co2piping.com

Comfort Cooling – Offices and Homes

Cooling load per room and for the whole home or office, proposed air conditioning units and refrigerant, with the rooms drawn in plan.

Project

.html
File
Share and print

The file is a link file: double-click it to open the project in your browser, or choose it with Open. Older .json files can still be opened.

All inputs are shown.

Use, country and system

Design climate

Design day: clear sky, the outdoor temperature reaches its maximum at 15:00 solar time. Times are solar time.

Building

Ventilation and infiltration

Rooms

Rooms are drawn side by side in the plan; exterior facades, windows and units as entered.

Design

Liquid line sizes used: 1/4" (Ø 6.35 × 0.8 · ID 4.75), 3/8" (Ø 9.52 × 0.8 · ID 7.92), 1/2" (Ø 12.70 × 0.8 · ID 11.10), 5/8" (Ø 15.88 × 1.0 · ID 13.88).
A link or link file holds the whole project: anyone who gets it can open it. Do not share it if the project is confidential.
Disclaimer: Estimate only. Cooling loads are calculated with a simplified method based on recognised practice (EN ISO 52016-1 / ASHRAE RTS / VDI 2078); no country prescribes this method by law. Equipment selection, refrigerant charge limits (EN 378 / ISO 5149 / IEC 60335-2-40 / ASHRAE 15) and installation must be checked by a qualified, certified installer. Refrigerant rules shown are for the selected country and date and may change.

Plan: rooms, units and refrigerant lines

Drag rooms, windows and indoor units
Drag a room to move it (it snaps to the edges of the other rooms), drag a window along its wall, drag an indoor unit inside its room; a locked room stays put. Click a room to find its card. Thick lines: exterior walls; blue: windows; red: refrigerant lines, only horizontal and vertical with 90° tees.

Cooling load per room

Units, circuits and refrigerant charge

Next step: pipe sizing and charge in the refrigerant apps

Rules for the country

Laws and regulations with source and status (checked 2026-11-05). Status: verified = read in the official text; secondary = authority or trade material; not verified = to be checked.

How the app calculates

Sun: solar position for the 21st of the design month at the given latitude (solar time); ASHRAE clear-sky model with the monthly constants A, B and C; diffuse radiation on walls with the factor Y, ground reflectance 0.2. With automatic month, the warm half-year is tried (April–October north, October–April south) with the design temperatures 2.5 K lower per month from the warmest (an assumption for temperate climates); each room keeps its worst month.

Outdoor temperature over the day: design dry-bulb minus the daily range times ASHRAE's hourly profile (maximum at 15:00); outdoor humidity from the wet-bulb (constant over the day).

Walls and roof: sol-air temperature with α/h_o 0.026 (light), 0.039 (medium) or 0.052 m²K/W (dark) and −3.9 K for the roof; conduction with a time lag of 3, 6 or 9 h and a decrement factor of 0.7, 0.4 or 0.2 by construction mass. Windows: g × angle factor × direct + 0.9 × g × diffuse, times the shading factor Fc; conduction U·A·Δt.

Heat gains become cooling load: the radiant part (sun 100 %, behind internal blinds 45 % and curtains 50 %; window conduction 46 %, or 33 % when g > 0.5; people 60 %, lighting 50 % (non-recessed luminaire), walls 46 %, roof 60 %, equipment 30 %) through a periodic exponential series with ratio 0.3, 0.5 or 0.7 by construction mass – a simplification of the radiant time series (2021 ASHRAE Handbook—Fundamentals (SI), ch. 18, Tables 1, 3 and 14; ch. 15, Tables 14A–G for the internal shading), not its tabulated factors. People: sensible and latent heat by activity (ch. 18, Table 1), for a 24 °C room and rounded to 5 W; at 27 °C the sensible part is about 20 % lower and the latent part correspondingly higher (note to Table 1). Outdoor air: sensible with heat recovery, latent from the humidity difference.

Units: next catalogue size above the room or circuit load with margin; multi-split and VRF outdoor units on the simultaneous peak of the rooms served. Charge: typical factory charge per kW plus the liquid line beyond the pre-charged length (7.5 m per split; VRF all of it) times the liquid density at 40 °C. Flammable refrigerants: m1/m2/m3 = 4/26/130 m³ × LFL (× 1.5 for A2L) and an estimate of m_max for the smallest room.

Sources

  • ASHRAE Handbook—Fundamentals: ch. 14 Climatic design information, ch. 15 Fenestration, ch. 18 Nonresidential cooling and heating load calculations (RTS), ch. 1 Psychrometrics. People, radiant fractions and internal shading checked against the 2021 edition (SI): ch. 18, Tables 1, 3 and 14 (Table 14 after Nigusse 2007; Table 3 after Fisher and Chantrasrisalai 2006, LED after Zhou et al. 2016) and ch. 15, Tables 14A–G (same values as the 2009 edition, ch. 15, Tables 13A–G); other chapters not verified
  • ASHRAE clear-sky model constants A, B, C (Fundamentals 1997 ch. 29 / 2005 ch. 31)
  • EN ISO 52016-1 (energy needs and loads, hourly method), VDI 2078:2015 (cooling load) – good practice, not law
  • EN 16798-1 (indoor environment, outdoor air rates), EN ISO 7730 (thermal comfort)
  • EN 378-1 annex C and IEC 60335-2-40:2024 annex GG (charge limits, h0) – paid standards, used as facts only
  • Regulation (EU) 2024/573 Annex IV points 7–9, Art. 11 and 13; Implementing Regulation (EU) 2024/2215; (EU) 206/2012, 626/2011, 2016/2281
  • USA 40 CFR 84.54, 40 CFR 82 subpart F and G (SNAP), 10 CFR 430.32; Canada SOR/2016-137, SOR/2016-311; Australia OPSGGM Regulations 1995
  • Sweden BFS 2024:8, AFS 2023:12; Germany ArbStättV, GModG; England Building Regulations Part O; Japan フロン排出抑制法, 高圧ガス保安法, 建築物省エネ法
  • Liquid densities: CoolProp 8.0.0; GWP and LFL: the GWP app of this site (IPCC AR4/AR6, (EU) 2024/573, ISO 817)

Frequently asked questions

How many kW of air conditioning does a room need?

It depends mostly on the sun through the windows, the people and the equipment. An office room often needs 60–120 W/m², a living room with large south or west windows more. Enter the room with its windows and orientation: the tool gives the peak load in kW and BTU/h and the next unit size.

What is the difference between sensible and latent load?

Sensible load raises the air temperature (sun, walls, lights, equipment, people's dry heat). Latent load is moisture from people and humid outdoor air, which the unit has to condense. The ratio sensible/total (SHR) shows how much of the capacity goes to drying.

Single split, multi split or VRF – which one?

One room: single split. A few rooms with one outdoor unit: multi split (often up to 5 indoor units and about 12.5 kW). Many rooms or offices: VRF with branch pipes. There is no law about it; the choice also depends on noise, space for the outdoor unit and the refrigerant rules above 12 kW.

Is R32 still allowed in the EU?

Yes, but in steps. In a new single split air-to-air up to 12 kW, R32 (GWP 675) may be installed until 2028-12-31 (Regulation (EU) 2024/573 Annex IV 9(c)). Air-to-water split up to 12 kW: from 2027 GWP below 150, which in practice means R290. VRF and split above 12 kW: R32 and R454B until 2032-12-31.

Can R290 (propane) be used in a split system?

In the EU yes, if the unit is tested for it and the room is large enough: the charge must stay within the limit for the smallest room served (EN 378-1, IEC 60335-2-40). In the USA, R-290 is accepted under SNAP only in self-contained room air conditioners, not in split systems.

Why does the whole building need less than the sum of the rooms?

The rooms have their peaks at different times: east rooms in the morning, west rooms in the afternoon. A multi split or VRF outdoor unit is sized on the highest simultaneous sum, which is usually lower than the sum of the room peaks.

Assumptions: Clear design day with steady-periodic conditions; no thermal bridges, no partitions to unconditioned rooms, no ground floor losses; latent loads from people and outdoor air only; sea-level air; times are solar time.

Disclaimer: Estimate only. Cooling loads are calculated with a simplified method based on recognised practice (EN ISO 52016-1 / ASHRAE RTS / VDI 2078); no country prescribes this method by law. Equipment selection, refrigerant charge limits (EN 378 / ISO 5149 / IEC 60335-2-40 / ASHRAE 15) and installation must be checked by a qualified, certified installer. Refrigerant rules shown are for the selected country and date and may change.

Help

Enter the rooms with their windows per facade; the load, the units and the refrigerant rules follow at once.

1. Use, country and date

  • The country chooses the refrigerant rules, the certification and the comfort rules shown, and the default indoor temperature.
  • The planned installation date decides whether a refrigerant is allowed, in transition (yellow) or prohibited (red).
  • System: "automatic" proposes split, multi-split or VRF from the number of rooms and the load; you can choose any type yourself.

2. Climate

  • Choose a city or type the design outdoor temperature (for example ASHRAE 0.4 % cooling dry-bulb) and the coincident wet-bulb for your site.
  • The daily range gives the outdoor temperature over the design day; the month and the latitude give the sun.
  • The city values are indicative and not yet checked against the ASHRAE station data: use your own design data for a real project.

3. Building and ventilation

  • U-values of walls, roof and windows, the g-value of the glass, the outside colour and the construction mass (light, medium, heavy).
  • Orientation: turn the building so that the plan's top side faces the right direction (0° = north, 90° = east).
  • Ventilation: outdoor air per person and per m², heat recovery, and infiltration (air changes per hour). Choose "separate air handling unit" if the outdoor air is cooled elsewhere.

4. Rooms

  • One card per room: size, people and activity, lighting, equipment, other loads and how the indoor unit is mounted.
  • Tick the exterior facades and give the window area and the shading of each; tick "roof above" for a top-floor room.
  • Tap a room in the drawing to find its card.

5. Results, files and print

  • Cards: design load, sum of the rooms, proposed system and refrigerant; the room table and the units with charge, smallest room and status.
  • Red and yellow lines: refrigerant rules for the selected country and date; flammable refrigerants above m1 are warned.
  • Project row at the top of the inputs: Save, Save as…, Open…, Copy link, Print and Export (PDF, Excel, CSV, image). The printout has the report first and the plan on a page of its own.