icon fan flashingDrip time in progress (fans held off after defrost). (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon fans flashingFans paused after defrost (time F5). (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon defrost onDefrost is called/in progress. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon defrost flashingDrip time after defrost (time d7); compressor and fans stopped. (The manual does not give the colour.)
AHT plug-in cases with Danfoss controller (Paris, Ibiza, Malta, Manhattan)[85]Defrost LED symbol onA manually started defrost is in progress (display shows dEF). (The manual does not give the colour.)
Secop SLV controller 105N46xx[81]LED Defrosting onDefrost is in progress. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]LED2 on (default)Defrost of control circuit 1 is active (default U12 = 2; can be reassigned). This default applies to the ST121/ST501; on the ST551 LED2 shows a high-pressure alarm by default.
Full Gauge TC-900E POWER / TC-900E 2HP[117]LED defrost onDefrost is in progress. (The manual does not give the colour.)
Full Gauge MT-512E Log[121]LED defrost onDefrost is in progress. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED defrost (amber) onA channel is in defrost; its alarms are inhibited during defrost and recovery. On the PR0440 the defrost LED shows the timer instead: lit = timer off (out of hours), dark = timer on.
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Icon defrost onCabinet is in defrost. (The manual does not give the colour.)
Dixell XR/XW (True cabinets)[145]Icon defrost onDefrost (or reversing condenser fan) is running. (The manual does not give the colour.)
Dixell XR/XW (True cabinets)[145]Icon defrost flashingDrip time after defrost is in progress. (The manual does not give the colour.)
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]LCD DEF flashingBarrel is in DEFROST PENDING (e.g. during beater overload recovery). (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon defrost onDefrost is active (can be stopped from the keypad). (The manual does not give the colour.)
ActronAir DS Series and R-32 split systems (Serene DS, Aspire DS, Cascade DS, MultiElite DS, Cassette 2)[138]Display FDefrost in progress; at power-on (15 s) it can instead be the filter replacement reminder. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Lamp green offMechanical controller: the DEFROST button has been pressed, cooling is off and manual defrost is on; press again to restart cooling.
AHT electronic controller (plug-in cases, standard)[82]Display -d- / dFr.Defrost in progress (AHT controller). (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display dEFDefrost in progress (SECOP controller or automatic defrost). (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]LED defrostDefrost is in progress. (The manual does not give the colour.)
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]Display -d-Defrost is in progress. (The manual does not give the colour.)
Heatcraft Beacon II[30]Display dEFDefrost in progress.
Heatcraft Beacon II[30]Display drnDrain (drip) time after defrost.
Danfoss ETC (True cabinets)[142]Icon defrost heaterThe defrost heater is on. (The manual does not give the colour.)
Danfoss ETC (True cabinets)[142]Display dEFA defrost is in progress (e.g. after a manual defrost). (The manual does not give the colour.)
Danfoss EKC 202A/B/C[2]LED defrost steadyDefrost relay is on, defrost in progress. (The manual does not give the colour.)
Danfoss EKC 202A/B/C[2]Display -d-Defrost is running or the room is still pulling down after defrost (shown up to 15 min). (The manual does not give the colour.)
Carel Heos[18]Defrost button backlight onA manually started defrost is running. (The manual does not give the colour.)
LAE AT1-5/AT2-5[166]Display DEFDefrost in progress. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Icon defrostThe defrost heater is on / the appliance is defrosting. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Display dEFDefrost in progress. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]LED defrostDefrost is on. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display dEFr On / OFFManual defrost started or ended from the keypad. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]Display drAiProcess stage: drainage after defrost. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED defrost onDefrost is in progress. (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED defrost flashingDrip time after defrost (d7): compressor and fans stay off. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED defrostDefrost is in progress. (The manual does not give the colour.)
RDM ML Controller case controller[134]Display dEFControl state: defrost. (The manual does not give the colour.)
Taylor C392/C393/C394 frozen beverage freezers[150]Icon defrost valveThe barrel defrost valve is open. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]LED defrostThe defrost output is on. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display Pre,Process stage: pre-defrost. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display dEFrProcess stage: defrost. (The manual does not give the colour.)
Full Gauge TC-900E Log[118]Display dRAiProcess stage: drainage (drip time). (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon defrost onDefrost is in progress. (The manual does not give the colour.)
Dixell XR70CX[54]LED defrost onDefrost is in progress. (The manual does not give the colour.)
Dixell XR70CX[54]LED defrost flashingDrip time after defrost is running. (The manual does not give the colour.)
Danfoss AK-CC 550A[3]Icon defrost steadyDefrost relay is on. (The manual does not give the colour.)
Danfoss AK-CC 550A[3]Display -d-Defrost sequence in progress, including drip-down, fan delay and pull-down. (The manual does not give the colour.)
Carel ir33[11]Icon defrost steadyDefrost is in progress. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display icon defrost steadyDefrost is in progress. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display -d-Defrost is in progress. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon fan flashingFans are paused after defrost (parameter F4). (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon defrost steadyDefrost is called for. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon defrost flashingDrip time after defrost is running (parameter d7). (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon fan flashingFans should run but are held by a delay (drip time). (The manual does not give the colour.)
Danfoss AK-RC 251[47]Icon defrost steadyDefrost relay is on. (The manual does not give the colour.)
Dixell XR06CX[51]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XR06CX[51]LED defrost flashingDrip time is in progress. (The manual does not give the colour.)
Dixell XR06CX[51]LED fan flashingFan delay after defrost is running. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED defrost flashingDrip time is in progress. (The manual does not give the colour.)
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Symbol defrostDefrost is in progress. (The manual does not give the colour.)
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Display dEFAutomatic defrost is in progress (max. 60 min). (The manual does not give the colour.)
Full Gauge TC-940R[119]LED DEFR steadyDefrost (heating) output is on. (The manual does not give the colour.)
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote pre-heat indicatorDefrost cycle has started. (The manual does not give the colour.)
Temperzone UC6 unit controller[135]DS1 digit 8De-ice mode or the time-out after de-ice. (The manual does not give the colour.)
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XR03CX/XR04CX (Hillphoenix display cases)[159]LED defrost flashingDrip time is in progress. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED defrost flashingDrip time after defrost (d7) is running. (The manual does not give the colour.)
Vaillant aroSTOR plus VWL B/BM 200/6, 260/6[171]Symbol de-icingManual de-icing is running (ends after 8 min). (The manual does not give the colour.)
Dixell XR60CX[12]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XR60CX[12]LED defrost flashingDrip (dripping) time after defrost is running. (The manual does not give the colour.)
Carel ir33+ VCC[20]Defrost icon steadyDefrost is in progress (dEF). (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Defrost icon steadyDefrost is active. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]LED DEFROST yellow steady (3PH panel)Power is available at the defrost terminals.
Danfoss AK-CC 450[32]LED defrost steadyDefrost relay is on; defrost in progress. (The manual does not give the colour.)
Danfoss AK-CC 750[36]Display LED 3 (defrost) steadyDefrost relay on (EKA display front LED). (The manual does not give the colour.)
Dixell XR35CX[52]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XR35CX[52]LED defrost flashingDrip time after defrost is running. (The manual does not give the colour.)
Dixell XWi70K[56]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XWi70K[56]LED defrost flashingDrip time after defrost is running. (The manual does not give the colour.)
Carel µChiller[60]Defrost icon steadyDefrost is in progress. (The manual does not give the colour.)
Carel µChiller[60]Defrost icon flashingDripping time after defrost. (The manual does not give the colour.)
AHT GD-Cooler (GD-XLS, GD-XL)[84]LED symbol defrost steadyAutomatic or manual defrost is running. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]LED defrost steadyDefrost cycle in progress (pump-down and heating stages; off again during drain-down and fan delay). (The manual does not give the colour.)
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]DEFROST/STAND BY lamp orange steadyHeating is being prepared: defrost or warm-up standby before the fan starts.
Full Gauge MT-512E 2HP[120]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED defrost steadyDefrost cycle in progress (pump-down and heating stages; off during drain-down and fan delay). (The manual does not give the colour.)
Carel PQ (True cabinets)[144]Defrost icon steadyDefrost heaters are energised. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Defrost LED steadyDefrost is active. (The manual does not give the colour.)
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Defrost LED flashingDefrost started manually or by digital input. (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Defrost icon steadyDefrost is active. (The manual does not give the colour.)
alpha innotec BWP 190S/260S DHW heat pump[168]Symbol defrost shownEvaporator defrost is in progress. (The manual does not give the colour.)
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red long pulsesHeat pump defrost is running.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]dFDefrost operation is running. Normal.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 6 s on / 2 s offDefrost or oil recovery is running in the outdoor unit. Normal; the indoor fan may stop or slow down meanwhile. (The manual does not give the colour.)
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]Icon defrost output steadyThe defrost output is energised. (The manual does not give the colour.)
Thermia Atella / Robust[114]Symbol defrostDefrosting is active. (The manual does not give the colour.)
Carel MasterCella[7]Defrost icon steadyDefrost is in progress. (The manual does not give the colour.)
Carel μC2SE[8]LED defrost steadyDefrost is in progress.
Carel μC2SE[8]LED defrost flashingDefrost has been requested and is waiting to start.
Pego 202BASE electronic board[167]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED defrost onA defrost is in progress. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED defrost flashingDrip time after defrost is running. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]DEFROST button LED onA manual defrost has been started. (The manual does not give the colour.)
Eliwell ID 974[13]LED defrost onA defrost is in progress. (The manual does not give the colour.)
Eliwell ID 974[13]LED defrost flashingDefrost has been called manually or by a digital input. (The manual does not give the colour.)
Evco EV3203[107]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Evco EV3203[107]LED defrost blinkingDefrost is delayed or the evaporator is dripping after defrost. (The manual does not give the colour.)
Evco EVK214[109]LED defrost steadyDefrost is in progress. (The manual does not give the colour.)
Evco EVK214[109]LED defrost blinkingDefrost is waiting for compressor protection, the evaporator is dripping (d7), or the refrigerant is being heated (dA). (The manual does not give the colour.)

The lamp or symbol shows that a defrost or the drip time after it is running.

Check: Nothing to do; if the defrost never ends, troubleshoot the defrost.

Alarm lamp: an alarm is active

ControllerCode
Danfoss ERC 21X[1]Icon alarm steadyAn alarm is active; read the A/E code shown alternately with the temperature. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED alarm flashingA new alarm has occurred; open the alarm menu to read it. (The manual does not give the colour.)
Copeland EazyCool ZX (XCM25D)[5]LED alarm (active) onAn alarm is currently active. (The manual does not give the colour.)
Carel EVD ice / EVD mini[17]Red LED flashingAn alarm is active; read the A/E code on the display.
Carel MPXone[21]Alarm icon (triangle) flashingAn alarm is active; the code is shown on the display. (The manual does not give the colour.)
Carel MPXone[21]ALARM button LED flashingAn active alarm is present. (The manual does not give the colour.)
Carel MPXone[21]ALARM button LED onAlarm has been acknowledged (buzzer muted). (The manual does not give the colour.)
Carel µRack[25]Icon ALARM onAn alarm is active; the display alternates value and alarm code. (The manual does not give the colour.)
Carel µRack[25]Red ALARM LED onA manual-reset alarm (compressor/fan overload) is or was active today; outputs stay disabled until alarms are cleared with A19.
Carel µRack[25]Icon suction probe + ALARM flashingSuction probe alarm: high or low value, or probe not connected. (The manual does not give the colour.)
Carel µRack[25]Icon discharge probe + ALARM flashingDischarge probe alarm: high value or probe not connected. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED ! on (upper)A new alarm has occurred; open the alarm menu. (The manual does not give the colour.)
Copeland Large ZX 22–30 HP[29]LED ! on (lower)An alarm is currently active. (The manual does not give the colour.)
Danfoss AK-CC 550 / 550B[33]All LEDs flashingAn alarm is active; press the top button briefly to show the code and acknowledge. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Alarm flashingActive or unacknowledged alarm. (The manual does not give the colour.)
Danfoss AK-PC 781A[37]LED Alarm steadyActive alarm that has been acknowledged. (The manual does not give the colour.)
Danfoss EKC 202D1[41]LEDs flashing fastAn alarm is active; push the top button to show the alarm code. (The manual does not give the colour.)
Dixell XEV12D[49]LED superheat alarm onSuperheat is outside its alarm limits.
Dixell XR460C[53]Icon alarm onAn alarm is active; read the code on the display. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon alarm flashingAn alarm is present; its code alternates with the temperature. (The manual does not give the colour.)
Pego ECP200 EXPERT PULSE[89]Icon alarm steadyAn alarm occurred and has since cleared; press UP to reset the memory. (The manual does not give the colour.)
Secop SLV controller 105N46xx[81]LED Alarm onAn alarm is active; short press the upper button to see the code. (The manual does not give the colour.)
Secop SLV controller 105N46xx[81]External alarm LED (DI1 = 17) onMirrors the display Alarm LED: an alarm is active. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]Display flashingAn alarm is active (with A15 = 1, 3 or 5); read the alarm code.
Copeland compressor electronics communications (20–40 ton scroll)[65]LED red flash + solid red (lockout)Compressor is locked out; the red flash code before it shows the cause.
RDM Mercury / Intuitive Mercury thermostats and monitors[129]LED alarm (red) onA fault or alarm is detected; read it on the display.
RDM Intuitive Bitzer IQ Rack (BITZER CM-RC-01 alarms)[133]Status bar redAn alarm condition is present.
Danfoss ERC 11x (True and Beverage-Air cabinets)[141]Icon alarm onAn alarm is active; read the code on the display. (The manual does not give the colour.)
Dixell XR/XW (True cabinets)[145]Icon alarm onAn alarm is active; read the code on the display. (The manual does not give the colour.)
Taylor frozen beverage freezers C300, C302, C303/C314, 345/346/349/355[149]LCD FAULT flashingA machine fault has occurred (with warning tone); read the fault message. (The manual does not give the colour.)
Carel iJF with VCC (Hillphoenix SMD-H)[161]Icon service onAn alarm is active (service/maintenance indication); read the code on the display. (The manual does not give the colour.)
Toshiba Digital Inverter / Super Digital Inverter RAV (RAV-SM, RAV-RM, RAV-GM, RAV-HM light commercial split)[125]Receiver lamps Operation/Timer/Ready flashingWireless models: an error is shown by the lamp pattern; read the check code with the remote or the service table. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display flashing pointElectronic controller: an alarm is active; press STANDBY briefly to show the fault code. (The manual does not give the colour.)
AHT electronic controller (plug-in cases, standard)[82]Display red point next to hornSECOP controller: an alarm is active and stays lit until the fault is fixed; press STANDBY RESET to see the code.
Danfoss AK-CC55 (Single Coil, Multi Coil, Compact)[34]LED alarmAn alarm is active; hold the alarm button 3 s to read the code. (The manual does not give the colour.)
Danfoss AK-PC 782A/782B[38]LED Alarm flashingAn alarm is active or not yet acknowledged. (The manual does not give the colour.)
BAC TrilliumSeries adiabatic cooler TRF[174]EC fan LED orangeEC fan motor: a warning is active.
BAC TrilliumSeries adiabatic cooler TRF[174]EC fan LED redEC fan motor: failure; the motor status relay opens.
BAC TrilliumSeries adiabatic cooler TRF[174]HMI fan dot redFan status Alarm: a fan alarm is active; see the fan alarms menu.
BAC TrilliumSeries adiabatic cooler TRF[174]HMI alarm row redThe alarm in that row is active; inactive alarms are not highlighted.
Copeland PerformanceAlert diagnostic module[62]LED yellow long flash + codeOne long yellow flash before the flash code means the module has locked the compressor out; count the following flashes for the cause.
Danfoss EKC 202A/B/C[2]LEDs flashingAn alarm is active; press the top button briefly to read the code and acknowledge it. (The manual does not give the colour.)
Danfoss EKC 326A[42]All four LEDs flashingA regulation error is active; push the upper button briefly to show the code and cancel the alarm. (The manual does not give the colour.)
Copeland EXD-SH1/2[26]LED alarm onAn alarm is active; read the code on the display. (The manual does not give the colour.)
Danfoss VLT HVAC Basic Drive FC 101[70]LED Warn. yellowA warning is active; read the code on the display. The motor may keep running.
Danfoss VLT HVAC Basic Drive FC 101[70]LED Alarm red flashingThe drive has tripped on an alarm; fix the cause, then press Reset (a trip lock needs a mains power cycle).
Danfoss VLT HVAC Basic Drive FC 101[70]LED Warn. + Alarm flashingDirectly after a trip both warning and alarm flash; when the cause is gone only the alarm keeps flashing until reset.
Danfoss VLT FC 103[14]LED Warn yellow steadyA warning is active; the display shows the warning text and number.
Danfoss VLT FC 103[14]LED Alarm red flashingAn alarm has tripped the drive; read the alarm number and reset after the cause is fixed.
Danfoss VLT FC 103[14]LED Warn yellow + Alarm red flashingTrip lock: the drive is locked out; cycle the mains power after fixing the cause.
Carel Heos[18]Alarm LED red flashingA new alarm is active (buzzer and alarm relay on if configured); press Alarm to read it.
Carel Heos[18]Power+ LED RUN/FAULT redThe Power+ drive has an alarm; read the drive alarm on the controller.
HTPG EcoNet enabled unit coolers[162]Red LED above display flashingAn alarm is active; read it under Service > Current Alarms.
Hussmann parallel rack / CO2 cascade (basic alarm package)[86]Alarm indicator lightBasic alarm package: the lit indicator shows which alarm (oil failure, phase loss, low liquid, high suction, high discharge or compressor failure) has tripped; with an electronic rack controller read the alarm there. (The manual does not give the colour.)
LAE AT1-5/AT2-5[166]Indicator alarmAn alarm is active; read the code on the display. (The manual does not give the colour.)
LAE AR2/BR1/BIT25 and BR+/CD25/TM (True cabinets)[146]Icon alarmAR2/BR1/BIT25: an alarm is active; read the code (hi, Lo, do, E1-E3). (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]Group icon yellow ×MJ-310E: equipment in the group is abnormal; open the group to read the error code.
Mitsubishi Electric City Multi (M-NET error codes)[102]Mark at top right of group iconMJ-310E: abnormality in the outdoor unit, sub outdoor unit, BC controller, gateway or interface unit of that group. (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]Message bar Serious failureMJ-310E: abnormality in an interface unit (IFU) or gateway (G/W). (The manual does not give the colour.)
Mitsubishi Electric City Multi (M-NET error codes)[102]Message bar Slight failureMJ-310E: abnormality in an air conditioning unit. (The manual does not give the colour.)
Full Gauge MT-514E Faston[122]LED alarmAn alarm is active; read the message on the display. (The manual does not give the colour.)
NIBE F1255 ground source heat pump[78]Front lamp redA-alarm: an alarm icon shows in the display and the heat pump may reduce comfort or stop; read the alarm number.
NIBE F1255 ground source heat pump[78]Front lamp green + service symbolB-alarm (information alarm): a temporary fault the heat pump handles itself; it resets automatically and is not logged.
NIBE F1255 ground source heat pump[78]Inverter status LED red steadyThe inverter has an alarm; read the alarm in the heat pump display.
Danfoss Optyma iCO2[46]Icon alarm/warning redAn alarm or warning is active; read the A, E or H code on the MMILDS display.
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED alarm onAn alarm or warning is active, or an EH/EL temperature alarm has cleared but not yet been acknowledged (press mute). (The manual does not give the colour.)
Pego ECP202 EXPERT / ECP202 EXPERT D7.5[90]LED alarm flashing + temperature flashingRoom temperature is outside the A1/A2 limits; the buzzer sounds. (The manual does not give the colour.)
Carel pRack pR300[22]Terminal LED red flashingOne or more alarms are active and not yet acknowledged; press Alarm to read them.
Carel pRack pR300[22]Icon alarm (main screen)An alarm is active, manual operation is on, or a prevent function (e.g. high-pressure prevent) is acting; open the alarm list. (The manual does not give the colour.)
RDM Mercury AC and roof top unit controllers[130]LED alarmAn alarm is active; read the message on the display. (The manual does not give the colour.)
RDM ML Controller case controller[134]LED alarmAn alarm is active; read the message on the display. (The manual does not give the colour.)
Taylor C392/C393/C394 frozen beverage freezers[150]Yellow triangle on touchscreenA machine fault has occurred (warning tone sounds); open the fault screen to read it.
Taylor C392/C393/C394 frozen beverage freezers[150]Red rectangle in Current ConditionsThe input or barrel shown in red has an active fault.
Taylor C392/C393/C394 frozen beverage freezers[150]PNR LED red fast flashingA fault has occurred on that barrel (flashes at about half-second intervals).
Taylor R280 fry dispenser[158]Display and basket LEDs flashing with ErrAn error has been detected on that side; read the Err number and press Enter to reset. (The manual does not give the colour.)
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]OPERATION green + TIMER orange flashing 5 HzProtection for the connecting cable / serial signal or another protection (including compressor); read the check code with the remote controller.
Toshiba RAS residential split and multi-split (RAS-2M…5M G3, RAS-B J2, RAS-PKVPG; check codes)[126]All indoor lamps flashing 5 Hz + beeps (service mode)During remote-controller self-diagnosis: the check code now shown is the fault.
Vaillant uniTOWER plus VIH QW 190/6 E / aroTHERM plus split[170]Symbol fault F.XXXA fault is active; the F code (with plain text) replaces the basic display. (The manual does not give the colour.)
Dixell XM669K/XM679K[50]Icon generic alarmAn alarm is active; read the code on the display. (The manual does not give the colour.)
Dixell XR70CX[54]LED alarm onAn alarm is active; read the code on the display. (The manual does not give the colour.)
Danfoss AK-CC 550A[3]All icons flashingAn alarm is active; press the top button to read the code. (The manual does not give the colour.)
Carel ir33[11]Icon alarm flashingAn alarm is active (e.g. high/low temperature or external input); read the code. (The manual does not give the colour.)
Carel ir33[11]Icon service (spanner) flashingInternal malfunction such as an EEPROM error or a probe fault; call service. (The manual does not give the colour.)
Carel ir33[11]Icon HACCP flashingNew HACCP alarms (HA and/or HF) are stored and not yet cleared. (The manual does not give the colour.)
Carel ir33 universale[19]Icon alarm flashingAn alarm is active, including immediate or delayed external input alarms; read the code. (The manual does not give the colour.)
Carel ir33 universale[19]Icon service (spanner) flashingMalfunction such as an EEPROM error or probe fault; also shown for the signal-only alarm E17. (The manual does not give the colour.)
Carel pRack pR300T (transcritical CO2)[23]Terminal LED red flashingActive alarm that has not been acknowledged; press Alarm to read it.
Carel pRack pR300T (transcritical CO2)[23]Terminal LED red steadyAlarm present and acknowledged, or an auto-reset alarm still waiting to be viewed.
Copeland Stream condensing units (Next Gen CoreSense)[27]LED green flashingWarning condition; the compressor keeps running. Count the flashes for the cause.
Copeland Stream condensing units (Next Gen CoreSense)[27]LED orange flashingTrip; the compressor has stopped and restarts by itself after a set time. Count the flashes.
Copeland Stream condensing units (Next Gen CoreSense)[27]LED red flashingLockout; manual reset is needed. Count the flashes for the cause.
Sanhua SEC60x[31]LED alarm steadyAn alarm is active; read the code on the display. (The manual does not give the colour.)
Danfoss AK-CC55 Water Loop[35]Display alarm LED steadyAn alarm is active; hold the alarm button for 3 s to read the code. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon alarm steadyAn alarm occurred and has cleared; it is shown until acknowledged. (The manual does not give the colour.)
Danfoss Optyma control AK-RC 113[39]Icon alarm flashingAn alarm is in progress; read the code on the display. (The manual does not give the colour.)
Danfoss EKE 1A/1B/1C/1D[43]Status LED red flickeringAlarm or error condition; read the code.
Danfoss AK-RC 251[47]Icon alarm steadyAn alarm is active (not a HACCP alarm); read the code. (The manual does not give the colour.)
Dixell XW60K/XW60L[55]LED alarm steadyAn alarm is active; read the code. (The manual does not give the colour.)
Carel µC2SE for process chiller[59]Icon alarm red steadyAn alarm is active; read the code.
Copeland CoreSense Communications (13–15 ton scroll)[67]LED yellow 2Compressor ran 12 s to 15 min and then tripped for more than 7 min; repeated events lead to lockout (red 2).
Copeland CoreSense Communications (13–15 ton scroll)[67]LED red N + solid redLockout: the red flash code is followed by a pause and a steady red phase; power cycle or Modbus reset is needed.
AHT electronic controller (Nidec/Secop, e.g. Kinley XL)[83]Symbol alarmAn alarm is active; the error code alternates with the temperature. Stays until the fault is cleared. (The manual does not give the colour.)
RDM DMTouch / miniDM[91]LED alarm flashingAn alarm directed to the front panel is active (sounder also on). (The manual does not give the colour.)
Kriwan INT69 PYF Diagnose[95]LED red 6 / orange 3Cos phi monitoring: value outside the permitted limit.
Kriwan INT69 PYF Diagnose[95]LED green / orange flashingWarning pending; count green then orange pulses (same table as the red codes).
Kriwan INT69 PYF Diagnose[95]LED red / orange flashingFault, motor shut down; count red then orange pulses.
Full Gauge TC-940R[119]LED ALRM steadyAlarm output is on; read the message. (The manual does not give the colour.)
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote operation lamp flashingA fault or protective device has stopped the unit; read the check code. (The manual does not give the colour.)
Toshiba VRF high-temperature hot water module MMW-AP0481CHQ-E (R134a)[127]Remote check code / service displayA protective device has operated or a fault occurred; read the check code. (The manual does not give the colour.)
RDM Intuitive / Mercury pack and condenser controllers[131]LED alarm steadyAn alarm is active; read the message on the display. (The manual does not give the colour.)
Temperzone UC6 unit controller[135]Alarm LED (AOUT 4) flashingExternal 7-segment alarm LED flashes with the alarm code. (The manual does not give the colour.)
True Ice TI/TCIM ice machines[147]UV LED red slow flashingUV lamp current too low.
True Ice TI/TCIM ice machines[147]UV LED red fast flashingUV lamp overload (current too high).
True Ice TI/TCIM ice machines[147]Alert triangle on home screenAn alarm is active; press the triangle to read it. (The manual does not give the colour.)
Copeland (CPC) E2 RX/BX/CX controller[163]Case controller alarm LEDs red flashing 2/sCC-100/CS-100 is in fail-safe mode (corrupt set point or software, or failed sensors).
Pego 202BASE electronic board[167]LED alarm flashingTemperature alarm (below A1 or above A2); the temperature also flashes and the buzzer sounds. (The manual does not give the colour.)
Carpigiani AES PSP[15]CHECK LED flashingAn alarm has occurred; press STOP to show the last alarm. (The manual does not give the colour.)
Carpigiani AES PSP[15]CHECK LED steadyReminder of an earlier alarm, or a pasteurisation that was repeated after a blackout. (The manual does not give the colour.)
Daikin RA / SkyAir / VRV (malfunction codes)[75]Remote operation LED flashingUnit stopped by a malfunction; the code is shown on the wired remote. (The manual does not give the colour.)
Daikin RA / SkyAir / VRV (malfunction codes)[75]Indoor unit operation LED flashingUnit stopped by a malfunction (wireless remote); read the code via inspection mode. (The manual does not give the colour.)
Danfoss Optyma Plus[4]All LEDs flashingAn alarm is active and the alarm relay has cut in; press the top button to read the code. (The manual does not give the colour.)
Carel μC2SE[8]LED alarm steadyAn alarm is active; read the code on the display.
Dixell XR60CX[12]LED alarm steadyAn alarm is active; read the code on the display. (The manual does not give the colour.)
Carel EVD evolution / EVD evolution twin[16]LED alarm red steadyA system alarm is active (probe, EEPROM, valve motor; also mains failure when an Ultracap/battery module closes the valve); control alarms do not light it.
Carel ir33+ VCC[20]Alarm icon flashingAn alarm is active; the code (E0, LO, HI, UCF, COM …) is shown on the display. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Alarm icon flashingAn alarm is active (e.g. high/low temperature or a malfunction); read the code. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]Service (spanner) icon flashingMalfunction such as EEPROM error or faulty probe; read the code. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]HACCP icon flashingA HACCP alarm has been stored; check HA/HF. (The manual does not give the colour.)
Carel SmartCella / SmartCella 3PH[24]LED ALARM red steady (3PH panel)Alarm: breaker QF1, motor protector QM1 or alarm input (HP switch/compressor protector) has tripped.
Danfoss AK-CC 450[32]All LEDs flashingAn alarm is active and the alarm relay has cut in; push the top button to read and accept the code. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED Alarm flashingActive alarm not yet acknowledged. (The manual does not give the colour.)
Danfoss AK-CC 750[36]LED Alarm steadyActive alarm that has been acknowledged. (The manual does not give the colour.)
Danfoss AK-CC 750[36]Display LEDs flashingAn alarm has been triggered; press the top button to show the code. (The manual does not give the colour.)
Danfoss EKE 100[44]LED alarm red flashing 1 HzAn alarm or warning is active on valve A or B; read the code.
Dixell XC645D[48]LED load 1–4 flashing 2 HzDigital-input safety alarm for that load, or the load is disabled for maintenance; read the display. (The manual does not give the colour.)
Dixell XC645D[48]LED alarm steadyAn alarm is active; read the code. (The manual does not give the colour.)
Dixell XC645D[48]LED alarm-log flashingA new alarm has occurred; open the alarm log. (The manual does not give the colour.)
Dixell XR35CX[52]LED alarm steadyAn alarm is active; read the code on the display. (The manual does not give the colour.)
Dixell XWi70K[56]LED alarm steadyAn alarm is active; read the code (in Pr2 it marks parameters also present in Pr1). (The manual does not give the colour.)
Carel µChiller[60]Service (spanner) icon flashingSerious alarm that needs a qualified technician; read the code. (The manual does not give the colour.)
Danfoss GD gas detection (Basic/Premium/Heavy Duty units, controller unit)[72]LED yellow steadyA fault is pending (see System Errors / error memory).
Danfoss DHP heat pumps (DHP-A/AL/C/H/L)[76]Alarm indicator flashingAn alarm has blocked the heat pump (e.g. HP/LP switch, overheat protector); read the text and reset by switching the operating mode to OFF and back. (The manual does not give the colour.)
AHT GD-Cooler (GD-XLS, GD-XL)[84]Display code flashing alternating with temperatureA fault is active (P1, P2, HA, LA, noL); it stays until the fault is cleared. (The manual does not give the colour.)
RDM Mercury 3 Twin Coil[92]LED alarm steadyAn alarm is active; read the message on the display. (The manual does not give the colour.)
Kriwan INT69 UY Diagnose[96]LED green / orange (warning)Warning: machine in a critical range but still running; count green then orange pulses, same numbering as the red error codes.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]ON/OFF lamp green blinking (wired remote)Remote controller is starting up, or the unit has stopped on an error; read the check code.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp green blinking (indoor unit)Unit stopped on a malfunction; run the self-check to read the code.
Mitsubishi Electric Mr. Slim PLA-RP indoor units (check codes)[104]Operation lamp B 14 flashesOther outdoor error; see the outdoor unit service manual (pattern B = outdoor/other unit: lamp on for about 3 s, then the flashes).
Copeland Electronic Unit Controller[116]LED alarm-menu flashingA new alarm has been recorded. (The manual does not give the colour.)
Copeland Electronic Unit Controller[116]LED alarm steadyAn alarm is active; read the code on the display. (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Timer + Ready alternate blinkingIndoor fan, drain overflow or liquid backflow fault (P01, P10, P12, P13); read the 7-segment code. (Operation off.) (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Light block Operation + Ready alternate blinkingOutdoor protective stop (P03–P31: discharge temp., HP switch, phase/voltage, heat sink, gas leak, 4-way valve, fan IPDU …); read the 7-segment code. (Timer off.) (The manual does not give the colour.)
Toshiba VRF SMMS / SHRM / Mini-SMMS (MMY, MCY, MMU, MML, MMD, MMF, MMC indoor units; check codes)[124]Indoor P.C. board LED flashing (CHK pin test)During the CHK-pin test the float switch or fan motor is abnormal (LED is lit when normal). (The manual does not give the colour.)
RDM Mercury / Intuitive Mercury case and coldroom controllers[128]LED alarm steadyAn alarm is active (e.g. MOP); read the message on the display. (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Status bar red flashingNew alarm active; sounder on. Press accept to mute.
RDM Intuitive Superpack / Transcritical Superpack[132]Status bar red steadyAlarm still active but accepted (sounder muted); bar returns to blue when the alarm clears.
Eliwell controller (Beverage-Air DW deep well refrigerators)[148]Alarm LED steadyAn alarm is active; read the code. (The manual does not give the colour.)
Taylor R160 frozen food dispenser[156]Alarm LED steadyAn alarm is active; read the code (HA, LA, P1). (The manual does not give the colour.)
Carel MPXzero (Hillphoenix display cases)[160]Alarm icon red flashingAn alarm is active; the code is shown on the display.
Carel MPXzero (Hillphoenix display cases)[160]Alarm icon red steadyAlarm acknowledged (still present until the cause clears).
BAC Nexus modular hybrid cooler (NXF controls)[172]Alarm button redAn alarm is present; press the button to show the alarm description.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]EE:EEAn error is stored: switch the unit off and hold the two buttons given for the model (e.g. Energy Save + Zone Control, or both temperature buttons) for about 3–5 s to show the code and unit address.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 6 + LED 2 steadyThe indoor unit reports a fault; read the code at the indoor unit.
Staff BTX/BFX automatic batch freezers (BTX150, BFX150, BFX200, BFX201, BFX400, BFX600, BFX1000, BFX1500)[193]Long repeated beepsMachine alarm (agitator motor thermal protection, inverter alarm or memory alarm); read the error shown on the display.
Fujitsu AIRSTAGE J-II VRF – wired and simple remote controllers UTY-RNK*, UTY-RSK*, UTY-RHK* (error code on the display)[197]9UOutdoor unit error: the fault is in the outdoor unit. Read the code on the outdoor 7-segment display (E.xx.x) or with the group RC.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.5U.1Indoor unit error: an indoor unit has a fault; press SELECT/ENTER to see which address. Check that indoor unit’s code (indoor troubleshooting 1–11).
Fujitsu AIRSTAGE J-II VRF – network convertor UTY-VGGX (group remote or single split connection)[202]5UIndoor or outdoor unit error on the unit connected to the convertor. Read and clear the fault on that indoor or outdoor unit.
Fujitsu AIRSTAGE J-II VRF – indoor units (Operation/Timer/Filter lamps)[199]Operation 9 + Timer 15 + Filter flashing fastOutdoor unit error (code 9U): read the outdoor 7-segment display. Some outdoor faults are not shown on the indoor unit. The Filter lamp flickers fast (0.1 s) as the error marker; Operation and Timer flash their counts in turn. (The manual does not give the colour.)
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]LED102 ERROR flashing fastAn error is active (LED102 flashes about 0.1 s on/off while LED101 stays lit); the display shows Err. and the code, step through several codes with SELECT.
LAE BR1-27/BR1-28/BR5-A/BR5-B/BD1-28/CD25[165]Icon alarm steadyAn alarm is active; any key mutes the buzzer. (The manual does not give the colour.)
Thermia Atella / Robust[114]Alarm indicator green flashingAn alarm is active; the alarm text is shown in the display.
Carel MasterCella[7]Alarm icon flashingAn alarm is active, e.g. high/low temperature or an external digital-input alarm. (The manual does not give the colour.)
Carel MasterCella[7]Service icon (spanner) flashingInternal fault such as an EEPROM error or a probe fault; call service. (The manual does not give the colour.)
Carel MasterCella[7]HACCP icon flashingNew HACCP alarms (HA and/or HF) are stored. (The manual does not give the colour.)
Carel pRack pR300T (transcritical CO2)[23]Main screen alarm signal (field 4)The main screen shows a signal that an alarm is active. (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Remote display fault LED1 (pressure) onRemote display LED1 signals a pressure fault. (The manual does not give the colour.)
RDM Intuitive Superpack / Transcritical Superpack[132]Remote display fault LED2 (status input) onRemote display LED2 signals a status-input fault. (The manual does not give the colour.)
Carel ir33+ VCC[20]Service (spanner) icon flashing with alarm iconShown together with the flashing alarm icon for probe faults, pump-down, low pressure, condenser, door, EEPROM and VCC faults. (The manual does not give the colour.)
Carel ir33+ VCC[20]HACCP icon flashing (HA/HF)A HACCP alarm (HA or HF) has been recorded. (The manual does not give the colour.)
Störk-Tronic ST121 / ST501 / ST551[93]ST551 LED1 on (default)With factory settings LED1 on the ST551 shows an alarm. (The manual does not give the colour.)
Pego 202BASE electronic board[167]LED alarm steadyAn EL or EH temperature alarm has cleared but stays shown until acknowledged with the mute key. (The manual does not give the colour.)
Dixell XW270L/XW271L[9]LED alarm onAn alarm is active; in the Pr2 menu it instead marks a parameter that is also in Pr1. (The manual does not give the colour.)
Eliwell ID 974[13]LED alarm onAn alarm is active (buzzer sounds if fitted). (The manual does not give the colour.)
Evco EV3 300 series[108]LED alarm steadyAn alarm is active; read the code on the display. (The manual does not give the colour.)
Evco EVK214[109]LED HACCP blinkingAt least one new HACCP alarm has been stored; view it in the LS list. (The manual does not give the colour.)
Evco EVK214[109]LED alarm steadyAn alarm or error is active; read the code on the display. (The manual does not give the colour.)

The lamp or symbol only shows that an alarm is active; the code in the display or the alarm list tells which.

Check: Read the code in the display or the alarm log and look it up on this page.

Thermal disinfection (legionella) not completed

ControllerCode
IVT AirX air-to-water heat pump[175]5284The hot water peak did not reach 65 °C within its three-hour window; a new attempt is made the following night.
IVT AirSplit 200/300 split air-to-water heat pump[176]5284Thermal disinfection failed: continuous hot water draw or heater output too low for the tank volume; retried the next day.
IVT Geo 500/600 series ground source heat pump[177]5284Thermal disinfection (legionella peak) failed: heater overheat protector tripped, continuous hot water draw or heater output too low; retried the next day.
IVT Geo 312/412 ground source heat pump[178]5284Thermal disinfection failed: heater overheat protector tripped, hot water drawn continuously, or heater output set too low for the tank volume.
IVT Vent 202/302/402 exhaust air heat pump[179]5284Thermal disinfection failed: continuous hot water draw or heater output too low for the tank volume; retried the next day.

The hot water tank did not reach the disinfection temperature within the time allowed, so the anti-legionella cycle was not completed; most units try again at the next scheduled time.

Check: Check whether hot water was drawn during the cycle, that the immersion heater works and its overheat protector has not tripped, that its output is high enough for the tank volume and that the tank sensor sits correctly. Repeated failures leave the tank without legionella protection.

Brine temperature out of range

ControllerCode
IVT Geo 500/600 series ground source heat pump[177]5547Incoming brine TB0 below about -6 °C (borehole) or 2 °C (groundwater) (warning).
IVT Geo 500/600 series ground source heat pump[177]5549Incoming brine TB0 below about -6 °C (borehole) or 2 °C (groundwater) (alarm).
IVT Geo 500/600 series ground source heat pump[177]5551Brine sensor TB1 below about -6 °C (borehole) or 2 °C (groundwater) (warning).
IVT Geo 500/600 series ground source heat pump[177]5553Brine sensor TB1 below about -6 °C (borehole) or 2 °C (groundwater) (alarm).
IVT Geo 500/600 series ground source heat pump[177]5555Incoming brine TB0 too warm (warning).
IVT Geo 500/600 series ground source heat pump[177]5557Incoming brine TB0 too warm (alarm).
IVT Geo 500/600 series ground source heat pump[177]5559Brine sensor TB1 too warm (warning).
IVT Geo 500/600 series ground source heat pump[177]5561Brine sensor TB1 too warm (alarm).
IVT Geo 500/600 series ground source heat pump[177]5585The low pressure transmitter indicates a problem on the brine side (too cold brine or too little brine flow).
IVT Geo 312/412 ground source heat pump[178]5547Incoming brine TB0 below about -6 °C (borehole) or 2 °C (groundwater) (warning).
IVT Geo 312/412 ground source heat pump[178]5549Incoming brine TB0 below about -6 °C (borehole) or 2 °C (groundwater) (alarm).
IVT Geo 312/412 ground source heat pump[178]5551Brine sensor TB1 below about -6 °C (borehole) or 2 °C (groundwater) (warning).
IVT Geo 312/412 ground source heat pump[178]5553Brine sensor TB1 below about -6 °C (borehole) or 2 °C (groundwater) (alarm).
IVT Geo 312/412 ground source heat pump[178]5555Incoming brine TB0 too warm (warning).
IVT Geo 312/412 ground source heat pump[178]5557Incoming brine TB0 too warm (alarm).
IVT Geo 312/412 ground source heat pump[178]5559Brine sensor TB1 too warm (warning).
IVT Geo 312/412 ground source heat pump[178]5561Brine sensor TB1 too warm (alarm).
IVT Geo 312/412 ground source heat pump[178]5585The low pressure transmitter indicates a problem on the brine side (too cold brine or too little brine flow).

The brine (collector fluid) entering or leaving a ground or water source heat pump is colder or warmer than the limits for the collector type, so the unit warns and then stops the compressor.

Check: Compare the brine in and out temperatures with the limits, check the brine flow (pump, strainer, air), the antifreeze concentration and whether the borehole or ground loop is undersized or overloaded by long running at high output. Too warm brine can point to a wrong sensor or an external heat source in the loop.

Water or brine temperature sensor fault

ControllerCode
IVT AirX air-to-water heat pump[175]5204Supply (flow) temperature sensor T0: open circuit.
IVT AirX air-to-water heat pump[175]5205Supply (flow) temperature sensor T0: short circuit.
IVT AirX air-to-water heat pump[175]5206Supply temperature sensor T0 alarm after three faults within 3 h or a fault lasting 30 min.
IVT AirX air-to-water heat pump[175]5207Heating-medium outlet sensor TC1 (water leaving the heat pump): open circuit.
IVT AirX air-to-water heat pump[175]5208Heating-medium outlet sensor TC1 (water leaving the heat pump): short circuit.
IVT AirX air-to-water heat pump[175]5209Heating-medium outlet sensor TC1 (water leaving the heat pump): faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5213Heating-medium return sensor TC0 (water entering the heat pump): open circuit.
IVT AirX air-to-water heat pump[175]5214Heating-medium return sensor TC0 (water entering the heat pump): short circuit.
IVT AirX air-to-water heat pump[175]5215Heating-medium return sensor TC0 (water entering the heat pump): faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5234Pool temperature sensor TP1: open circuit.
IVT AirX air-to-water heat pump[175]5235Pool temperature sensor TP1: short circuit.
IVT AirX air-to-water heat pump[175]5236Pool temperature sensor TP1: faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5237Hot water sensor TW1: open circuit.
IVT AirX air-to-water heat pump[175]5238Hot water sensor TW1: short circuit.
IVT AirX air-to-water heat pump[175]5239Hot water sensor TW1: faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5320Condenser outlet sensor TC3 (heating water leaving the condenser): open circuit.
IVT AirX air-to-water heat pump[175]5321Condenser outlet sensor TC3 (heating water leaving the condenser): short circuit.
IVT AirX air-to-water heat pump[175]5322Condenser outlet sensor TC3 (heating water leaving the condenser): faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5204Supply (flow) temperature sensor T0: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5205Supply (flow) temperature sensor T0: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5206Supply temperature sensor T0 alarm after three faults within 3 h or a fault lasting 30 min.
IVT AirSplit 200/300 split air-to-water heat pump[176]5207Heating-medium outlet sensor TC1 (water leaving the heat pump): open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5208Heating-medium outlet sensor TC1 (water leaving the heat pump): short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5209Heating-medium outlet sensor TC1 (water leaving the heat pump): faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5213Heating-medium return sensor TC0 (water entering the heat pump): open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5214Heating-medium return sensor TC0 (water entering the heat pump): short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5215Heating-medium return sensor TC0 (water entering the heat pump): faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5234Pool temperature sensor TP1: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5235Pool temperature sensor TP1: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5236Pool temperature sensor TP1: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5237Hot water sensor TW1: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5238Hot water sensor TW1: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5239Hot water sensor TW1: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5320Condenser outlet sensor TC3 (heating water leaving the condenser): open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5321Condenser outlet sensor TC3 (heating water leaving the condenser): short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5322Condenser outlet sensor TC3 (heating water leaving the condenser): faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5204Supply (flow) temperature sensor T0: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5205Supply (flow) temperature sensor T0: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5206Supply (flow) temperature sensor T0: faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5207Heating-medium outlet sensor TC1 (water leaving the heat pump): open circuit.
IVT Geo 500/600 series ground source heat pump[177]5208Heating-medium outlet sensor TC1 (water leaving the heat pump): short circuit.
IVT Geo 500/600 series ground source heat pump[177]5209Heating-medium outlet sensor TC1 (water leaving the heat pump): faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5213Heating-medium return sensor TC0 (water entering the heat pump): open circuit.
IVT Geo 500/600 series ground source heat pump[177]5214Heating-medium return sensor TC0 (water entering the heat pump): short circuit.
IVT Geo 500/600 series ground source heat pump[177]5215Heating-medium return sensor TC0 (water entering the heat pump): faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5234Pool temperature sensor (TP1, called TC1 in the description): open circuit.
IVT Geo 500/600 series ground source heat pump[177]5235Pool temperature sensor: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5236Pool temperature sensor alarm after three faults within 3 h or 15 min with an open or short circuit.
IVT Geo 500/600 series ground source heat pump[177]5237Hot water sensor TW1: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5238Hot water sensor TW1: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5239Hot water sensor TW1: faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5320Condenser sensor TC3 (heating water leaving the condenser): open circuit.
IVT Geo 500/600 series ground source heat pump[177]5321Condenser sensor TC3 (heating water leaving the condenser): short circuit.
IVT Geo 500/600 series ground source heat pump[177]5322Condenser sensor TC3 (heating water leaving the condenser): faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5545Both brine sensors TB0 (in) and TB1 (out) are open or short-circuited.
IVT Geo 500/600 series ground source heat pump[177]5571Brine in sensor TB0: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5573Brine in sensor TB0: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5575Brine in sensor TB0 faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5577Brine out sensor TB1: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5579Brine out sensor TB1: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5581Brine out sensor TB1 faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]6216Upper hot water sensor TW2 signal outside the allowed range (info).
IVT Geo 500/600 series ground source heat pump[177]6217No signal from upper hot water sensor TW2 (info).
IVT Geo 500/600 series ground source heat pump[177]6218Upper hot water sensor TW2 signal outside the allowed range (alarm).
IVT Geo 312/412 ground source heat pump[178]5204Supply (flow) temperature sensor T0: open circuit.
IVT Geo 312/412 ground source heat pump[178]5205Supply (flow) temperature sensor T0: short circuit.
IVT Geo 312/412 ground source heat pump[178]5206Supply (flow) temperature sensor T0: faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5207Heating-medium outlet sensor TC1 (water leaving the heat pump): open circuit.
IVT Geo 312/412 ground source heat pump[178]5208Heating-medium outlet sensor TC1 (water leaving the heat pump): short circuit.
IVT Geo 312/412 ground source heat pump[178]5209Heating-medium outlet sensor TC1 (water leaving the heat pump): faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5213Heating-medium return sensor TC0 (water entering the heat pump): open circuit.
IVT Geo 312/412 ground source heat pump[178]5214Heating-medium return sensor TC0 (water entering the heat pump): short circuit.
IVT Geo 312/412 ground source heat pump[178]5215Heating-medium return sensor TC0 (water entering the heat pump): faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5234Pool temperature sensor (TP1, called TC1 in the description): open circuit.
IVT Geo 312/412 ground source heat pump[178]5235Pool temperature sensor: short circuit.
IVT Geo 312/412 ground source heat pump[178]5236Pool temperature sensor alarm after three faults within 3 h or 15 min with an open or short circuit.
IVT Geo 312/412 ground source heat pump[178]5237Hot water sensor TW1: open circuit.
IVT Geo 312/412 ground source heat pump[178]5238Hot water sensor TW1: short circuit.
IVT Geo 312/412 ground source heat pump[178]5239Hot water sensor TW1: faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5320Condenser sensor TC3 (heating water leaving the condenser): open circuit.
IVT Geo 312/412 ground source heat pump[178]5321Condenser sensor TC3 (heating water leaving the condenser): short circuit.
IVT Geo 312/412 ground source heat pump[178]5322Condenser sensor TC3 (heating water leaving the condenser): faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5545Both brine sensors TB0 (in) and TB1 (out) are open or short-circuited.
IVT Geo 312/412 ground source heat pump[178]5571Brine in sensor TB0: short circuit.
IVT Geo 312/412 ground source heat pump[178]5573Brine in sensor TB0: open circuit.
IVT Geo 312/412 ground source heat pump[178]5575Brine in sensor TB0 faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5577Brine out sensor TB1: short circuit.
IVT Geo 312/412 ground source heat pump[178]5579Brine out sensor TB1: open circuit.
IVT Geo 312/412 ground source heat pump[178]5581Brine out sensor TB1 faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5204Supply (flow) temperature sensor T0: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5205Supply (flow) temperature sensor T0: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5206Supply temperature sensor T0 alarm after three faults within 3 h or a fault lasting 30 min.
IVT Vent 202/302/402 exhaust air heat pump[179]5207Heating-medium outlet sensor TC1 (water leaving the heat pump): open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5208Heating-medium outlet sensor TC1 (water leaving the heat pump): short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5209Heating-medium outlet sensor TC1 (water leaving the heat pump): faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5213Heating-medium return sensor TC0 (water entering the heat pump): open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5214Heating-medium return sensor TC0 (water entering the heat pump): short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5215Heating-medium return sensor TC0 (water entering the heat pump): faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5234Pool temperature sensor TP1: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5235Pool temperature sensor TP1: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5236Pool temperature sensor TP1: faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5237Hot water sensor TW1: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5238Hot water sensor TW1: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5239Hot water sensor TW1: faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5320Condenser outlet sensor TC3 (heating water leaving the condenser): open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5321Condenser outlet sensor TC3 (heating water leaving the condenser): short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5322Condenser outlet sensor TC3 (heating water leaving the condenser): faulty (alarm stage).

A temperature sensor on the water side (supply, return, heating medium, hot water, pool or brine) reads open circuit, short circuit or an implausible value, so the unit runs on a fallback value or stops the function that uses it.

Check: Measure the sensor resistance against the manufacturer's table at a known temperature, check the cable and terminals for breaks, damage and moisture, and check that the sensor sits properly in its pocket or on the pipe.

Refrigerant circuit temperature sensor fault

ControllerCode
IVT AirX air-to-water heat pump[175]5314Discharge (hot gas) sensor TR6: open circuit.
IVT AirX air-to-water heat pump[175]5315Discharge (hot gas) sensor TR6: short circuit.
IVT AirX air-to-water heat pump[175]5316Discharge (hot gas) sensor TR6: faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5414Liquid line sensor TR3 (heating mode): open circuit.
IVT AirX air-to-water heat pump[175]5415Liquid line sensor TR3 (heating mode): short circuit.
IVT AirX air-to-water heat pump[175]5416Liquid line sensor TR3 (heating mode): faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5420Liquid line sensor TR4 (cooling mode): open circuit.
IVT AirX air-to-water heat pump[175]5421Liquid line sensor TR4 (cooling mode): short circuit.
IVT AirX air-to-water heat pump[175]5422Liquid line sensor TR4 (cooling mode): faulty (alarm stage).
IVT AirX air-to-water heat pump[175]5531Compressor temperature sensor TR1: open circuit.
IVT AirX air-to-water heat pump[175]5532Compressor temperature sensor TR1: short circuit.
IVT AirX air-to-water heat pump[175]5533Compressor temperature sensor TR1: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5314Discharge (hot gas) sensor TR6: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5315Discharge (hot gas) sensor TR6: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5316Discharge (hot gas) sensor TR6: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5414Liquid line sensor TR3 (heating mode): open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5415Liquid line sensor TR3 (heating mode): short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5416Liquid line sensor TR3 (heating mode): faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5420Liquid line sensor TR4 (cooling mode): open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5421Liquid line sensor TR4 (cooling mode): short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5422Liquid line sensor TR4 (cooling mode): faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5531Compressor temperature sensor TR1: open circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5532Compressor temperature sensor TR1: short circuit.
IVT AirSplit 200/300 split air-to-water heat pump[176]5533Compressor temperature sensor TR1: faulty (alarm stage).
IVT AirSplit 200/300 split air-to-water heat pump[176]5622Discharge (hot gas) sensor TR6 fault, LG code 41 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5623Discharge (hot gas) sensor TR6 fault, LG code 41 (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5626Evaporator (probably mid-coil) temperature sensor TR8 fault, LG code 45 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5627Evaporator (probably mid-coil) temperature sensor TR8 fault, LG code 45 (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5650Condenser outlet temperature sensor TR7: open circuit (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5651Condenser outlet temperature sensor TR7: short circuit (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5652Condenser outlet temperature sensor TR7 faulty (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5656Condenser inlet temperature sensor TR3: open circuit (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5657Condenser inlet temperature sensor TR3: short circuit (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5658Condenser inlet temperature sensor TR3 faulty (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5664Evaporator inlet temperature sensor TR4 open or short-circuited, LG code 48 (info).
IVT AirSplit 200/300 split air-to-water heat pump[176]5665Evaporator inlet temperature sensor TR4 faulty, LG code 48.
IVT Geo 500/600 series ground source heat pump[177]5314Discharge (hot gas) sensor TR6: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5315Discharge (hot gas) sensor TR6: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5316Discharge (hot gas) sensor TR6: faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5414Liquid line sensor TR3 (heating mode): open circuit.
IVT Geo 500/600 series ground source heat pump[177]5415Liquid line sensor TR3 (heating mode): short circuit.
IVT Geo 500/600 series ground source heat pump[177]5416Liquid line sensor TR3 (heating mode): faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5420Liquid line sensor TR4 (cooling mode): open circuit.
IVT Geo 500/600 series ground source heat pump[177]5421Liquid line sensor TR4 (cooling mode): short circuit.
IVT Geo 500/600 series ground source heat pump[177]5422Liquid line sensor TR4 (cooling mode): faulty (alarm stage).
IVT Geo 500/600 series ground source heat pump[177]5531Compressor temperature sensor TR1: open circuit.
IVT Geo 500/600 series ground source heat pump[177]5532Compressor temperature sensor TR1: short circuit.
IVT Geo 500/600 series ground source heat pump[177]5533Compressor temperature sensor TR1: faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5314Discharge (hot gas) sensor TR6: open circuit.
IVT Geo 312/412 ground source heat pump[178]5315Discharge (hot gas) sensor TR6: short circuit.
IVT Geo 312/412 ground source heat pump[178]5316Discharge (hot gas) sensor TR6: faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5414Liquid line sensor TR3 (heating mode): open circuit.
IVT Geo 312/412 ground source heat pump[178]5415Liquid line sensor TR3 (heating mode): short circuit.
IVT Geo 312/412 ground source heat pump[178]5416Liquid line sensor TR3 (heating mode): faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5420Liquid line sensor TR4 (cooling mode): open circuit.
IVT Geo 312/412 ground source heat pump[178]5421Liquid line sensor TR4 (cooling mode): short circuit.
IVT Geo 312/412 ground source heat pump[178]5422Liquid line sensor TR4 (cooling mode): faulty (alarm stage).
IVT Geo 312/412 ground source heat pump[178]5531Compressor temperature sensor TR1: open circuit.
IVT Geo 312/412 ground source heat pump[178]5532Compressor temperature sensor TR1: short circuit.
IVT Geo 312/412 ground source heat pump[178]5533Compressor temperature sensor TR1: faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5314Discharge (hot gas) sensor TR6: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5315Discharge (hot gas) sensor TR6: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5316Discharge (hot gas) sensor TR6: faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5414Liquid line sensor TR3 (heating mode): open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5415Liquid line sensor TR3 (heating mode): short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5416Liquid line sensor TR3 (heating mode): faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5420Liquid line sensor TR4 (cooling mode): open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5421Liquid line sensor TR4 (cooling mode): short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5422Liquid line sensor TR4 (cooling mode): faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5531Compressor temperature sensor TR1: open circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5532Compressor temperature sensor TR1: short circuit.
IVT Vent 202/302/402 exhaust air heat pump[179]5533Compressor temperature sensor TR1: faulty (alarm stage).
IVT Vent 202/302/402 exhaust air heat pump[179]5597Evaporator temperature sensor TR4: short circuit (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5598Evaporator temperature sensor TR4: open circuit (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5599Evaporator temperature sensor TR4 faulty (alarm).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 2 + Timer 3Indoor coil (pipe) thermistor open or short circuit (code 04/05): measure the thermistor; replace the PCB only if the sensor is good.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 2 + Timer 4Indoor heat exchanger (middle) thermistor fault on models that have a second coil sensor.
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 3 + Timer 2Discharge pipe thermistor open or short circuit (code 0C/0d).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 3 + Timer 3Outdoor heat exchanger thermistor open or short circuit (code 06/07).
Fujitsu inverter wall-mounted split (indoor Operation/Timer lamps)[180]Operation 3 + Timer 8Compressor body thermistor open or short circuit (code 15).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 2 + Timer 3Indoor heat exchanger thermistor open or short circuit (04/05).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Timer 2Discharge pipe thermistor fault (0C/0d).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Timer 3Outdoor heat exchanger thermistor fault (06/07).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Air Clean 2Thermistor at the 2-way (liquid) valve of this indoor unit's circuit is faulty (1d).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Air Clean 3Thermistor at the 3-way (gas) valve of this indoor unit's circuit is faulty (1E).
Fujitsu multi-zone indoor units ASU/ARU/AUU …RML (Operation/Timer/Air Clean/Coil Dry lamps)[181]Operation 3 + Timer 8Compressor thermistor fault (15).
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 2 flashesOutdoor discharge pipe thermistor fault.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 3 flashesOutdoor heat exchanger thermistor fault.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 5 flashes2-way (liquid) valve thermistor for indoor unit A is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 2 5 flashes2-way (liquid) valve thermistor for indoor unit B is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 3 5 flashes2-way (liquid) valve thermistor for indoor unit C is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 6 flashes3-way (gas) valve thermistor for indoor unit A is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 2 6 flashes3-way (gas) valve thermistor for indoor unit B is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 3 6 flashes3-way (gas) valve thermistor for indoor unit C is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 4 6 flashes3-way (gas) valve thermistor for indoor unit D is faulty.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 7 flashesCompressor thermistor fault.
Fujitsu multi-zone outdoor unit AOU24RML/AOU36RML (PCB LED 1–4)[182]LED 1 16 flashesOutdoor heat exchanger middle thermistor fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]04Indoor coil (pipe) thermistor open circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]05Indoor coil (pipe) thermistor short circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]06Outdoor coil (pipe) thermistor open circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]07Outdoor coil (pipe) thermistor short circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]0CDischarge pipe thermistor open circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]0dDischarge pipe thermistor short circuit.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]15Compressor temperature thermistor fault.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]1d2-way (liquid) valve thermistor fault (multi units).
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]1E3-way (gas) valve thermistor fault on multi units; the older UK guide lists an expansion valve error.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]28Indoor heat exchanger temperature abnormal.
Fujitsu wired remote controller (error code + unit address after EE:EE)[183]29Outdoor heat exchanger middle temperature abnormal.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E4:00Indoor coil thermistor open circuit or missing.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E5:00Indoor coil thermistor short circuit.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E6:00Outdoor coil thermistor open circuit or missing.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]E7:00Outdoor coil thermistor short circuit.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]EC:00Discharge pipe thermistor open circuit.
Fujitsu wired remote controller, older models (E-codes with unit address)[184]ED:00Discharge pipe thermistor short circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 3Outdoor pipe thermistor fault.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 5Discharge thermistor open circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 5 + Swing blinkingDischarge thermistor short circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation blinking + Timer 9Compressor temperature thermistor fault.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 3 + Timer blinkingIndoor pipe thermistor open circuit.
Fujitsu cassette, ceiling and duct units AUY/ABY/AWY with wireless remote (older, UK)[185]Operation 3 + Timer blinking + Swing blinkingIndoor pipe thermistor short circuit.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red 2 + Green blinking, test button: Red blinking + Green 3Indoor sensor fault group; after the test button: indoor pipe thermistor.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 2, test button: Red 2 + Green blinkingOutdoor thermistor group; after the test button: discharge thermistor.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 2, test button: Red 4 + Green blinkingOutdoor thermistor group; after the test button: outdoor pipe thermistor.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 2, test button: Red 8 + Green blinkingOutdoor thermistor group; after the test button: compressor temperature thermistor.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 2, test button: Red 9 + Green blinkingOutdoor thermistor group; after the test button: 2-way valve thermistor.
Fujitsu wall-mounted multi indoor units (older, UK; two-stage lamp code)[186]Red blinking + Green 2, test button: Red 10 + Green blinkingOutdoor thermistor group; after the test button: 3-way valve thermistor.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 2Discharge thermistor fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 3Outdoor pipe thermistor fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 52-way valve thermistor fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 63-way valve thermistor fault.
Fujitsu inverter outdoor unit PCB, models 9–30 (older, one red LED)[187]LED red 7Compressor thermistor fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 2Discharge thermistor fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 3Outdoor pipe thermistor fault.
Fujitsu inverter outdoor unit PCB, models 36–54 (older, one red LED)[188]LED red 7Compressor thermistor fault.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 2 + LED 2 steadyDischarge temperature thermistor fault.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 3 + LED 2 steadyOutdoor pipe thermistor fault.
Fujitsu non-inverter outdoor unit PCB (older, two red LEDs)[189]LED 1 10 + LED 2 steadyCompressor temperature thermistor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 2 flashesDischarge thermistor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 3 flashesOutdoor pipe thermistor fault.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 5 flashes2-way valve thermistor fault on this circuit.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 6 flashes3-way valve thermistor fault on this circuit.
Fujitsu inverter multi outdoor unit AOY30 (older, LEDs A–D)[190]LED A–D 7 flashesCompressor thermistor fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 3 short + Green rapid (D, E, F)Indoor pipe sensor open circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red 3 short + Green rapid + Yellow rapid (E, F)Indoor pipe sensor short circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red long + Green 3 short (C)Pipe sensor fault.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 3 short (F)Outdoor pipe sensor open circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 3 short + Yellow rapid (F)Outdoor pipe sensor short circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 5 short (F)Discharge sensor open circuit.
Fujitsu older wireless-remote indoor units ASY/ABY/AUY (UK model groups A–G, three lamps)[191]Red rapid + Green 5 short + Yellow rapid (F)Discharge sensor short circuit.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]71Outdoor discharge thermistor TH1 open or short (E.71.1). Measure it against the thermistor A table.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]72Outdoor compressor temperature thermistor TH10 open or short (E.72.1). Measure it against the thermistor A table.
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]73Outdoor heat exchanger liquid pipe thermistor TH5 open or short (E.73.3).
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]82Sub-cool heat exchanger gas inlet (TH8) or gas outlet (TH9) thermistor fault (E.82.1/E.82.2).
Fujitsu AIRSTAGE J-II VRF – group remote controller UTY-CGGY/UTY-CGGG[198]83Liquid pipe (sub-cool heat exchanger liquid outlet, TH7) thermistor fault (E.83.2).
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.71.1Discharge thermistor TH1 short, or open after the compressor has run 5 min. Check the connector, measure TH1 off the board (thermistor A: about 49.8 kΩ at 25 °C, 6.3 kΩ at 80 °C) and 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.72.1Compressor (body) temperature thermistor TH10 short, or open after 5 min of compressor run. Measure it against the thermistor A table and check 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.73.3Outdoor heat exchanger liquid pipe thermistor TH5 open or short. Measure it (thermistor B: about 4.8 kΩ at 25 °C) and 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.82.1Sub-cool heat exchanger gas inlet thermistor TH8 open or short. Measure it (thermistor B) and 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.82.2Sub-cool heat exchanger gas outlet thermistor TH9 open or short. Measure it (thermistor B) and 5 V DC at the PCB input.
Fujitsu AIRSTAGE J-II VRF – outdoor unit main PCB (7-segment display, LED101/LED102)[200]E.83.2Sub-cool heat exchanger liquid outlet thermistor TH7 open or short. Measure it (thermistor B) and 5 V DC at the PCB input.

A temperature sensor in the refrigerant circuit (discharge, liquid line, compressor body, condenser or evaporator) reads open circuit, short circuit or an implausible value, so the protection or control that relies on it cannot work.

Check: Measure the sensor resistance against the table at a known temperature, check the cable and connector on the circuit board, and that the sensor is fixed and insulated on the right pipe.

Condensation (dew point) guard in cooling mode

ControllerCode
IVT AirX air-to-water heat pump[175]5294Condensation guard tripped in cooling mode: humidity too high, or a short circuit in the sensor or its wiring (warning).
IVT AirX air-to-water heat pump[175]5295Condensation guard tripped in cooling mode: humidity too high, or a short circuit in the sensor or its wiring (alarm).
IVT AirSplit 200/300 split air-to-water heat pump[176]5294Condensation guard tripped in cooling mode: humidity too high, or a short circuit in the sensor or its wiring (warning).
IVT AirSplit 200/300 split air-to-water heat pump[176]5295Condensation guard tripped in cooling mode: humidity too high, or a short circuit in the sensor or its wiring (alarm).
IVT Geo 500/600 series ground source heat pump[177]5294The dew point guard has closed during cooling; not a fault, it clears when the humidity falls.
IVT Geo 500/600 series ground source heat pump[177]5295The dew point warning 5294 has been active for 30 min; must be reset by hand.
IVT Vent 202/302/402 exhaust air heat pump[179]5294Condensation guard tripped in cooling mode: humidity too high, or a short circuit in the sensor or its wiring (warning).
IVT Vent 202/302/402 exhaust air heat pump[179]5295Condensation guard tripped in cooling mode: humidity too high, or a short circuit in the sensor or its wiring (alarm).

During cooling a humidity or condensation sensor on the supply pipe has detected that the pipes or emitters are at or below the dew point, so the unit raises the supply temperature or stops cooling to avoid condensation.

Check: Check the room humidity and the cooling supply temperature setting, that only emitters made for cooling are in the circuit and that pipes are insulated; if the guard trips in dry conditions, check the sensor and its wiring for moisture or a short circuit.

Supply temperature to the heating circuit too high

ControllerCode
IVT AirX air-to-water heat pump[175]3121The temperature limiter on input MC1 of mixing module MM100 for heating circuit 1 has opened (supply too hot, e.g. for floor heating).
IVT AirX air-to-water heat pump[175]3122The temperature limiter on input MC1 of mixing module MM100 for heating circuit 2 has opened (supply too hot, e.g. for floor heating).
IVT AirX air-to-water heat pump[175]3123The temperature limiter on input MC1 of mixing module MM100 for heating circuit 3 has opened (supply too hot, e.g. for floor heating).
IVT AirX air-to-water heat pump[175]3124The temperature limiter on input MC1 of mixing module MM100 for heating circuit 4 has opened (supply too hot, e.g. for floor heating).
IVT AirX air-to-water heat pump[175]5271Supply temperature in heating circuit 1 above its alarm limit; low system pressure, air or low flow are typical causes.
IVT AirX air-to-water heat pump[175]5500The temperature limiter for floor heating on the external input has tripped; reset it and check the heating curve.
IVT AirSplit 200/300 split air-to-water heat pump[176]3121The temperature limiter on input MC1 of mixing module MM100 for heating circuit 1 has opened (supply too hot, e.g. for floor heating).
IVT AirSplit 200/300 split air-to-water heat pump[176]3122The temperature limiter on input MC1 of mixing module MM100 for heating circuit 2 has opened (supply too hot, e.g. for floor heating).
IVT AirSplit 200/300 split air-to-water heat pump[176]3123The temperature limiter on input MC1 of mixing module MM100 for heating circuit 3 has opened (supply too hot, e.g. for floor heating).
IVT AirSplit 200/300 split air-to-water heat pump[176]3124The temperature limiter on input MC1 of mixing module MM100 for heating circuit 4 has opened (supply too hot, e.g. for floor heating).
IVT AirSplit 200/300 split air-to-water heat pump[176]5271Supply temperature in heating circuit 1 above its alarm limit; low system pressure, air or low flow are typical causes.
IVT AirSplit 200/300 split air-to-water heat pump[176]5500The temperature limiter for floor heating on the external input has tripped; reset it and check the heating curve.
IVT Geo 500/600 series ground source heat pump[177]3121The temperature limiter on input MC1 of mixing module MM100 for heating circuit 1 has opened (supply too hot, e.g. for floor heating).
IVT Geo 500/600 series ground source heat pump[177]3122The temperature limiter on input MC1 of mixing module MM100 for heating circuit 2 has opened (supply too hot, e.g. for floor heating).
IVT Geo 500/600 series ground source heat pump[177]5271Supply temperature in heating circuit 1 too high: alarm limit set wrong, or low flow through the heating system.
IVT Geo 500/600 series ground source heat pump[177]5500The floor heating temperature limiter on the external input has tripped; reset it and check the heating curve.
IVT Geo 312/412 ground source heat pump[178]5271Supply temperature in heating circuit 1 too high: alarm limit set wrong, or low flow through the heating system.
IVT Geo 312/412 ground source heat pump[178]5500The floor heating temperature limiter on the external input has tripped; reset it and check the heating curve.
IVT Vent 202/302/402 exhaust air heat pump[179]3121The temperature limiter on input MC1 of mixing module MM100 for heating circuit 1 has opened (supply too hot, e.g. for floor heating).
IVT Vent 202/302/402 exhaust air heat pump[179]3122The temperature limiter on input MC1 of mixing module MM100 for heating circuit 2 has opened (supply too hot, e.g. for floor heating).
IVT Vent 202/302/402 exhaust air heat pump[179]3123The temperature limiter on input MC1 of mixing module MM100 for heating circuit 3 has opened (supply too hot, e.g. for floor heating).
IVT Vent 202/302/402 exhaust air heat pump[179]3124The temperature limiter on input MC1 of mixing module MM100 for heating circuit 4 has opened (supply too hot, e.g. for floor heating).
IVT Vent 202/302/402 exhaust air heat pump[179]5271Supply temperature in heating circuit 1 above its alarm limit; low system pressure, air or low flow are typical causes.
IVT Vent 202/302/402 exhaust air heat pump[179]5500The temperature limiter for floor heating on the external input has tripped; reset it and check the heating curve.

The water sent out to a heating circuit is hotter than its alarm limit, or a temperature limiter (often for floor heating) on that circuit has opened, so the circuit is stopped to protect floors and pipes.

Check: Check the maximum supply temperature and heating curve settings, the mixing valve and its actuator, the flow through the circuit and the limiter setting; reset the limiter only once the cause is found.

Powered (electric) anode fault

ControllerCode
IVT AirSplit 200/300 split air-to-water heat pump[176]5275The powered (electric) anode in the hot water tank is not working.
IVT Geo 500/600 series ground source heat pump[177]5275The powered (electric) anode in the hot water tank is not working.
IVT Geo 312/412 ground source heat pump[178]5275The powered (electric) anode in the hot water tank is not working.
IVT Vent 202/302/402 exhaust air heat pump[179]5275The powered (electric) anode in the hot water tank is not working.

The impressed-current anode that protects the hot water tank against corrosion reports a fault, so the tank may not be protected.

Check: Check that the anode is connected and supplied, its cable and connections, and that the tank is filled with water; measure or replace the anode as the manufacturer describes.

Auger or gear motor speed fault

ControllerCode
NTF linear (auger) granular ice makers, G series (G160, G280, G510/G500, G1000; GB and TB versions)[196]Rotation sensor LED red blinkingAuger speed fault: the sensor measured below about 4 rpm or above about 13 rpm and has stopped the compressor for a new delay period. Check for ice binding in the evaporator (low water, low evaporating temperature), worn evaporator bearings and the gear motor.
NTF linear (auger) granular ice makers, G series (G160, G280, G510/G500, G1000; GB and TB versions)[196]Rotation sensor LED red steadyLock-out after 8 consecutive auger speed faults. Find the cause (auger, bearings, gear motor, water supply, refrigerant charge), then switch the power off and on to reset.

The rotation sensor of an auger (flake, granular or nugget) ice maker sees the auger turning too slowly, too fast or not at all, and stops the compressor; after repeated faults it locks out. Common causes are ice binding in the evaporator, worn evaporator bearings or a failing gear motor.

Check: Check the water supply and level, the evaporating temperature and refrigerant charge (ice binding), the evaporator bearings and auger, and the gear motor and its capacitor; then reset by switching the power off and on.

The selection is our own and does not cover all codes. Source for each controller: the manual and its version.

Sources

  1. Danfoss – User Guide, electronic refrigeration control type ERC 21X series, BC194286421698en-001101 (2025.09); same codes in Installation Guide ERC 213 (DKRCE.PI.RL0.G5, 2016.04) and ERC 214 (AN19438642089705-000401, 2024.06)
  2. Danfoss – User Guide Controller for temperature control EKC 202A, B, C, RS8DZ902 (2018-10)
  3. Danfoss – Service guide (pocket guide) AK-CC 550A, AX278928624187en (2018)
  4. Danfoss – User Guide, controller for condensing unit Optyma Plus, SW 3.7x, BC172686425380en-001202 (2025.12)
  5. Copeland – Application guidelines, outdoor refrigeration units for A2L & A1 (ZXMY/ZXDY), AGL_Unit_ZX_A2L_A1_EN_Rev03, appendix 6; and Copeland ZX quick installation guide, TI_Unit_ZX_10_EN_Rev03
  6. Carel – MPX user manual, +030220191 rel. 2.0 (25/06/2001)
  7. Carel MasterCella – användarmanual, svensk utgåva (AB Kylmateriel), instruktion 4.0178.40 (juni 2001)
  8. Carel – μC2SE electronic control, user manual rel. 2.6 (08.07.2019), table of alarms
  9. Dixell – Installing and operating instructions XW270L–XW271L, 1592009037 r1.0 (03.08.2015)
  10. Daikin Europe – Technical Info ESIE 17-02, parameter and error list Zanotti GM-Uniblock & GS-Split (09/2017)
  11. Carel – ir33 platform user manual (ir33, ir33 power, ir33 DIN, powercompact, mastercella), +030220441 (rel. 2.5, 16.06.2010), chapter 8
  12. Dixell – XR60CX Digital controller with defrost and fans management, user manual 1592020060 (rel. 1.1, 27.04.2015)
  13. Eliwell – IDPlus 902/961/971/974 Elektroniska kontroller för kyl- och frysutrustningar, cod. 9IS54165 (rel. 07/11); Eliwell/Invensys – ID 974 user manual, cod. 9IS42066 (4/2002)
  14. Danfoss – VLT Refrigeration Drive FC 103 Instruction Manual 1.1–90 kW, MG16E322 (Rev. 2014-04-10, software 1.21), warnings and alarms; Operating Instructions 75–630 kW, MG16J202 (Rev. 05/2014), 9.4 table 9.1 Alarm/Warning Code List
  15. Carpigiani – Instruction Handbook AES PSP (AES 261/381/403/503 PSP), aes psp_EN, issue 06 (2012/04), section 5.1
  16. Carel – EVD evolution user manual, +0300005EN (rel. 4.2, 24.01.2024), table of alarms; EVD evolution twin user manual, +0300006EN (rel. 2.4, 30.10.2015), table of alarms
  17. Carel – EVD ice user manual, +0300038EN (rel. 1.2, 20.10.2020), 9.6 alarm table; EVD mini user manual, +0300036EN (rel. 1.2, 23.04.2018), 9.6 alarm table
  18. Carel – Heos high efficiency showcase controller user manual, +0300078EN (rel. 1.6, 23.11.2017), 8.5 alarm table
  19. Carel – ir33 universale electronic control user manual, +030220801 (rel. 2.3, 16.04.2012), 8.5 table of alarms
  20. Carel – ir33+ VCC technical supplement to the ir33+ platform manual, +040000059 (rel. 1.3, 10.09.2018), 6. alarm table (FR/DE/IT edition)
  21. Carel – MPXone user manual, +0300086EN (rel. 2.0, 15.10.2019), 8.4 alarm table
  22. Carel – pRack pR300 compressor rack controller user manual, +0300025EN (rel. 1.3, 17.12.2015), A.4 alarm table
  23. Carel – pRack pR300T user manual for transcritical CO2 systems, +0300018EN (rel. 1.6, 23.07.2020), 7.2 alarm table
  24. Carel – SmartCella/SmartCella 3PH cold room controller user manual, +0300084EN (rel. 1.2, 28.03.2017), 8.4.1 table of alarm signals
  25. Carel – µRack standard compressor racks single/two circuit user manual, +03P220431 (rel. 2.3, 06.06.2012), tab. 7.a
  26. Copeland – EXD-SH1/2 Controller with ModBus communication capability for electrical control valves, operating instructions, P/N 865917 Rev08 (18.11.2025)
  27. Copeland – User manual, Semi-hermetic Stream reciprocating condensing units, 2021/MEA/73 (2021)
  28. Copeland – User manual, ZSI scroll condensing units, 8504574 (2018, ed. 2024)
  29. Copeland – User manual, Large ZX 22–30HP condensing unit, 10746350 (July 2024)
  30. Heatcraft – Beacon II Refrigeration Systems, installation and operation manual, H-IM-79G (June 2020); and MAC Series condensing units, H-IM-67H (March 2018), Beacon II Smart Controller
  31. Sanhua – Electronic expansion valve controller SEC60x series, installation instructions, II-SEC60x-EN-R1709
  32. Danfoss – User Guide, controller for appliance control AK-CC 450, RS8EU702 (2015.10)
  33. Danfoss – User Guide AK-CC 550, RS8EN702 (2016-03); User guide AK-CC 550B, RS8GL402 (2018-11)
  34. Danfoss – User guide AK-CC55 Single Coil & Single Coil UI SW 2.4x, BC364229688105en-010401 (2026.08); User guide AK-CC55 Compact SW 2.3x, BC365212986197en-000302 (2026.08); Installation guide AK-CC55 Single Coil 084R8053, AN294432763974en-000601 (2026.04)
  35. Danfoss – User Guide, case controller for semi plug-in AK-CC55 Water Loop SW 1.2x, BC378540472015en-000101 (2022.04)
  36. Danfoss – Design Guide, controller for evaporator control AK-CC 750 (080Z0130 & 080Z0139), RS8GM222 (10-2014)
  37. Danfoss – User guide Capacity controller AK-PC 781A, Appendix B Alarm texts, RS8HE202 (2017-07)
  38. Danfoss – User Guide Pack controller AK-PC 782A, BC245386497365en-001201 (2026.09) and AK-PC 782B, BC417018981850en-000501 (2026.09), Appendix B Alarm texts
  39. Danfoss – User Guide Optyma control AK-RC 113 three phase, BC317523579312en-000101 (2020.03), section 7.1
  40. Danfoss – User Guide Superheat controller EIM 365 (PV01), BC415322248492en-000101 (2022.09), Alarms
  41. Danfoss – Instructions EKC 202D1 (084R8022), RI8NK459 (06-2015)
  42. Danfoss – Instructions EKC 326A, RI8NG552 (10/2011)
  43. Danfoss – User Guide Superheat controller and stepper valve driver EKE 1A, 1B, 1C, 1D, BC398828796060en-000103 (2024.08), section 8.1
  44. Danfoss – User Guide Superheat Controller EKE 100 (PV04), BC457625021427en-000201 (2026.06), section 6
  45. Danfoss – Instructions Optyma Plus OP-MPS/MPT/LPV/LPK/MPI, section 19 Module B Plus, table 1 error blink code, 118A2177D / AN37261897352602-010602 (2026.06)
  46. Danfoss – Application Guidelines, Optyma iCO2 condensing units R744 50 Hz, sections 9.3, 10.11 and 11, AB399636244436en-000301 (2026.03)
  47. Danfoss – User Guide, temperature controller for walk-in coolers and freezers type AK-RC 251, BC364433930186en-000101 (2021.02)
  48. Dixell – XC645D controller for compressor racks (suction and condenser), 1592001831 r3.5h (14.01.2022)
  49. Dixell – XEV12D on-off electronic expansion valve driver, software rel. 1.6, 1592019040 r1.6 (01.09.2025)
  50. Dixell – XM669K-XM679K controllers for multiplexed cabinets, rel. 5.4j, 1592023190 r5.4 (24.09.2025)
  51. Dixell – XR06CX digital controller with defrost and fans management, 1592020160 r1.2 (27.07.2015)
  52. Copeland (Dixell) – XR35CX Digital Controller I/O Manual, 026-1203 R4 (2024)
  53. Dixell – XR460C dual temperature controller, installing and operating instructions, 1592018110 r2.0 (06.10.2006)
  54. Dixell – XR70CX RTC digital controller with defrost and fans management, 1592020570 r1.0 (27.03.2015)
  55. Dixell – XW60K (and T620T/T620/V620/CX620), 1592026020 r2.3 (08.04.2015); Dixell – XW60L RTC digital controller for medium-low temperature refrigeration, 1592027050 r1.0 (18.03.2015)
  56. Dixell – XWi70K standard controller, FW rel. 21.4, 1592026640 r1.0 (04.06.2020)
  57. Bitzer – VARIPACK external BITZER frequency inverters FDU+6 .. FKU+260, operating instructions CB-100-2 (80060102, 06.2018), chapter 9 fault messages (Tab. 7)
  58. Bitzer – VARIPACK external BITZER frequency inverters, operating instructions CB-110-4 (80061604, 10.2023), STO fault code; VARIPACK IP55/66 operating instructions CB-111-3 (80061703, 11.2021)
  59. Carel – µC2SE for process chiller, user manual, +030220416 (rel. 2.3, 17.05.2018), chapter 8 Alarms (alarms table and 8.2)
  60. Carel – µChiller user manual, +0300053EN (rel. 2.1, 18.05.2021), 8.2 Alarm list
  61. Copeland – Copeland Digital Compressor Controller, AE8-1328 R7 (September 2024), Flash Code Troubleshooting
  62. Copeland (Emerson) – Copeland PerformanceAlert Diagnostic Module, AE8-1347 R3 (March 2016), Table 8 Troubleshooting
  63. Copeland (Emerson) – CoreSense Protection for Copeland Discus Compressors, AE8-1367 R6 (August 2018), Tables 3–6 LED flash codes
  64. Copeland (Emerson) – CoreSense Diagnostics for Copeland Scroll Air Conditioning Compressors, AE8-1379 R2 (February 2015), Tables 1–2
  65. Copeland – Compressor Electronics Communications for 20 to 40 Ton Copeland Air Conditioning Scroll Compressors, AE8-1384 R9 (July 2026), warning and alert/lockout codes, Tables 2 and 6
  66. Copeland – CoreSense Diagnostics for Copeland Scroll UltraTech Air Conditioning Compressors, AE8-1385 R2 (August 2024)
  67. Copeland – CoreSense Communications for 13 to 15 Ton Copeland Scroll Air Conditioning Compressors, AE8-1408 R3 (August 2024)
  68. Emerson (Copeland) – CoreSense Diagnostic Modules for Copeland Scroll Refrigeration Compressors, AE8-1424 (October 2017)
  69. Danfoss – Application Guide Scroll Compressors VZH088-117-170 Gen3, AB300034185311en-000501 (2021.03), Frequency converter troubleshooting; Application guidelines VLZ065 version B with CDS drive, AB444226142054en-000101 (2023.05), Troubleshooting; CDS303/803 Quick troubleshooting guide, AX404427814471en-000101 (2022.03)
  70. Danfoss – VLT HVAC Basic Drive FC 101 Programming Guide, AU275648914272en-000801 / 130R0221 (2024.11, software 6.4x), 5.1 table 23 Alarm/Warning Code List
  71. Danfoss – User Guide Danfoss Gas Sensor type DGS, BC291049702513en-000401 (2024.11), 3.9 Troubleshooting, 5.1 Error status, 5.4 Measuring values
  72. Danfoss – User Guide Gas Detection Units type Basic, Premium and Heavy Duty, BC272555038544en-000201 (2024.09), 4.1 Fault management; User Guide Gas Detection Controller unit and Expansion module, BC272555441546en-000201 (2022.03), 5.1.3 System messages and errors
  73. ebm-papst – User Manual ECCN02-CT0/ECCN06-CT0 BACnet gateway (version 1.0, 2022-01-28), table 5 fan warning and error indicator; CN1116 Modbus Display & Control Operating and Maintenance Instructions, 210-OMI14229-Iss8.1 (2021-10-05), 9 Fault indication and table 9
  74. ebm-papst – Operating instructions K3G310-PV69-03, item no. 57280-5-9970 (change 218409, 2020-09-10), and W3G910-LV12-36, item no. 56913-5-9970 (change 318338, 2025-05-22), 6.1 warning and status codes
  75. Daikin – Simple Self-Diagnosis by Malfunction Code, SM-TS3 (RA, SkyAir, VRV, PA, Heat Reclaim Ventilator; PDF 2014-10); drain codes A3/AF also Daikin AC Americas – VRV Service & Troubleshooting, Participant Guide EGVUSE09-07C (2007)
  76. Danfoss – Service instructions DHP-A, DHP-AL, DHP-C, DHP-H, DHP-L (incl. Opti/Opti Pro), VMGFC302 (2010), 10.1 Alarm and 10.4 Operational problems; Heat Pump Troubleshooting Guide, VMIFB202 (2024)
  77. LG – Multi V 5 Outdoor Units Service Manual, SM_MultiV_5_OutdoorUnits_09_18, Error Codes p. 125–216; Multi V 5 Operation & Maintenance Manual, OM_MULTI-V-5 (06/24), Error Codes
  78. NIBE – Service manual F1255, SEM GB 1609-1 M11932, chapter 6 Troubleshooting, Alarm list
  79. Heatcraft – Installation and Operations Manual A2L Unit Coolers, H-IM-UC-A2L, part no. 25012201 Rev. C (December 2025), section Refrigerant Detection System (RDS)
  80. Secop – Controllers for BD Compressors, Operating Instructions (BD P-Housing), DES.S.100.F2.02 (07-2016); Secop – Instructions Electronic Unit for BD35F/50F/35K/80CN, 101N0242/101N0680/682, DES.I.101.X2.02 / 520N1304 (June 2022)
  81. Secop – SLV Controller 105N46xx Series, Operating Instructions, DES.S.300.A2.02 (February 2013)
  82. AHT Cooling Systems – Betriebsanleitung / Operating manual Athen, Ibiza, Macao, Malta, Manhattan, Miami, Palma, Paris, Salzburg, Singapore, Sydney, SNr. 916026 (361929), status 09/17
  83. AHT Cooling Systems – Supplement Electronic controller NIDEC, Kinley XL, Snr. 377890, version 1 (12/2018); same code list in operating manual SNr. 916026 (361929), status 09/17
  84. AHT Cooling Systems – Betriebsanleitung / Operating instructions GD-Cooler, SNr. 352858, status 09/17
  85. AHT Cooling Systems – Supplementary sheet Electronic controller Danfoss, PNo. 386379 EL/0218
  86. Hussmann – Parallel Rack Systems Installation & Operation Manual, P/N 0427598_E (August 2018); Parallel Rack System & CO2 Cascade Installation & Operation Manual, P/N 3151784_C (October 2025)
  87. Hussmann – Transcritical CO2 Rack, Installation, Operation, and Service Manual, P/N 3182569_G (June 2026)
  88. Hussmann – Pumped Liquid CO2 Secondary Refrigeration, Installation & Operation Manual, P/N 0516803_D (June 2024)
  89. Pego – ECP200 EXPERT PULSE for EEV PULSE 230V, use and maintenance manual (rev. 01-24, software rel. 7), chap. 7 Diagnostics
  90. Pego – ECP202 EXPERT use and maintenance manual (rev. 02-25, software rel. 27), 7.1 Troubleshooting; ECP202 EXPERT D7.5 use and maintenance manual (rev. 01-21, software rel. 26), 7.1 Troubleshooting
  91. Resource Data Management – DMTouch & miniDM Commissioning & User Guide, PR05XX-XX (document revision 4.3.7), alarm indexes
  92. Resource Data Management – Mercury 3 Twin Coil Case Controller Commissioning/User Guide, PR0740/744-TWI (document revision 3.3a), display messages and network alarms
  93. Störk-Tronic – data sheets ST121-KD1KAR.112 (order no. 900323.001, V1.74, 04.11.2021), ST501-KC1KAR.112 (900390.001) and ST551 (900350.034), status displays and error messages
  94. Kriwan – INT69 F Diagnose data sheet, 710.00723.1
  95. Kriwan – INT69 PYF Diagnose data sheet, 710.00721.0
  96. Kriwan – INT69 UY Diagnose data sheet, 710.00650.1
  97. Kriwan – INT69 Y Diagnose data sheet, edition 710.00406.2
  98. Kriwan – INT69 YF Diagnose data sheet, 710.00708.1
  99. Mayekawa – MYPRO TOUCH Device List / MYPRO Touch Area Manual (Modbus), ALARM & FAILURE bits, Ver.208.121.135 (2014-10-23)
  100. Temperzone – UC8 Controller Quick Reference Operation and Fault Diagnosis (1015); Troubleshooting Guide for UC8 (v2, 0715); Service Training Manual, Issue 08 (January 2023)
  101. Temperzone – UC7 Controller Quick Reference Operation and Fault Diagnosis (1114); Troubleshooting Guide for UC7, revision 3 (19 October 2012)
  102. Mitsubishi Electric – MJ-310E Operation Manual (Management), 12 Error code list, WT03239X02
  103. Mitsubishi Electric – Technical & Service Manual SUZ-KA25/35/50/60/71VA4, No. OCH545 (August 2013), 11-2 trouble shooting check table
  104. Mitsubishi Electric – Service Manual PLA-RP35/50/60/71/100/125/140BA, No. OCH416 Revised Edition-D (September 2012), 10-2 and 10-3 self-diagnosis
  105. Goodman – DX20VC Condensing Unit Installation & Service Reference, IOD-4011L (9/2020), troubleshooting fault code table
  106. Krack – Microchannel Remote Air Cooled Condensers installation and operation manual, PN E660159_P, Tables 14–15 and 48 and section 8.3 (KB drive LED status)
  107. Evco – EV3203 instruction sheet, 1043203E103 (checked 2026-10-28)
  108. Evco – EV3 300 series instruction sheet, 1043300E103 (checked 2026-10-28)
  109. Evco – EVK214 instruction sheet, 104K214E05 (checked 2026-10-28)
  110. Evco – EV3 HP / EVD HP manual, 1443DHPE124 (checked 2026-10-28)
  111. Evco – EV3 CHILL / HPRU manual, 1443DCHE304 (checked 2026-10-28)
  112. Evco – EV3 MVC / EVD MVC manual, 1443DMVCE104 (checked 2026-10-28)
  113. Hitachi – Operation Manual P5417020 (2017), section 8.4 Alarm codes
  114. Thermia – Atella user manual 086U8113 (section 10) and Robust user manual 086U4257 (section 4)
  115. Thermia – Calibra user guide BWCA01UG0102 (alarm classes A, B, C; checked 2026-10-28)
  116. Copeland – AE8-1376 Electronic Unit Controller (2013), section 9
  117. Full Gauge Controls – TC-900E POWER instruction manual (Ver.04), section 7 Signals; TC-900E 2HP instruction manual (Ver.06), section 7 Signals
  118. Full Gauge Controls – TC-900E Log instruction manual (Ver.02), Signals
  119. Full Gauge Controls – TC-940R controller for refrigeration and defrost with alarm output (Version 03), 5.7 Indicators and alarms
  120. Full Gauge Controls – MT-512E 2HP instruction manual (Ver.13), 9 Display signalings
  121. Full Gauge Controls – MT-512E Log instruction manual (Ver.09), 9 Signals
  122. Full Gauge Controls – MT-514E Faston instruction manual (Ver.02), 7 Signals
  123. Castel – GoGreen Technical Handbook (R744 products), Handbook 2023, chapter 8.1 Electronic oil level regulators
  124. Toshiba – Service Manual SMMS-i MMY-MAP***4HT8P-E, SVM-13024-8 (2015); also Service Manual SHRM-i MMY-MAP***4FT8-E, A12-006; Service Manual Mini-SMMS MCY-MAP***HT, A05-015 (rev. Jun. 2006); Service Manuals VRF indoor units A10-033-4, A10-1420 (MMF-AP***6H-E), A10-1615 (MMU-AP***7MH-E); Installation Manuals MMU-AP***4HP-E (1114119301), MMD-AP***BHP-E (1115460102), MML-AP***4H-E (EH99879999), MML-AP***4NH-E (1112750209-1); Air-to-Air Heat Exchanger with DX-coil (and Humidifier) service and installation manuals (EH99887601-2); BACnet Interface BMS-IFBN640TLE Service Manual A10-1509
  125. Toshiba – Service Manual RAV-SM***4UTP-E, SVM-13010-5 (2014); also Service Manuals A08-007 (RAV-SM***4SDT-E), A10-1811 (RAV-RM***1MUT-E), A10-1906 (RAV-RM***1FT-ES), SVM-22024 (RAV-HM***01U1TP-E); Installation Manuals 1116950198-1 (RAV-SM***6BTP-E1), EB99819101 (RAV-RM***1MUT-E), EB99819301 (RAV-RM***1SDT-E), H99885801 (RAV-SM***4SDT-E), EB99832901 (RAV-RM***1FT-ES), EB99819501 (RAV-GM***1UT-E), 1114119201 (RAV 4-way cassette); remote controller RBC-AMS55E-ES installation manual
  126. Toshiba – Service Manual RAS-5M34G3AVG-E, SVM-23012 (2023); also SVM-22112 (RAS-2M10/2M14G3AVG-E, 2022), SVM-20012-1 (RAS-B**J2FVG-E console), SVM-18049-5 (RAS-**PKVPG-E / PAVPG-E high wall)
  127. Toshiba – Service Manual HT Hot Water Module MMW-AP0481CHQ-E, A10-1821 (2018); also Installation Manual EB99829001-02 (2024)
  128. Resource Data Management – Mercury & Intuitive Mercury Case Controller Installation & User Guide PR074X/PR075X (software 5.3M & 5.5E, 16-07-25), display messages and network alarms; also Mercury Controller PR0744 CAS (5.1M & 5.4E), Mercury 3 Controller PR0740-CAS (4.0), Mercury 2 & Intuitive Mercury Controller (rev. 2.6e), Mercury 3 Stepper PR0740-STEP (3.5), Mercury & Intuitive Mercury Stepper (V3.5/V3.0, V4.4 24 V, V3.4c mains), Intuitive Mercury LT PR0952 (1.0a), Two Section (Mercury 3 rev. 3.2b/3.3a, Mercury 2 rev. 1.0e), Two Section EEV PR07xx-TSSE (1.0a), Four Section (3.0a), Twin EEV PR07xx-2E-TWINE (3.0/3.1), Mini Intuitive 3 EEV PR068X-3EC (1.9), Mobile (Mercury 3 rev. 3.5, Mercury 2 rev. 1.2), Sub-Cooler Case (1.0b), Frequency Controller PR0740/0744-FQC (1.0g), Mercury T PR0700 (1.2a), Power Tray PR0040–45 (2.0c), Coldroom Panel PR0150 (7.7d), Stepper Coldroom Panel (7.1b), Plate Heat Exchanger PHX (3.8; Mercury 2 stepper PHX 2.4b)
  129. Resource Data Management – Mercury Monitor Installation & User Guide PR0744 MON (software 3.2, rev. L, 28-12-23); also Mercury 3 & Intuitive Mercury Monitor PR0740/PR0750/PR0760-MON (3.2), Mercury 2 & Intuitive Mercury Monitor (1.8b), Mercury 3 & Intuitive 5 Channel Thermostat PR0740/0750-5ISTA (3.2), Mercury 2 & Intuitive 5 Channel Thermostat (1.0d), Control Thermostat PR0740/750-STA (3.0c, 3.1d; Mercury 2 1.0b), Intuitive Mercury Thermostat & Humidistat PR0440 (3.1a)
  130. Resource Data Management – Mercury 3 AC Controller Commissioning/User Guide PR0740-AC (software 3.0, rev. C, 21-6-19); also Mercury 2 & Intuitive Mercury Air Conditioning (1.8a), Mercury 3 and Intuitive Mercury Roof Top Unit Controller PR07XX-RTU (3.3), Mercury 2 & Intuitive Mercury Roof Top Unit Controller (1.5b)
  131. Resource Data Management – Intuitive Mercury Mini Pack / Condenser Controller Installation & User Guide PR0750-MPA (rev. 3.4, 05-12-23); also Mercury 2 & Intuitive Mercury Minipack (1.6a), Intuitive Mercury Two Section Pack Controller (1.6a), Intuitive Plant Pack Controller (4.0d), Mercury 11-10PV Pack Condenser Controller PR033x (6.7c), Mercury 11-5C Condenser PR0266 (2.0a), Mercury 11-10CV PR027x (2.0a), CO2 Mini Transcritical CO2 Controller (1.6a), Mercury 6-10 Step Controller PR033x (rev. 1.6)
  132. Resource Data Management – Intuitive V2 & Mini Transcritical Superpack Commissioning/User Guide PR0650-STCO2 (rev. 5.9, software 6.0, 21-05-25); also Intuitive Transcritical Superpack (3.8), Intuitive V2 & Mini Superpack Controller PR0650/680-SUP (6.1a, 25-11-25), Intuitive V2 & Mini Super Pack Multi INV Controller (1.4, 16-04-25)
  133. Resource Data Management – Intuitive Bitzer IQ Rack Commissioning/User Guide PR0650-BITZIQ (rev. 3.1), Modbus alarms and CM-RC-01 sub alarm numbers
  134. Resource Data Management – ML Controller Case Controller Commissioning/User Guide PR0123 (document revision 3.4a)
  135. Temperzone – UC6 (Unit Controller 6) and pGD1 Service Terminal: Functionality Overview and Service Interface via the pGD
  136. ActronAir – Troubleshooting Guide Advance / Aires / VCC and GENESIS Units, Doc. 9590-2015-03 Ver. 12 (260219); Error Codes, 9590-0000-05
  137. ActronAir – Troubleshooting Guide Advance / Aires / VCC and GENESIS Units, Doc. 9590-2015-03 Ver. 12 (260219); Error Codes, 9590-0000-05
  138. ActronAir – Serene DS Series Troubleshooting, Doc. No. 9590-2037-03 Ver. 1 (251119); Aspire DS Troubleshooting, Doc. No. 9590-2031-03 Ver. 1; MultiElite DS Series Troubleshooting, Doc. No. 9590-2036-03 Ver. 2 (251022); Cascade DS Series Owner's Manual, Doc. No. 9590-4032 Ver. 1 (250610); R-32 Cassette 2 Owner's Manual, Doc. No. 9590-4016 Ver. 2 (220616); Universal Wired Remote Controller WC-03 Installation and Owner's Manual, Doc. No. 9590-4029 Ver. 8 (251104)
  139. ActronAir – Nexus Touch Controller WTC-01 Installation and Commissioning Guide, Doc. No. 9590-3039-02 Ver. 2 (251120)
  140. ActronAir – UltraSlim Ducted Split System Owner's Manual, Doc. No. 9590-4015 Ver. 1 (220608)
  141. True – Commercial Refrigeration General Control Guide, TEC_TM_001 / P#811072 (Rev. C, 2025-09-03); Beverage-Air – Installation and Operating Instructions (Danfoss ERC 112): CT 809-154A, BZ 809-236A Rev. D, WTFCS 48–96 809-256A, WTFCS 36 809-177A Rev. D, SM 809-186A, UCRF 809-175A, WTCTCS 809-260A, UCF 809-174A Rev. D, DW 809-184A
  142. True – Commercial Refrigeration General Control Guide, TEC_TM_001 / P#811072 (Rev. C, 2025-09-03)
  143. True – Commercial Refrigeration General Control Guide, TEC_TM_001 / P#811072 (Rev. C, 2025-09-03)
  144. True – Commercial Refrigeration General Control Guide, TEC_TM_001 / P#811072 (Rev. C, 2025-09-03)
  145. True – Commercial Refrigeration General Control Guide, TEC_TM_001 / P#811072 (Rev. C, 2025-09-03); True – Owner's Manual Retail Merchandiser TRM2M/TRM3M/TRM4M, 842860 Rev. H
  146. True – Commercial Refrigeration General Control Guide, TEC_TM_001 / P#811072 (Rev. C, 2025-09-03)
  147. True – Service Manual True Ice TI/TCIM, 857284 Rev. A (EN; also ES and FR editions)
  148. Beverage-Air – Installation and Operating Instructions, Hydrocarbon DW Deep Well Refrigerators, 809-184A
  149. Taylor – Operator Manuals C300 (op and opNP editions), C302, C303/C314, Models 0345/346/349/355
  150. Taylor – Service Manual C392, C393, C394
  151. Taylor – Operator Manuals C708/C716 (R449A), C708 Heat Treatment Shake Freezer (R449A), C606 Combination Freezer (R449A)
  152. Taylor – Operator Manuals C709/C717, C712, C713 (R449A), C612 Combination Freezer
  153. Taylor – Operator Manual Model 0736
  154. Taylor – Operator Manuals Model ISI-161TH (095616, November 2025, updated 2026-07-14) and ISI-161TI (095614)
  155. Taylor – Operator Manuals Icetro ISI-301TH and ISI-300TA (324027102, 2026-04-24), ISI-271THS/SHS (324022907)
  156. Taylor – Operator Manual R160
  157. Taylor – Operator Manual R200
  158. Taylor – Operator Manual R280
  159. Hillphoenix – Installation & Operations Manuals, display cases (Dixell XR03CX/XR04CX controller section): CF-R/CF-FS-R/CF-S-R (rv1-v2), BMD-R/BMD-D (rv3), OB-R, HVI-3-406R/408R (v2), HVI-4-406R/408R, HVI-4-406S (rv1), HTPT-R (rv6), CNZLA/CNEZLA R-290 (rv4), PT-R/PT-R-RRS (rv3), SMD-R (rv2), DLPF-R (rv6), PF-48/51/54/72-R (rv6), SD-H-R, SD-RG, SSA-R/SSF-R/SSAW-R (rv3), SSD-R-LT, BLF-R/BLF-D (rv3), BLF-SR/BLF-SD (rv3), QC-24/30/35-R (rv5)
  160. Hillphoenix – Installation & Operations Manual CF-SC (R-290), rv3 (Carel MPXzero alarm table); same controller in ONIZVA (R-290) and JNRZHSA/JNRBHSA (R-290) P119505H rev 9.0
  161. Hillphoenix – Installation & Operations Manual SMD-H/Deli, rv4 (Carel iJF IJFHS*/IJFHL* alarm table)
  162. HTPG – Troubleshooting Guide EcoNet Enabled Unit Coolers, HTPG0425_TSG (04/2025)
  163. CPC/HTPG – E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers, 026-1610 Rev 10 (06-APR-2010)
  164. Krack – Installation, Operation, and Service Manual KR-A2L Series Compact Evaporator/Unit Cooler, P/N 3227890
  165. LAE electronic – Instructions for use BR1-27, BR1-28, BR5-A (2022), BR5-B, BD1-28, CD25 (02-08-2024)
  166. LAE electronic – Instructions for use AT1-5 and AT2-5 (EN/IT)
  167. Pego – Scheda elettronica 202BASE guide (ITA-ENG-FRE-ESP-GER-NED, 01-24)
  168. alpha innotec – Betriebsanleitung Trinkwarmwasser-Wärmepumpen Innenaufstellung BWP 190S/BWP 260S, 83034800eDE (OE02:961-2105)
  169. alpha innotec – Betriebsanleitung Trinkwarmwasserwärmepumpe Innenaufstellung WWB 190, 83023900cDE (OE04:221-2106)
  170. Vaillant – uniTOWER plus VIH QW 190/6 E, Operating and installation and maintenance instructions, 0020291511_03 (16.12.2024)
  171. Vaillant – aroSTOR plus VWL B/BM 200/6 and 260/6 230V, Installation and maintenance instructions, 8000034704_01 (27.10.2025)
  172. Baltimore Aircoil – Nexus Modular Hybrid Cooler Operation & Maintenance Manual, RGOMNXF-01
  173. Baltimore Aircoil – Vertex Evaporative Condenser Operation & Maintenance Manual, EC fan controls (VRC-xxxxA-xxxxN-xB), RGOMVRCA01 (2025-05-29)
  174. Baltimore Aircoil – TrilliumSeries Adiabatic Cooler TRF Operation & Maintenance Manual, RGOMTRF303 R5.0 (2024-08-06)
  175. IVT – Larmkoder, ivt.se/support/larmkoder (all models listed on the page), checked 2026-11-03
  176. IVT – Larmkoder, ivt.se/support/larmkoder (all models listed on the page), checked 2026-11-03
  177. IVT – Larmkoder, ivt.se/support/larmkoder (all models listed on the page), checked 2026-11-03
  178. IVT – Larmkoder, ivt.se/support/larmkoder (all models listed on the page), checked 2026-11-03
  179. IVT – Larmkoder, ivt.se/support/larmkoder (all models listed on the page), checked 2026-11-03
  180. Fujitsu General – Troubleshooting Guide 2019 (manufacturer's service document), US models, table "Wall Mounted 9–36 (…RL/CL/RLS/RLX)"; Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 1 "Current Models" (wall-mounted ASY/ASYA/ASYB); lamp colours also in Fujitsu Error Codes – Air Conditioner Hardwired Remote Controller System Error Codes (publisher unknown, not a Fujitsu document, undated)
  181. Fujitsu General – Troubleshooting Guide 2019 (manufacturer's service document), US models, table "Multi-Zones"
  182. Fujitsu General – Troubleshooting Guide 2019 (manufacturer's service document), US models, table "AOU24RML, AOU24RML1, AOU36RML, AOU36RML1"
  183. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 2 "Wired Remote Control Models" and p. 3 "Wired Controllers – Fault diagnostics"; Fujitsu General – Troubleshooting Guide 2019 (manufacturer's service document), US models, column "Wired Remote"; Fujitsu Error Codes – Air Conditioner Hardwired Remote Controller System Error Codes (publisher unknown, not a Fujitsu document, undated) (codes 00–09)
  184. Fujitsu Error Codes – Air Conditioner Hardwired Remote Controller System Error Codes (publisher unknown, not a Fujitsu document, undated); Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 3 "Wired Controllers – Fault diagnostics" and p. 4 code table
  185. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 1 "Current Models" (left-hand table)
  186. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 1 "Wall Mounted Multi Models"
  187. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 2 "Outdoor PCB Fault Codes"
  188. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 2 "Outdoor PCB Fault Codes"
  189. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 2 "Outdoor PCB Fault Codes" (non-inverter)
  190. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 2 "Inverter Multi AOY30"
  191. Fujitsu – Fujitsu Trouble Shooting Guide (UK edition, undated, R22 era, 4 pages), p. 3 (model references A–G) and p. 4 "Wireless Remote Control Models – Diagnostics"
  192. NTF – Technical Documentation, NTF ice makers families (SL, IC, CM, FRM/IW/DSS/ID, SLF/SLT, CVC/CV, GM/MGT, IFT, SM), 2019 (sections dated 2006–2018); GM360 Line, electric circuit and wiring diagram
  193. Staff – Operating and maintenance instructions, ice cream machines: batch freezers (IT/EN/SV, Swedish edition supplied by ABM AB), doc. 8000107710; ABM AB – Snabbguide för användande av STAFF BFX glassmaskiner (quick guide)
  194. Staff – Operating and maintenance instructions, ice cream machines: batch freezers (IT/EN/SV, Swedish edition supplied by ABM AB), doc. 8000107710
  195. Hitachi – Self-Contained Air Conditioners RUA-NP4ATS…RUA-NP10ATS (R410A), Installation, Operation and Maintenance Instructions Manual 65MP3197-A2 (Bosch Home Comfort Philippines); undated, PDF file created 2025
  196. NTF – Technical Documentation, NTF ice makers families (SL, IC, CM, FRM/IW/DSS/ID, SLF/SLT, CVC/CV, GM/MGT, IFT, SM), 2019 (sections dated 2006–2018); 'Linear ice makers series' service training slides, pages 104–135
  197. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 4-2-4/4-2-5 (p. 04-06–04-07) and trouble shooting 1–11, 82–84 (p. 04-12–04-22, 04-79–04-81)
  198. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 4-2-6 (p. 04-07) and trouble shooting 77–81 (p. 04-76–04-79)
  199. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 4-1-1 and 4-2-1 (p. 04-01, 04-03)
  200. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 2-6-1 (p. 02-11–02-12), 4-1-2, 4-2-2, 4-2-3 (p. 04-02, 04-04, 04-05) and trouble shooting 12–48 (p. 04-23–04-57)
  201. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 4-3-3 (2), trouble shooting 59–64 (p. 04-65–04-67)
  202. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 4-3-3 (3), trouble shooting 65–76 (p. 04-68–04-75)
  203. Fujitsu General – AIRSTAGE J-II Service Manual, small VRF system (R410A; outdoor units AJ*A36/45/54LALH), undated, ch. 4-3-3 (1), trouble shooting 55–58 (p. 04-63–04-64)

Trademarks belong to their owners. co2piping.com is not affiliated with or endorsed by the manufacturers.

Disclaimer: This text is guidance, not legal advice. It summarises regulations and standards and does not replace the official text. Always check the version in force and local requirements.
New feature – please report any errors: Report a bug