Netherlands: refrigerant rules – F-gas Besluit, BRL 100, BRL 200 and STEK

What applies in the Netherlands on top of the EU F-gas Regulation: the national Besluit and Regeling, BRL 200 personal certificates, BRL 100 company certificates and key dates 2025–2029.

Last checked: Last changed: – Updated the validity of company certificates (Regeling art. 13b), the exception for older ammonia, CO2 and hydrocarbon qualifications, and pressure equipment inspections.

Key points

  • The EU Regulation 2024/573 applies directly in the Netherlands. It is complemented by the Besluit and the Regeling gefluoreerde broeikasgassen en ozonlaagafbrekende stoffen, which were aligned with the new EU regulation in 2025 [1][2][3][4].
  • Technicians need a personal certificate under BRL 200, and companies and sole traders a company certificate under BRL 100. Both are listed in the Centraal Register Techniek [5].
  • Since 29 September 2025 a certificate is also required for work with hydrocarbons, CO2 and ammonia. An older vocational competence certificate for ammonia, flammable refrigerants or CO2 is accepted until 12 March 2029 at the latest [2][6].
  • BRL 100 version 3.0 formally enters into force on 31 August 2026. New exams under BRL 200 version 2.0 have been held since 29 March 2026 [3][6][7].
  • Old personal certificates remain valid until 12 March 2029 at the latest. The new certificates are valid for seven years [6].
  • The enforcing authority is the Inspectie Leefomgeving en Transport (ILT) [5].

The EU regulation applies directly, the Dutch rules complement it

The EU Regulation (EU) 2024/573 on fluorinated greenhouse gases has applied directly in the Netherlands since 11 March 2024 [1]. The requirements for leak checks, records, recovery, labelling and the EU bans on new products and servicing come from it. Leak checks are required for systems with 5 tonnes CO2e or more, and 10 tonnes CO2e for hermetically sealed systems [1].

The national basis is the Besluit gefluoreerde broeikasgassen en ozonlaagafbrekende stoffen (decree on fluorinated greenhouse gases and ozone-depleting substances) [2]. It is detailed in the Regeling gefluoreerde broeikasgassen en ozonlaagafbrekende stoffen (ministerial regulation of the same name) [3]. The Besluit was amended by a decree of 14 July 2025, published in Staatsblad 2025, 199, to implement (EU) 2024/573 and Regulation (EU) 2024/590 on ozone-depleting substances [4].

Enforcement lies with the Inspectie Leefomgeving en Transport (ILT, Human Environment and Transport Inspectorate). Among other things, the ILT checks that technicians and companies hold the right certificates. Anyone who suspects that someone works with refrigerants without a valid certificate can report it to the ILT [5].

Two certificates: person and company

The Netherlands distinguishes between personal certificates and company certificates. The requirements are set out in two assessment guidelines (beoordelingsrichtlijnen, BRL) referred to by the Regeling and issued by Rijkswaterstaat [3]:

CertificateWhoCurrent version
BRL 200 (persoonscertificaat)The technician working on the systemVersion 2.0 of 5 December 2025
BRL 100 (bedrijfscertificaat)The company or sole traderVersion 3.0 of 5 December 2025

Technicians obtain their personal certificate from an examination body. Certified persons and companies are listed in the Centraal Register Techniek (CRT), where clients can check them [5].

New from 2025: natural refrigerants too

The new EU regulation extends the training and certification requirements to work with alternatives to F-gases [1]. In the Netherlands, personal certification has been required since 29 September 2025 also for work with hydrocarbons, carbon dioxide (R744) and ammonia (R717) [6].

The new system has the certificate categories A1, A2, B, C, D and E. Since 29 March 2026 exams are held under BRL 200 version 2.0, and the transition period in BRL 200 applies only to the NH3 and CO2 exams. For those, an extended transition applied until 1 July 2026 [6].

Existing certificates remain valid under the conditions on which they were issued, but no later than 12 March 2029. By then every technician must hold a new certificate in the right category. The new certificates are valid for seven years [6].

An old F-gas certificate is not enough for work with hydrocarbons, CO2 or ammonia. Check that the technician holds the right category for the refrigerant before work starts, especially on CO2 systems [6]. Exception: for work involving only ammonia, a flammable refrigerant or CO2, a valid vocational competence certificate (vakbekwaamheidsbewijs) counts as equivalent until 12 March 2029 at the latest, if the exam met at least the minimum requirements under Article 10(8) of the EU regulation (Besluit, Article 18(5)) [2].

The company certificate BRL 100 version 3.0

BRL 100 version 3.0 formally enters into force on 31 August 2026. Until then, certification bodies may only audit and issue certificates under version 2.0 [7]. Under Article 13b of the Regeling (in force 10 October 2026), a company certificate issued before 1 September 2026 under BRL 100 version 2.0 remains valid until a certification body has decided whether the company meets the requirements [3]. The BRL transition rules set 31 August 2028 as the latest date [7]. During the transition, staff working on systems must meet the requirements of BRL 200 version 2.0 [7].

STEK (the industry certification scheme for refrigeration and air-conditioning companies) becomes a stand-alone scheme alongside BRL 100. The STEK requirements in the version of 19 March 2026 enter into force on 1 September 2026. New applications after that date are assessed only against that version [8].

Key dates

DateWhat happens
11 March 2024EU Regulation 2024/573 applies [1]
14 July 2025Amending decree to the Besluit adopted, Staatsblad 2025, 199 [4]
29 September 2025Certificate also required for hydrocarbons, CO2 and ammonia [6]
5 December 2025BRL 100 v3.0 and BRL 200 v2.0 adopted [3]
29 March 2026Exams under BRL 200 v2.0 [6]
31 August 2026BRL 100 v3.0 formally enters into force [7]
1 September 2026The stand-alone STEK scheme enters into force [8]
31 August 2028Latest date for company certificates under BRL 100 v2.0 according to the BRL transition rules [7]; the Regeling ties their validity to the body's decision [3]
12 March 2029Old personal certificates expire at the latest [6]

Leak checks and records

Leak checks follow the EU regulation directly. The interval depends on the refrigerant charge in tonnes CO2e and is extended if the system has a leak detection system [1]. After a repair, the system must be checked again at the earliest after 24 hours of operation and no later than one month after the repair [1]. Leak checks may only be carried out by persons holding the right certificate [1][5].

Pressure equipment: inspection before use and re-inspection

Refrigeration systems are also pressure equipment. Under the Warenwetbesluit drukapparatuur 2016, equipment designated by ministerial regulation must be inspected before first use (keuring voor ingebruikneming) and after each installation at a new location, and re-inspected later (herkeuring) [10]. Article 2 of the Warenwetregeling drukapparatuur 2016 designates, among others [9]:

  • vessels with a gas of fluid group 1 in category III and IV (and category I and II if the gas is unstable, very toxic or explosive);
  • vessels with a gas of fluid group 2 in category III and IV;
  • piping with a gas of fluid group 1 in category II and III;
  • piping with a gas of fluid group 2 in category III.

The categories follow from the classification under the Pressure Equipment Directive. Vessels and piping with liquids are designated at certain categories as well. The inspections are done by an NL-conformiteitsbeoordelingsinstantie (Dutch conformity assessment body) [9][10].

Practical checklist

  1. Check in the Centraal Register Techniek that both the technician (BRL 200) and the company (BRL 100) are certified [5].
  2. Make sure technicians working with CO2, ammonia or hydrocarbons hold a certificate in the right category [6].
  3. Plan renewal of old personal certificates before 12 March 2029 [6].
  4. Prepare the company for audits under BRL 100 version 3.0 from 31 August 2026 [7].
  5. Convert the charge into tonnes CO2e to set the leak check interval, for example with the GWP calculator [1].
Read the current text on wetten.overheid.nl. The ILT (ilent.nl) and IPLO (iplo.nl) publish current information on certification, transition rules and enforcement [2][3][5][6][7].

Calculate it yourself

Terms in this article

Sources

  1. Regulation (EU) 2024/573 on fluorinated greenhouse gases – EUR-Lex
  2. wetten.overheid.nl – Besluit gefluoreerde broeikasgassen en ozonlaagafbrekende stoffen (BWBR0037088)
  3. wetten.overheid.nl – Regeling gefluoreerde broeikasgassen en ozonlaagafbrekende stoffen (BWBR0037094)
  4. Staatsblad 2025, 199 – Besluit van 14 juli 2025 tot wijziging van het Besluit gefluoreerde broeikasgassen en ozonlaagafbrekende stoffen
  5. Inspectie Leefomgeving en Transport (ILT) – Certificaten voor werken met F-gassen en ozonlaagafbrekende stoffen
  6. IPLO (Informatiepunt Leefomgeving) – Eisen aan natuurlijke personen (monteurs)
  7. IPLO – Toelichting overgangsregeling BRL 100 v3.0
  8. STEK – Overgangsregeling STEK Bedrijfscertificering (2026)
  9. wetten.overheid.nl – Warenwetregeling drukapparatuur 2016 (BWBR0038317)
  10. wetten.overheid.nl – Warenwetbesluit drukapparatuur 2016 (BWBR0038083)
Disclaimer: This text is guidance, not legal advice. It summarises regulations and standards and does not replace the official text. Always check the version in force and local requirements.