Sun: solar position for the 21st of the design month at the given latitude (solar time); ASHRAE clear-sky model with the monthly constants A, B and C; diffuse radiation on walls with the factor Y, ground reflectance 0.2. With automatic month, the warm half-year is tried (April–October north, October–April south) with the design temperatures 2.5 K lower per month from the warmest (an assumption for temperate climates); each room keeps its worst month.
Outdoor temperature over the day: design dry-bulb minus the daily range times ASHRAE's hourly profile (maximum at 15:00); outdoor humidity from the wet-bulb (constant over the day).
Walls and roof: sol-air temperature with α/h_o 0.026 (light), 0.039 (medium) or 0.052 m²K/W (dark) and −3.9 K for the roof; conduction with a time lag of 3, 6 or 9 h and a decrement factor of 0.7, 0.4 or 0.2 by construction mass. Windows: g × angle factor × direct + 0.9 × g × diffuse, times the shading factor Fc; conduction U·A·Δt.
Heat gains become cooling load: the radiant part (sun 100 %, behind internal blinds 45 % and curtains 50 %; window conduction 46 %, or 33 % when g > 0.5; people 60 %, lighting 50 % (non-recessed luminaire), walls 46 %, roof 60 %, equipment 30 %) through a periodic exponential series with ratio 0.3, 0.5 or 0.7 by construction mass – a simplification of the radiant time series (2021 ASHRAE Handbook—Fundamentals (SI), ch. 18, Tables 1, 3 and 14; ch. 15, Tables 14A–G for the internal shading), not its tabulated factors. People: sensible and latent heat by activity (ch. 18, Table 1), for a 24 °C room and rounded to 5 W; at 27 °C the sensible part is about 20 % lower and the latent part correspondingly higher (note to Table 1). Outdoor air: sensible with heat recovery, latent from the humidity difference.
Units: next catalogue size above the room or circuit load with margin; multi-split and VRF outdoor units on the simultaneous peak of the rooms served. Charge: typical factory charge per kW plus the liquid line beyond the pre-charged length (7.5 m per split; VRF all of it) times the liquid density at 40 °C. Flammable refrigerants: m1/m2/m3 = 4/26/130 m³ × LFL (× 1.5 for A2L) and an estimate of m_max for the smallest room.
It depends mostly on the sun through the windows, the people and the equipment. An office room often needs 60–120 W/m², a living room with large south or west windows more. Enter the room with its windows and orientation: the tool gives the peak load in kW and BTU/h and the next unit size.
Sensible load raises the air temperature (sun, walls, lights, equipment, people's dry heat). Latent load is moisture from people and humid outdoor air, which the unit has to condense. The ratio sensible/total (SHR) shows how much of the capacity goes to drying.
One room: single split. A few rooms with one outdoor unit: multi split (often up to 5 indoor units and about 12.5 kW). Many rooms or offices: VRF with branch pipes. There is no law about it; the choice also depends on noise, space for the outdoor unit and the refrigerant rules above 12 kW.
Yes, but in steps. In a new single split air-to-air up to 12 kW, R32 (GWP 675) may be installed until 2028-12-31 (Regulation (EU) 2024/573 Annex IV 9(c)). Air-to-water split up to 12 kW: from 2027 GWP below 150, which in practice means R290. VRF and split above 12 kW: R32 and R454B until 2032-12-31.
In the EU yes, if the unit is tested for it and the room is large enough: the charge must stay within the limit for the smallest room served (EN 378-1, IEC 60335-2-40). In the USA, R-290 is accepted under SNAP only in self-contained room air conditioners, not in split systems.
The rooms have their peaks at different times: east rooms in the morning, west rooms in the afternoon. A multi split or VRF outdoor unit is sized on the highest simultaneous sum, which is usually lower than the sum of the room peaks.