Portugal: refrigerant rules – Decreto-Lei 145/2017, APA certification and reporting
What applies in Portugal in addition to the EU F-gas Regulation: Decreto-Lei 145/2017, certification of technicians and companies, annual reporting to APA and registration fees.
Key points
- The EU Regulation 2024/573 applies directly in Portugal. The national law is Decreto-Lei n.º 145/2017 of 30 November 2017, and the competent authority is the Agência Portuguesa do Ambiente (APA) [1][2].
- Technicians are certified under Implementing Regulation (EU) 2024/2215 by certification bodies recognised by APA, among others in the categories A1, A2 and E [2][7].
- Companies that install and service refrigeration, air-conditioning and heat pump equipment for others must be certified [4].
- Operators report to APA every year by 31 March, and purchases and sales of F-gas are reported by 30 June of the following year [5][8].
- According to APA, Decreto-Lei 145/2017 is being revised to follow the new EU regulation (as of December 2025) [6].
The EU regulation applies directly
The EU Regulation (EU) 2024/573 on fluorinated greenhouse gases applies directly in Portugal [1]. It sets the requirements for leak checks, records, recovery, and the EU bans on new products and on certain refrigerants for servicing [1].
Leak checks are required for systems with 5 tonnes CO2e or more, and 10 tonnes CO2e for hermetically sealed systems. The intervals depend on the charge in tonnes CO2e [1]:
| Charge (tonnes CO2e) | Without leak detection | With leak detection |
|---|---|---|
| 5 to under 50 | every 12 months | every 24 months |
| 50 to under 500 | every 6 months | every 12 months |
| 500 or more | every 3 months | every 6 months |
Systems with 500 tonnes CO2e or more must have a leak detection system. After a leak has been repaired, a certified person must check the system again within one month [1].
Since 1 January 2025, F-gases with a GWP of 2500 or more may not be used to service any refrigeration equipment; military equipment and equipment cooling products below −50 °C are exempt. Reclaimed or recycled refrigerant may be used until the end of 2029 [1].
The national law: Decreto-Lei 145/2017
Decreto-Lei n.º 145/2017 (decree-law no. 145/2017) of 30 November 2017 implements the EU F-gas rules in Portugal. It has applied since 1 January 2018 and replaced Decreto-Lei n.º 56/2011 [2]. It was corrected by Declaração de Retificação n.º 3-A/2018 [8].
The decree-law was written for the old Regulation (EU) No 517/2014. APA now applies it together with 2024/573, and in a document from December 2025 APA states that the decree-law is being revised [2][6][8].
The competent authority is the Agência Portuguesa do Ambiente (APA, Portuguese Environment Agency). In the Azores, the regional environment authority Direção Regional do Ambiente e Ação Climática (DRAAC) provides information on the rules [2][8].
Certification of technicians
Technicians who work on the refrigerant circuit must be certified. Certificates are issued by certification bodies recognised by APA, and recognition is applied for electronically [2]. The basis today is Implementing Regulation (EU) 2024/2215, which replaced (EU) 2015/2067 [7].
- A1: technicians for F-gases and hydrocarbons [7].
- A2: equipment with less than 3 kg, or hermetically sealed systems with less than 6 kg [7].
- E: leak checks without breaking into the refrigerant circuit [7].
If you hold a certificate from another EU country, APA can recognise it. APA has a specific procedure for persons and companies who want to work in Portugal with a certificate from another Member State [6].
Certification of companies
Companies that install, repair, maintain or decommission stationary refrigeration, air-conditioning and heat pump equipment containing F-gases must be certified under 2024/2215. The requirement in Article 13(1) of Decreto-Lei 145/2017 only applies when the company provides services to others [4].
Companies are certified by four certification bodies, CERTIF, eiC, SGS and APCER, using technical specifications published by APA [4].
Buying and selling refrigerant
According to APA, F-gases may only be sold to and bought by companies holding the relevant certificates, or companies with certified staff [5]. The seller must keep records of buyers, with certificate numbers and quantities bought [1][5].
Purchases and sales are reported to APA once a year. The data for a calendar year must be submitted by 30 June of the following year [5].
Annual reporting and fees
Operators of equipment containing F-gases report to APA every year through the electronic platform SILiAmb. The data for the previous year must be submitted by 31 March [8].
Portaria n.º 92/2020 (ministerial order) sets the fees for the platform. Registering, for example, stationary air-conditioning equipment and heat pumps costs EUR 17, and registering purchases and sales costs EUR 24. APA collects the fees [3].
Changes 2024–2026
- 11 March 2024: the EU Regulation 2024/573 entered into force [1].
- 1 January 2025: ban on F-gases with a GWP of 2500 or more for servicing any refrigeration equipment [1].
- December 2025: APA publishes a new procedure for recognising certificates from other EU countries and states that Decreto-Lei 145/2017 is being revised [6].
- 31 March 2026: deadline for operators' report on 2025 [8].
- 30 June 2026: deadline for the report on purchases and sales in 2025 [5].
Practical checklist
- Convert the charge to tonnes CO2e to see whether the system needs leak checks and leak detection [1].
- Make sure technicians hold a 2024/2215 certificate in the right category, and that foreign certificates are recognised by APA [6][7].
- If the company works for customers, it must be certified by one of the recognised certification bodies [4].
- Only buy and sell refrigerant to and from certified companies, and keep the data for the 30 June report [5].
- Report equipment data in SILiAmb by 31 March [8].
- After every leak repair, make sure a new check is done within one month [1].
Calculate it yourself
Terms in this article
Sources
- Regulation (EU) 2024/573 on fluorinated greenhouse gases – EUR-Lex
- Diário da República – Decreto-Lei n.º 145/2017, de 30 de novembro (gases fluorados com efeito de estufa)
- Diário da República – Portaria n.º 92/2020 (taxas da plataforma de gases fluorados)
- Agência Portuguesa do Ambiente (APA) – Certificação de Empresas (AVACR)
- Agência Portuguesa do Ambiente (APA) – Compra e Venda de Gases Fluorados
- Agência Portuguesa do Ambiente (APA) – Procedimento para o reconhecimento da certificação obtida noutro Estado-Membro (dezembro 2025)
- IPAC – Procedimento de certificação de técnicos de gases fluorados (Regulamento de Execução (UE) 2024/2215)
- Direção Regional do Ambiente e Ação Climática (Açores) – Gases Fluorados com Efeito de Estufa