CO2 (R744) transcritical systems: a practical service guide

How to service transcritical CO2 systems safely: pressures, dry ice and the triple point, trapped liquid, recovery, charging, testing and the EU rules for certificate B.

Last checked: Last changed: – New guide.

Key points

  • CO2 has its critical point at 31 °C and 73.8 bar and its triple point at -56.6 °C and 5.2 bar. Above the first it is a supercritical fluid, below the second it forms dry ice [1][4].
  • In transcritical operation the discharge pressure is typically 80-120 bar, and the standstill pressure of a stopped warm system can be much higher than the normal suction pressure [1][2].
  • CO2 is an A1 refrigerant with a practical limit of 0.1 kg/m3 in EN 378, but it is an asphyxiant that collects at floor level. Detectors and ventilation are needed where a leak can exceed the limit [2][4][7].
  • Never charge liquid into a system below the triple point pressure, and never leave liquid trapped between closed valves [2][3].
  • CO2 is not an F-gas, so the leak check duty of Regulation (EU) 2024/573 does not apply to it. Technicians still need a certificate, type B for CO2 [5][6].

What is different with CO2

R744 behaves differently from HFCs at both ends of its range. The critical point is 31 °C and 73.8 bar. On warm days the heat rejection in the gas cooler takes place above that pressure, so the refrigerant does not condense but cools as a supercritical fluid. This is called transcritical operation [1]. The triple point is -56.6 °C and 5.2 bar (absolute). Below that pressure there is no liquid, only solid and gas, so CO2 that is expanded or vented too far turns into dry ice at about -78 °C [1][4].

ValueFigureWhy it matters when servicing
Critical point31 °C, 73.8 barAbove it there is no liquid and no clear liquid level [1]
Triple point-56.6 °C, 5.2 bar abs (about 4.2 bar gauge)Below it dry ice forms, which can block hoses and vent lines [2][4]
Discharge pressure, transcriticaltypically 80-120 barComponents, hoses and tools must be rated for it [1][2]
Cylinder pressure at 20 °C57.3 barHigher than the working pressure of some parts of the system [3][4]

A typical supermarket or industrial system has a gas cooler on the high-pressure side, a receiver (flash tank) at intermediate pressure, and compressors for low and medium temperature. The flash gas formed in the expansion is handled by a bypass valve or by a parallel compressor, which is more efficient in warm climates [8]. The CO2 copper and steel calculators size the pipework for these pressures.

Safety before you start

  • Asphyxiation. CO2 is odourless and heavier than air, so it collects low in machinery rooms, pits and cold rooms. The 8-hour exposure limit is 5,000 ppm [2]. At about 10 % in air a person can lose consciousness in less than a minute [4].
  • Practical limit. CO2 is class A1 and the EN 378 practical limit is 0.1 kg/m3 [4][7]. Where a leak can exceed it in an occupied space, permanent detection with an alarm is required [2]. Mount the detector low, not at breathing height [3].
  • Pressure relief. Relief valves on the receiver and other vessels may discharge on a fault, for example after a power failure. The outlet must go outdoors, and dry ice can form there [2]. See the article on EN 13136 relief devices.
  • Standstill pressure. A stopped system warms up and pressurises. On some systems the standstill pressure is above the maximum rated suction pressure. Auxiliary cooling or a relief valve then limits it [2][3]. Read the pressure before you open anything.
  • PPE. Wear gloves and goggles. Contact with solid or liquid CO2 gives freeze burns [2][4]. Use a personal CO2 detector when working in low spaces [4].
Trapped liquid CO2 is a burst hazard. As a rule of thumb the pressure of liquid trapped between closed valves rises by about 10 bar for every 1 °C. An example from Copeland: liquid at -10 °C and 44 bar reaches about 240 bar after a 20 °C rise [2]. Never close liquid in between two valves, or into a hose.

Service steps

  1. Assess the situation. Read the pressures, check that the detector works and that the room is ventilated. Do a risk analysis of the job before you start; it is part of what a certified technician must be able to do [6].
  2. Use rated equipment. Hoses, manifolds, gauges and recovery equipment must be rated for the pressure of the part you connect to. Use high-pressure hoses with an anti-whip cable [2][4].
  3. Isolate and recover. Close the section off, with a relief path for any liquid that may be trapped. Recover the CO2 into a suitable cylinder. If venting cannot be avoided, vent outdoors, away from people, and monitor the pressure. Copeland advises venting in liquid form to avoid dry ice [2].
  4. Test. Pressure test with dry nitrogen, strength first and then tightness. The Danfoss guide gives 1.43 × PS as the test pressure [1]; the details are in the guide to pressure testing. Then do a leak check with a CO2 detector, since CO2 is already in the air [3]. See the leak check guide.
  5. Evacuate. CO2 tolerates very little water: about 10 ppm is a suitable maximum, and free water gives ice crystals and acids. Evacuate thoroughly; a molecular sieve filter drier helps [1]. See the evacuation guide.
  6. Break the vacuum with vapour. After evacuation the system is below the triple point. Charging liquid then makes dry ice. Charge vapour until the pressure is above the triple point and as the manufacturer instructs, and only then switch to liquid [2][3].
  7. Charge slowly. The maximum pressure of some systems, such as cascade systems and parts of booster systems, is below the cylinder pressure. Charge slowly so that relief valves do not open [2].
  8. Check and document. Start the system and check pressures, the gas cooler setpoint and the receiver pressure against the manual. Write the service report.
The Danfoss guide states that an oil-filled vacuum pump can be used with ester oil for all refrigerants, including CO2 [1]. For compressor oil type and oil change, follow the compressor manufacturer; no general rule is given here.

Rules in the EU

  • R744 is not an F-gas. The F-gas Regulation covers the substances listed in its Annexes I and II, and CO2 is not one of them [5]. The leak check duty in Article 5 applies to equipment with those gases [5], so it does not apply to a CO2-only system.
  • Competence is still required. Article 10 of (EU) 2024/573 requires certification for installation, maintenance, repair and decommissioning, and covers the relevant alternatives to F-gases, including natural refrigerants [5]. Implementing Regulation (EU) 2024/2215 sets the types: A1 and A2 for F-gases and hydrocarbons, B for CO2, C for ammonia (Article 3(2)). Unless exempted, the holder must have the certificate for the activity [6].
  • What the B exam covers. The test includes pressure and vacuum tests, safe removal and charging of R744, risk analysis, gas detection and PPE, and the dry ice formed at the triple point (Annex I, heading 13) [6]. Brazing may be done by a person who has the national qualification under supervision (Article 3(3)(a)) [6].
  • Pressure equipment and safety. The Pressure Equipment Directive 2014/68/EU and EN 378 apply to the system regardless of the refrigerant, and national inspection rules may add requirements. See the articles on PED and on EN 378. Whether and how certificate B is required is decided by each Member State, so check the national article.

Typical faults and where to look next

Faults are best found by comparing the pressure and temperature readings with the setpoints of the pack controller, for example the Danfoss AK-PC 782 or Carel controllers. Parameter names and alarm codes differ between makers. Look them up in the Troubleshooting app and in the controller manual instead of guessing.

Checklist

  • Valid certificate for CO2 (type B in the EU) and a risk analysis done.
  • Detector working, room ventilated, gloves, goggles and a personal detector in use.
  • Pressures read before opening; standstill pressure considered.
  • Hoses, manifold and recovery equipment rated for the pressure.
  • No liquid trapped between closed valves.
  • Vapour first when charging an evacuated system, then liquid.
  • Pressure test, leak check and evacuation done and recorded.
  • Relief valve outlets clear and led outdoors.
Manufacturer manuals and local rules decide. Verify certificate and inspection requirements with your national authority, and check the current text on EUR-Lex [5][6].

Calculate it yourself

Terms in this article

Sources

  1. Danfoss – Transcritical Refrigeration Systems with Carbon Dioxide (CO2), application guide
  2. Copeland – CO2 as a Refrigerant: Five Potential Hazards of R-744
  3. Copeland (Emerson) – CO2 Refrigeration Fundamentals: Servicing Tips
  4. Climalife – Best practice for handling high pressure cylinders R-744
  5. Regulation (EU) 2024/573 on fluorinated greenhouse gases – EUR-Lex
  6. Implementing Regulation (EU) 2024/2215 on certificates for natural and legal persons – EUR-Lex
  7. EN 378-1:2016+A1:2020 Refrigerating systems and heat pumps – Safety and environmental requirements – Part 1
  8. Carel – R744 innovations from Japan, part 2 (R744.com article on parallel compression and flash gas bypass)
Disclaimer: This text is guidance, not legal advice. It summarises regulations and standards and does not replace the official text. Always check the version in force and local requirements.